Download ACT20M Presentation - Weidmuller B2B Portal

Survey
yes no Was this document useful for you?
   Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project

Document related concepts

Electrification wikipedia, lookup

Mains electricity wikipedia, lookup

History of electric power transmission wikipedia, lookup

Power engineering wikipedia, lookup

Buck converter wikipedia, lookup

Switched-mode power supply wikipedia, lookup

Opto-isolator wikipedia, lookup

Alternating current wikipedia, lookup

Voltage optimisation wikipedia, lookup

Schmitt trigger wikipedia, lookup

Rectifier wikipedia, lookup

Variable-frequency drive wikipedia, lookup

Power inverter wikipedia, lookup

AC adapter wikipedia, lookup

Power over Ethernet wikipedia, lookup

Electric power system wikipedia, lookup

Audio power wikipedia, lookup

Amtrak's 25 Hz traction power system wikipedia, lookup

Control system wikipedia, lookup

Wireless power transfer wikipedia, lookup

Flip-flop (electronics) wikipedia, lookup

Power supply wikipedia, lookup

Standby power wikipedia, lookup

Transcript
ACT20M
6mm Signal Isolators and Converters
ACT20M – 1 & 2 channels in 6mm width !
 Phase 1…..10 models – isolators & converters
 Power rail option – minimizes cabling time
 Hazardous approvals (Class 1 Div 2, Zone 2 ATEX)
 Includes 2 channel options – in 6mm width !
 DIP switch settable - except UI (computer configurable)
 Wide ambient -25 to 70C
part no.
1176070000
1176080000
1176040000
1176050000
1176030000
1175980000
1176000000
1176010000
1175990000
1176020000
Description
ACT20M-CI-CO-ILP-S
ACT20M-2CI-2CO-ILP-S
ACT20M-CI-CO-OLP-S
ACT20M-2CI-2CO-OLP-S
ACT20M-UI-AO-S
ACT20M-CI-CO-S
ACT20M-AI-AO-S
ACT20M-AI-AO-E-S
ACT20M-CI-2CO-S
ACT20M-AI-2AO-S
ACT20M training
Function
1 channel passive current isolator
2 channel passive current isolator
1 channel OLP isolator
2 channel OLP isolator
Universal input converter/isolator
1 channel current isolator
1 channel convertor/isolator - DIP selectable
Economy Convertor/isolator - DIP selectable
Current Splitter/isolator
Current/voltage Splitter/isolator
Power
Input loop
Input loop
Output loop
Output loop
Auxiliary
Auxiliary
Auxiliary
Auxiliary
Auxiliary
Auxiliary
Page 2
From MAS to ACT20M….
Questions and Answers
What does the name mean?
ACT20M
Analog Conditioner Transmitter IP20 Micro
Why a new product family?
ACT20M replaces and expands the existing
MICROANALOG series – the functionality of which is
limited by having only 6 terminals. ACT20M has 8.
Will MAS range be replaced?
Some overlap exists - but probably not, as ACT20M is for
process customers, whereas MAS has been mainly for
factory / machinery customers.
When will ACT20M products be available?
There are 10 variants. End November 2011 we have 6
variants in Richmond stock.
Seite 3
ACT20M training
More performance in 6mm !
Expansion with 3 new functions
Dual OLP Isolators,
Universal Converter in 6mm,
Aux powered Splitters
Replacement and Improvement
of the existing MAS DC/DC select
Splitter with sensor supply
- Aux power permits power
for 2-wire transmitter
Wide temperature range:
-25…+70°C operating temperature
High galvanic isolation
300 V rated voltage,
2,5 kV test voltage
Worldwide application
international approvals cULus,
ATEX Zone 2, FM-Div. 2,, GL, DNV
Quick and easy configuration
by DIP-Switches or FDT/DTM
Software
Power supply via DIN-Rail-Bus
24 V supply via DIN-Rail
Seite 4
ACT20M training
High accuracy
of up to 0,05%
Who are the target customers for ACT20M?
 Process Industries, e.g….
 Oil & Gas (Production and transmission)
 Chemicals and Petro-chem
 Power, Paper & Pulp
 Iron & Steel, Cement
 Customers are:
 Systems Integrators
 Plant end-users (above)
 Package plant OEMs (separators, dryers, coolers, effluent
treatment, chemical dosing, pumping)
Page 5
ACT20M training
How does ACT20M compare?
Weidmuller
Phoenix
Red Lion
Omron
WAGO
ACT20M
MINI MCR
AIMA/IAMA/AFCM
K3FP Series
Series 857
10
14
3
10
9
Screw / Tension
Screw
Screw / Tension
Screw
Screw
Tension
Power rail option
Yes
Yes
No
Yes
No
Approvals - Normal
cULus, CE, DNV, GL
cULus, CE, GL
cULus, CE, GL
UL 508
CE, cULus, GL (pending)
Approvals - Hazloc
FM Div2, ATEX Zone 2
Typ. FM Div2
Typ. FM Div2
None
Div 2
-25 to 70C
-20 to 60C
-20 to 60C
-20 to 65C
-20 to 70C (/50C)
2.5kV
1.5kV
1.5kV
1.5kV
2.5kV
No. of models
Ambient temperature
Isolation
ACT20M training
Page 6
Typical application – ACT20M-AI-2AO-S
Hazardous Area
Safe Area
Division 2 or Zone 2 area
Power supply, e.g.
CP T SNT 90W 24V 3.8A
a.c.
Local display DI350
Remote PLC
DC power for tx
P S
+
0–5V output 1
4-20mA input from tx
Level
transmitter
Input
O/P 1
O/P 2
PLC and display
have passive
inputs
4-20mA output 2
ACT20M-AI-2AO-S
Use where the splitter’s
receivers have passive
inputs
ACT20M training
Page 7
Typical application – ACT20M-CI-2CO-S
Hazardous Area
Safe Area
Division 2 or Zone 2 area
Power supplies,
e.g. CP T SNT 90W 24V 3.8A
Local loop-powered
display DI350
Remote PLC
P S
4-20mA output 1
4-20mA input from tx
Level
transmitter
Input
O/P 1
O/P 2
PLC and display
have passive
inputs
4-20mA output 2
ACT20M-CI-2CO-S
Use where all signals are mA,
and the isolator’s receivers
have passive inputs
ACT20M training
Page 8
Typical application.... ACT20M-CI-CO-S
Control room PLC
+24Vdc
+24Vdc
In-head
2-wire tx
DC Power
Supply
DC power for tx
Passive input
P S
4-20mA
4-20mA
Input
O/P
Heat exchanger
ACT20M-CI-CO-S
Use where the field devices are
separately powered and the PLC
has a passive input.
ACT20M training
9
Typical application.... ACT20M-AI-AO-S
Control room PLC
+24Vdc
DC Power
Supply
DC power for tx
In-head
2-wire tx
P S
+17V
4-20mA
0-20mA
Input
O/P
ACT20M-AI-AO-S
Use where the field devices can
be powered from the isolator, and
the PLC has a passive analog
input.
Heat exchanger
ACT20M training
10
Typical application.... ACT20M-AI-AO-E-S
Control room PLC
Level tx
+24Vdc
+24Vdc
DC Power
Supply
P S
4-20mA
0-10V
Input
O/P
ACT20M-AI-AO-E-S
Use where mA/Volts conversion
is needed, the field devices are
separately powered, and the PLC
has a passive analog input.
ACT20M training
11
Typical application - ACT20M-UI-AO-S
Hazardous Area
Division 2 or Zone 2 area
Controller
+24VDC
3-wire
Pt100 probe
P S
Passive input
channel
4-20mA output
Input
O/P
ACT20M-UI-AO-S
Use where a mixture of inputs / converters are
needed (thermocouples, RTDs, Volts, mA) and
the receivers have passive inputs
Heat exchanger
ACT20M training
Page 12
Typical application – ACT20M-CI-CO-OLP-S
+24Vdc
DC Power for
field
instruments
Controller
+24Vdc
Active input cct –
powers the input
device
4-20mA
proportional to
flow
P S
I/P
4-20mA
Input
O/P
ACT20M-CI-CO-OLP-S
Flow Transmitter
2-wire, 4-20mA
Use where the field device is
separately powered and the
isolator is to be powered by it’s
receiver.
Process vessel
ACT20M training
Page 13
Typical application – ACT20M-2CI-2CO-OLP-S
Class 1 Division 2 or Zone 2 Area
Hazardous Area
Safe Area
+24Vdc
DC Power for
field
instruments
Active input ccts
– powers input
devices
4-20mA signals
proportional to
flow &
temperature
Controller
P S
I/P 1
4-20mA
Temperature transmitter
2-wire 4-20mA
Input
I/P 2
O/P 1
O/P 2
4-20mA
ACT20M-2CI-2CO-ILP-S
Flow Transmitter
2-wire 4-20mA
Use where the field devices are
separately powered and the
isolator is to be powered by it’s
receiver.
Process vessel
ACT20M-CI-CO-OLP-S
ACT20M training
Page 14
Typical application – ACT20M-CI-CO-ILP-S
+24Vdc
DC Power for
field
instruments
Controller
4-20mA
proportional to
flow
P S
I/P
Process vessel
Input
O/P
ACT20M-CI-CO-ILP-S
Flow Transmitter
2-wire 4-20mA
ACT20M training
Use where a separate isolator
power supply is not available,
or where the isolator is added
to the loop later.
Page 15
Typical application – ACT20M-2CI-2CO-ILP-S
Class 1 Division 2 or Zone 2 Area
Hazardous Area
Safe Area
+24Vdc
DC Power for
field
instruments
4-20mA signals
proportional to
flow &
temperature
Temperature transmitter
2-wire, 4-20mA
Controller
Passive input ccts
P S
I/P 1
Input
I/P 2
O/P 1
O/P 2
ACT20M-2CI-2CO-ILP-S
Flow Transmitter
2-wire, 4-20mA
Use where a separate isolator
power supply is not available,
or where the isolator is added
to the loop later. Receivers
should have passive inputs.
Process vessel
ACT20M-CI-CO-ILP-S
ACT20M training
Page 16
Seite 17
ACT20M training