Download English - Det

Survey
yes no Was this document useful for you?
   Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Document related concepts

Fault tolerance wikipedia , lookup

Flexible electronics wikipedia , lookup

Switch wikipedia , lookup

Opto-isolator wikipedia , lookup

Two-port network wikipedia , lookup

Regenerative circuit wikipedia , lookup

Surface-mount technology wikipedia , lookup

Integrated circuit wikipedia , lookup

Crossbar switch wikipedia , lookup

Earthing system wikipedia , lookup

Network analysis (electrical circuits) wikipedia , lookup

National Electrical Code wikipedia , lookup

Electrical wiring in the United Kingdom wikipedia , lookup

Transcript
ORDERING INFORMATION
SPECIFICATION DATA
When ordering, please specify:
Eagle Quantum™ Premier
EQ2200IDC Initiating Device Circuit
Initiating Device Circuit
Specify:
Enclosure material — Aluminum or stainless steel
Number of ports — 5 or 6
Port size — 3/4 inch NPT or 25 mm
Certification — FM/CSA/CENELEC/CE.
EQ2200IDC
For additional information or for assistance in
designing a system to meet the needs of a specific
application, please contact:
Detector Electronics Corporation
6901 West 110th Street
Minneapolis, Minnesota 55438 USA
Operator: (952) 941-5665 or (800) 765-FIRE
Customer Service: (952) 946-6491
Fax: (952) 829-8750
Web site: www.detronics.com
E-mail: [email protected]
DESCRIPTION
Functioning as part of the fire detection portion of the
safety system, the EQ2200IDC Initiating Device
Circuit (IDC) provides two supervised digital inputs
for use with dry contact inputs from devices such as
relays, pushbuttons, key switches, etc. The IDC
supports ANSI/NFPA 72 Class B Style B supervised
input circuits. Each circuit uses its own end of line
(EOL) resistor for monitoring circuit continuity.
The specifications contained within this document
subject to change without notice.
The output of the IDC is a status message that is sent
along the communication loop to the controller.
System response to the message is determined at the
time of configuration. The IDC supports ANSI/NFPA
72 Class A, Style 7 communication with the controller.
The IDC logs time, date, and circuit number each
time one of its input circuits is activated. Data for the
last eight events is stored in non-volatile memory.
The amber LED is provided for factory diagnostic
purposes and is not used by the customer. Illumination
of the amber LED normally indicates a failure in the
communication chip.
Replacement of the
communication module circuit board is required.
STATUS LEDS
ADDRESSABILITY
Three LEDs are located at the center of the
communication module circuit board and are visible
through the window on the cover.
Device identification is accomplished by setting
switches on an eight position DIP switch (valid
address range is 5 to 250).
The green LED serves as a power-on indicator and is
the only LED illuminated during normal operation (no
faults or alarms occurring).
ENCLOSURE
RED BY UL AN
D
STE
B
GI
SI
RE
ALARM LOG
S
230
RM
TERMINAL WIRING BOARD
FI
E RE D F
T E ED
R
82
6
.A
I
I
R EG
ST
O
REG
N
IR M
ISO 9001
The red LED is used to indicate an alarm or fault
condition. The flashing rate of the red LED indicates
the following conditions:
The explosion-proof, water-tight NEMA/Type 4X
enclosure is designed for use in a variety of
hazardous locations.
5 • N O.
25
On steady =
Blinking =
one of the inputs is active
fault condition such as an open input
circuit or not configured.
All external wiring is connected to screw terminal
connectors on the terminal wiring board located
inside the junction box.
Detector Electronics Corporation
6901 West 110th Street • Minneapolis, Minnesota 55438 • Operator (952) 941-5665 or (800) 765-FIRE
Customer Service (952) 946-6491 • Fax (952) 829-8750 • www.det-tronics.com • E-mail: [email protected]
2.2
©Detector Electronics Corporation 2003
8/06
90-1121
INSTALLATION
NOTE
For complete instructions regarding wiring and
installation, refer to manual number 95-8533 for
Eagle Quantum Premier systems or manual
number 95-8470 for Eagle Quantum systems.
11
14
10
13
8
7
2
3
4
5
6
WARNING
The hazardous area must be de-classified prior to
removing a junction box cover with power applied.
Special Conditions for Safe Use (X):
The device has an ambient temperature rating for
performance of –40°C to +75°C.
1. Remove the cover from the junction box.
SHIPPING WEIGHT—
Aluminum:
6 pounds (2.7 kilograms).
Stainless Steel: 10 pounds (4.5 kilograms).
2. Remove the communication module from the
junction box. Connect external system wiring to the
appropriate terminals on the terminal block inside
the junction box. See Figure 2 for terminal block
location and Figure 3 for terminal identification. The
input to the IDC consists of one or more normally
open switches (momentary pushbuttons are not
recommended), with a 10K ohm, 1/4 watt EOL
resistor in parallel across the last switch. An EOL
resistor must be installed on both IDC inputs
(including unused inputs). Wiring impedance must
not exceed 500 ohms.
SPECIFICATIONS
INPUT VOLTAGE—
24 vdc nominal, 18 to 30 vdc. Overvoltage of 10%
(33 vdc) will not cause damage to the equipment.
0.28
(0.71)
POWER REQUIREMENTS—
4.0 watts maximum.
4.7
(11.8)
3.4
(8.6)
INPUTS—
Two supervised digital inputs (switch or relay
contacts). A 10 kohm EOL resistor is required for
each input.
A1870
Figure 2—IDC Terminal Wiring Board Mounted
in Six-Port Junction Box
IDC
5.2
(13.2)
TEMPERATURE RANGE—
Operating:
–40°F to +167°F (–40°C to +75°C)
Storage:
–67°F to +185°F (–55°C to +85°C).
2.7
(6.8)
2
+
3
–
4
A
5
B
6
EOL (10K)
EOL (10K)
COM 2
DIMENSIONS—
See Figure 1.
B2045
Figure 1—Dimensions of IDC in Inches (Centimeters)
(Six Port Model Shown)
90-1121
–
8
13
–
A
9
12
+
B
10
11
+
24 VDC
COM 1
A1871
Figure 3—Terminal Configuration for Initiating Device Circuit
6. Inspect the junction box O-ring to be sure that it is
in good condition and properly installed. Lubricate
the O-ring and the threads of the junction box cover
with a thin coat of an appropriate grease to ease
installation and ensure a watertight enclosure. The
recommended lubricant is a silicone free grease,
available from Det-Tronics. Place the cover on the
junction box. Tighten only until snug. Do not over
tighten.
2.2
14
1
2
3
4
5
6
7
8
OPEN
BINARY
VALUE
1
2
4
8
16 32 64 128
1
2
3
4
OPEN
}
1.28
(3.25)
7
COM SHIELDS
5. Install the communication module inside the
junction box. Be sure that the keyed ribbon cable is
properly connected.
6.6
(16.8)
2
–
CIRCUIT 2
4. Set the node address for the device. Each device
on the LON/SLC must be assigned a unique
address. This is accomplished by setting DIP
switches on the module’s circuit board. See Figure
4. Each rocker switch has a specific binary value.
The node address is equal to the added value of all
closed rocker switches. All open switches are
ignored. The valid address range is from 5 to 250.
Refer to the Eagle Quantum system manual (form
95-8470) for additional information.
HUMIDITY RANGE—
5 to 95% RH, non-condensing.
CERTIFICATION —
FM / CSA:
Class I, Div. 1, Groups B, C, D.
Class I, Zone 1, Group IIC.
Class II/III, Div. 1, Groups E, F, G.
Class I, Div. 2, Groups A, B, C, D (T4A).
Class I, Zone 2, Group IIC (T4).
Class II/III, Div. 2, Groups F & G (T4A).
NEMA/Type 4X.
1
3. Check the wiring to ensure proper connections.
0.32 (0.81) OVAL SLOT MOUNTING
(TYPICAL FOUR PLACES)
VIBRATION—
Meets MIL SPEC 810C, method 514.2, curve AW.
+
MANUAL PULL STATION
OR OTHER CONTACT DEVICE
CIRCUIT 1
IMPORTANT
Insulate the shields to prevent shorting to the
device housing or to any other conductor.
OUTPUTS—
Digital communication, transformer isolated (78.5
kbps).
2.2
GND
12
• Two Class B Style B supervised digital inputs.
• Field addressable.
• Unique patented fault isolation.
• Non-volatile memory for configuration and alarm logs.
• Utilizes state-of-the-art communication technology.
• Pass through communication circuitry on power loss.
• EMI hardened.
• FMR, CSA, CENELEC and CE Mark Certifications.
• FMR performance verified per ANSI/NFPA 72-1996.
• Compatible with Eagle Quantum Premier and Eagle
Quantum systems.
9
CENELEC/CE: ATEX/EMC Directive Compliant.
0539
II 2 G
EEx d IIC T4-T6
DEMKO 02 ATEX 131321X
T6 (Tamb = –55°C to +50°C).
T5 (Tamb = –55°C to +65°C).
T4 (Tamb = –55°C to +75°C).
IP66.
1
FEATURES
LEAVE IN
OPEN POSITION
NODE ADDRESS EQUALS THE ADDED VALUE
OF ALL CLOSED ROCKER SWITCHES
OPEN = OFF
CLOSED = ON
A1557
Figure 4—Field Device Address Switches
3
90-1121
INSTALLATION
NOTE
For complete instructions regarding wiring and
installation, refer to manual number 95-8533 for
Eagle Quantum Premier systems or manual
number 95-8470 for Eagle Quantum systems.
11
14
10
13
8
7
2
3
4
5
6
WARNING
The hazardous area must be de-classified prior to
removing a junction box cover with power applied.
Special Conditions for Safe Use (X):
The device has an ambient temperature rating for
performance of –40°C to +75°C.
1. Remove the cover from the junction box.
SHIPPING WEIGHT—
Aluminum:
6 pounds (2.7 kilograms).
Stainless Steel: 10 pounds (4.5 kilograms).
2. Remove the communication module from the
junction box. Connect external system wiring to the
appropriate terminals on the terminal block inside
the junction box. See Figure 2 for terminal block
location and Figure 3 for terminal identification. The
input to the IDC consists of one or more normally
open switches (momentary pushbuttons are not
recommended), with a 10K ohm, 1/4 watt EOL
resistor in parallel across the last switch. An EOL
resistor must be installed on both IDC inputs
(including unused inputs). Wiring impedance must
not exceed 500 ohms.
SPECIFICATIONS
INPUT VOLTAGE—
24 vdc nominal, 18 to 30 vdc. Overvoltage of 10%
(33 vdc) will not cause damage to the equipment.
0.28
(0.71)
POWER REQUIREMENTS—
4.0 watts maximum.
4.7
(11.8)
3.4
(8.6)
INPUTS—
Two supervised digital inputs (switch or relay
contacts). A 10 kohm EOL resistor is required for
each input.
A1870
Figure 2—IDC Terminal Wiring Board Mounted
in Six-Port Junction Box
IDC
5.2
(13.2)
TEMPERATURE RANGE—
Operating:
–40°F to +167°F (–40°C to +75°C)
Storage:
–67°F to +185°F (–55°C to +85°C).
2.7
(6.8)
2
+
3
–
4
A
5
B
6
EOL (10K)
EOL (10K)
COM 2
DIMENSIONS—
See Figure 1.
B2045
Figure 1—Dimensions of IDC in Inches (Centimeters)
(Six Port Model Shown)
90-1121
–
8
13
–
A
9
12
+
B
10
11
+
24 VDC
COM 1
A1871
Figure 3—Terminal Configuration for Initiating Device Circuit
6. Inspect the junction box O-ring to be sure that it is
in good condition and properly installed. Lubricate
the O-ring and the threads of the junction box cover
with a thin coat of an appropriate grease to ease
installation and ensure a watertight enclosure. The
recommended lubricant is a silicone free grease,
available from Det-Tronics. Place the cover on the
junction box. Tighten only until snug. Do not over
tighten.
2.2
14
1
2
3
4
5
6
7
8
OPEN
BINARY
VALUE
1
2
4
8
16 32 64 128
1
2
3
4
OPEN
}
1.28
(3.25)
7
COM SHIELDS
5. Install the communication module inside the
junction box. Be sure that the keyed ribbon cable is
properly connected.
6.6
(16.8)
2
–
CIRCUIT 2
4. Set the node address for the device. Each device
on the LON/SLC must be assigned a unique
address. This is accomplished by setting DIP
switches on the module’s circuit board. See Figure
4. Each rocker switch has a specific binary value.
The node address is equal to the added value of all
closed rocker switches. All open switches are
ignored. The valid address range is from 5 to 250.
Refer to the Eagle Quantum system manual (form
95-8470) for additional information.
HUMIDITY RANGE—
5 to 95% RH, non-condensing.
CERTIFICATION —
FM / CSA:
Class I, Div. 1, Groups B, C, D.
Class I, Zone 1, Group IIC.
Class II/III, Div. 1, Groups E, F, G.
Class I, Div. 2, Groups A, B, C, D (T4A).
Class I, Zone 2, Group IIC (T4).
Class II/III, Div. 2, Groups F & G (T4A).
NEMA/Type 4X.
1
3. Check the wiring to ensure proper connections.
0.32 (0.81) OVAL SLOT MOUNTING
(TYPICAL FOUR PLACES)
VIBRATION—
Meets MIL SPEC 810C, method 514.2, curve AW.
+
MANUAL PULL STATION
OR OTHER CONTACT DEVICE
CIRCUIT 1
IMPORTANT
Insulate the shields to prevent shorting to the
device housing or to any other conductor.
OUTPUTS—
Digital communication, transformer isolated (78.5
kbps).
2.2
GND
12
• Two Class B Style B supervised digital inputs.
• Field addressable.
• Unique patented fault isolation.
• Non-volatile memory for configuration and alarm logs.
• Utilizes state-of-the-art communication technology.
• Pass through communication circuitry on power loss.
• EMI hardened.
• FMR, CSA, CENELEC and CE Mark Certifications.
• FMR performance verified per ANSI/NFPA 72-1996.
• Compatible with Eagle Quantum Premier and Eagle
Quantum systems.
9
CENELEC/CE: ATEX/EMC Directive Compliant.
0539
II 2 G
EEx d IIC T4-T6
DEMKO 02 ATEX 131321X
T6 (Tamb = –55°C to +50°C).
T5 (Tamb = –55°C to +65°C).
T4 (Tamb = –55°C to +75°C).
IP66.
1
FEATURES
LEAVE IN
OPEN POSITION
NODE ADDRESS EQUALS THE ADDED VALUE
OF ALL CLOSED ROCKER SWITCHES
OPEN = OFF
CLOSED = ON
A1557
Figure 4—Field Device Address Switches
3
90-1121
ORDERING INFORMATION
SPECIFICATION DATA
When ordering, please specify:
Eagle Quantum™ Premier
EQ2200IDC Initiating Device Circuit
Initiating Device Circuit
Specify:
Enclosure material — Aluminum or stainless steel
Number of ports — 5 or 6
Port size — 3/4 inch NPT or 25 mm
Certification — FM/CSA/CENELEC/CE.
EQ2200IDC
For additional information or for assistance in
designing a system to meet the needs of a specific
application, please contact:
Detector Electronics Corporation
6901 West 110th Street
Minneapolis, Minnesota 55438 USA
Operator: (952) 941-5665 or (800) 765-FIRE
Customer Service: (952) 946-6491
Fax: (952) 829-8750
Web site: www.detronics.com
E-mail: [email protected]
DESCRIPTION
Functioning as part of the fire detection portion of the
safety system, the EQ2200IDC Initiating Device
Circuit (IDC) provides two supervised digital inputs
for use with dry contact inputs from devices such as
relays, pushbuttons, key switches, etc. The IDC
supports ANSI/NFPA 72 Class B Style B supervised
input circuits. Each circuit uses its own end of line
(EOL) resistor for monitoring circuit continuity.
The specifications contained within this document
subject to change without notice.
The output of the IDC is a status message that is sent
along the communication loop to the controller.
System response to the message is determined at the
time of configuration. The IDC supports ANSI/NFPA
72 Class A, Style 7 communication with the controller.
The IDC logs time, date, and circuit number each
time one of its input circuits is activated. Data for the
last eight events is stored in non-volatile memory.
The amber LED is provided for factory diagnostic
purposes and is not used by the customer. Illumination
of the amber LED normally indicates a failure in the
communication chip.
Replacement of the
communication module circuit board is required.
STATUS LEDS
ADDRESSABILITY
Three LEDs are located at the center of the
communication module circuit board and are visible
through the window on the cover.
Device identification is accomplished by setting
switches on an eight position DIP switch (valid
address range is 5 to 250).
The green LED serves as a power-on indicator and is
the only LED illuminated during normal operation (no
faults or alarms occurring).
ENCLOSURE
RED BY UL AN
D
STE
B
GI
SI
RE
ALARM LOG
S
230
RM
TERMINAL WIRING BOARD
FI
E RE D F
T E ED
R
82
6
.A
I
I
R EG
ST
O
REG
N
IR M
ISO 9001
The red LED is used to indicate an alarm or fault
condition. The flashing rate of the red LED indicates
the following conditions:
The explosion-proof, water-tight NEMA/Type 4X
enclosure is designed for use in a variety of
hazardous locations.
5 • N O.
25
On steady =
Blinking =
one of the inputs is active
fault condition such as an open input
circuit or not configured.
All external wiring is connected to screw terminal
connectors on the terminal wiring board located
inside the junction box.
Detector Electronics Corporation
6901 West 110th Street • Minneapolis, Minnesota 55438 • Operator (952) 941-5665 or (800) 765-FIRE
Customer Service (952) 946-6491 • Fax (952) 829-8750 • www.det-tronics.com • E-mail: [email protected]
2.2
©Detector Electronics Corporation 2003
8/06
90-1121