Doepke
The experts in residual current protection technology
DATA SHEET
HS 3-230AC/40-20
with coil voltage 230 V AC
Article number 09980439
Internetlink
symbolic image
Function
Installation contactors are electromagnetically operated switches. If a control current flows through the magnetic coil, the main
circuit closes the magnetic energiser. As long as the control current flows, the switch-on position is maintained. If the control current
is interrupted, a spring forces the disconnection o return of the contacts to their original position. This design means that contactors
ensure a galvanic separation between the control circuit and the switched circuit whilst simultaneously allowing high currents to be
switched. Installation contactors are only designed in a limited way for release and must be protected against overload and short-circuits
by upstream protective devices. Installation contactors in series HS for installation in distribution boards are extremely quiet and have
very low-noise switching processes, are highly versatile thanks to their utilization categories and have a long mechanical and electrical
service life. The magnetic coil of this series is suitable for continuous operation (100% duty cycle). Devices in this design are operated with
a control voltage of 230 V AC.
Features
wide range of different contacts, high electrical and mechanical endurance, extremely quiet, suitable auxiliary switch and seal cap
available
Mounting
quick fastening to mounting rail, any installation position
Applications
Installation contactors are frequently used in residential and purpose-built buildings as well as industrial facilities. They take on the
switching of incandescent lamps, fluorescent lamps, transformers for halogen low-voltage lamps, mercury vapour high-pressure lamps
(HQL, HPL), metal halide lamps (HQI, HPI), sodium vapour, low and high-pressure lamps, storage heaters or drives (motors).
Notes
The designation for the devices in this series includes both the rated current (first group of digits) and the contact design (final group of
digits). A HS 25-31 therefore has a rated current of 25 A, three normally opened contacts and one normally closed contact, At ambient
temperatures above 40 °C, we recommend using the RD 05 spacer.
Accessories
HSH 11, HS P-40/63, RD 05
Technical Data
Technical Data
Series
Rated voltage (AC)
Rated frequency
Rated power (switch on)
rated power (retaining)
Specification
contact assignment (detailed)
Rated voltage (AC)
Overvoltage class
Rated current (AC)
2017_03_29
HS 3-230AC/40-20
HS 3
Control input
230 V
50 Hz/60 Hz
33 VA ... 45 VA
5 VA ... 7 VA
Load circuit
Switching contact
2 NO
400 V
I, II, III
40 A
doepke_09980439_dbl_en.pdf
1/3
Doepke
The experts in residual current protection technology
Technical Data
Rated insulation voltage
Switching frequency
Allowed utilization category
Power dissipation per pole AC-1
rated short-circuit current "r"
rated short-circuit current "Iq"
Rated voltage AC-1 (fix)
max. Output O1 Rated power
AC-1 230 V
Rated voltage AC-3 one-phase
(fixed)
max. Output O1 Rated power
AC-3 230 V
max. Output O1 rated power
glow lamps
max. Output O1 Rated power
fluorescent lamp compensated
max. Output O1 Rated
power fluorescent lamp not
compensated
max. Output O1 rated power
fluorescent lamps duo-switching
contact endurance AC-1
contact endurance AC-3
Duration of light arcs
Switching delay, open
Switching delay, close
Allowed types of wires
Max number of wires per
terminal
Cross section solid
Connecting capacity flexible
Cross section stranded
Allowed types of wires
Max number of wires per
terminal
Cross section solid
Connecting capacity flexible
Cross section stranded
General data description
Duty cycle
Operating position
Mechanical endurance
Electrical endurance
textual ambient temperature
Housing type
Mounting type
Housing material
Protection class
Width
2017_03_29
HS 3-230AC/40-20
440 V
max. 600 / h
AC-1, AC-2, AC-3
3W
3 kA
10 kA
230 V
9 kW
230 V
2.6 kW
6000 VA
2805 VA
2975 VA
5280 VA
100000 Schaltspiele
150000 Schaltspiele
10 ms ... 15 ms
6 ms ... 13 ms
11 ms ... 15 ms
Screw-type terminal top and bottom (Load circuit)
Aluminium conductors, Copper conductors, massive conductors, flexible conductors
1
1-wire: 2.5 mm² ... 25 mm²
1-wire: 2.5 mm² ... 16 mm²
1-wire: 2.5 mm² ... 25 mm²
Screw-type terminal top and bottom (Control input)
Aluminium conductors, Copper conductors, massive conductors, flexible conductors
1
1-wire: 0.75 mm² ... 2.5 mm²
1-wire: 0.5 mm² ... 2.5 mm²
1-wire: 0.75 mm² ... 2.5 mm²
General data
continuous operation (Duty cycle ≤ 100 %)
any
min. 10 · 10⁶ cycles
min. 1 · 10⁶ cycles
60°C when installed individually
Distributor housing
Mounting rail
Thermoplastic resin
IP20
52.5 mm
doepke_09980439_dbl_en.pdf
2/3
Doepke
The experts in residual current protection technology
Technical Data
HS 3-230AC/40-20
85 mm
65 mm
60 mm
3
EN 60715, EN 60947-4-1, VDE 0660-102
3
Height
Depth
Installation depth
Width (modules)
Design requirements/Standards
Degree of pollution according to
EN 60664
Dimensions
Wiring example
Dimensional drawing Group view
STEP file
Wiring diagram
2017_03_29
doepke_09980439_dbl_en.pdf