* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project
Download The display indication shall be in 2 languages
Fault tolerance wikipedia , lookup
Electrical substation wikipedia , lookup
Control theory wikipedia , lookup
Distributed control system wikipedia , lookup
Resilient control systems wikipedia , lookup
Rectiverter wikipedia , lookup
Protective relay wikipedia , lookup
Transformer specification (Low power transformer) Protection and control unit Since the Protection and Control unit is installed in the switchgear, it must meet the severest environmental withstand requirements, in particular: IEC standards: 60255-5 impulse withstand: 5 kV 60255-22-1 1Mhz wave: Class III 60255-22-4 fast transients: Class IV 61000-4-3 electromagnetic radiation: class III 60529 degree of protection: IP 52 on front panel 60255-21-1,2,3 vibration, shocks, earthquakes: class II 60068-2-52 Salt mist The operating temperature shall be between -25°C and + 70° C. One unit shall be designed to accommodate all types of control power supply voltages: 24, 48, 127 & 220 Vdc and 110 & 230 Vac. The design and manufacturing process shall be ISO 9001 certified. The Protection and Control Unit shall have UL and CSA certification. It should be possible to withdraw the unit without prior current circuit short-circuiting The control output relays shall be capable of withstanding steady state current of 8 A. Operating dependability The Protection and Control unit shall include: an internal function self-monitoring mechanism, which activates one fail-safe watchdog changeover contacts an automatic device for switching to the fail-safe position, disabling output controls when a major internal failure is detected indication of self test status of the device by LED and text. Installation The Protection and Control unit should be compact and easy to install reduced depth (<100 mm) remote optional modules shall be prewired Protection The Protection and Control Unit shall contain all the necessary protections for the specific application: Transformer protection 50/51 Phase overcurrent 50N/51N Earth fault (or neutral) 46 Unbalance / negative sequence 49 RMS thermal overload Thermostat / Buchholz Temperature monitoring Each protection device shall have wide setting ranges, in particular for current protections, providing a choice of curve types between definite time curve (DT), with time delay settings from instantaneous (50 ms) to 300 s, and IDMT curves (SIT, VIT, LTI, EIT, UIT, RI, IEC SIT / A, IEC VIT or LTI / B, IEC EIT / C, IEEE moderately inverse, IEEE very inverse, IEEE extremely inverse, IAC inverse, IAC very inverse, IAC extremely inverse) adjustable either by time delay or TMS factor. Phase overcurrent and earth fault protection shall have an adjustable timer hold to allow restriking faults detection. Earth fault protection shall integrate a harmonic 2 restraint, which can be inhibited or activated. Alternative overcurrent setting groups will be selectable by logical conditions to adapt fast protection plan change as well as remote setting facilities for thresholds and time delay adjustments. The unit shall allow for the use of upstream and downstream logic discrimination in order to discriminate correctly when used in a cascade scheme. Overload protection will be based on RMS current value (up to a minimum 17th harmonic) and will take into account the ambient temperature. Alternative overload setting groups will be selectable by logical conditions to adapt operating mode change. Setting shall be performed by the direct input of actual current values. Protection tripping shall be indicated on the front of the device by a LED and text indicating the cause of the fault. Metering Man Machine Interface (front panel) Each Protection and Control unit shall include the measurements needed for operation and commissioning, i.e. at least the following : RMS 3-phase current measurement residual current measurement average and maximum phase current demand measurement of fault current broken in each phase additional measurements such as unbalance ratio, thermal capacity used, ... The unit shall provide one of the measurement on an analog output The Protection and Control unit shall include a display unit that indicates: measurement values operating messages (choice of language English or local) device maintenance messages The display unit shall have as a minimum 2 lines for clear annunciation of alarm conditions. 8 Signals LEDs will be available for alarms and status, including: breaker position (open/closed), relay self test, phase fault and earth fault alarms. It shall be possible to customize the assignment of the signal LEDs. The display indication shall be in 2 languages English Local The Protection and Control unit shall include a keypad to allow to perform the following operations: display of metering and operating data, alarm messages clearing of alarms and resetting, acknowledgement access to protection settings access to the unit parameter settings Access to setting mode will be protected by 2 different customized passwords of at least 4 characters: 1 to protect access to the protection settings, the other to protect access to the unit parameter settings. It shall be possible to remote the MMI to allow installation of the Protection and Control unit in a different place than the MMI for the most advantageous location for operation & monitoring. Control and monitoring The Protection and Control unit shall include the logic inputs and outputs resources required for control of the breaking device (circuit-breaker or contactor) and for interfacing with the monitoring or logic process. The unit shall have at least 4 relay outputs, with extension capability up to 10 logic inputs and 8 relay outputs Extension of the number of logic inputs and outputs will be possible to : CB open and close control, whatever the type of shunt trip or undervoltage release coil control ANSI 69 / Inhibit closing Remote tripping As an option, monitoring of the circuit breaker for maintenance statistics purpose: operating time, charging time, trip circuit supervision (covering power supply, wiring and coil) cumulative total of tripping currents for 5 current ranges, operation counter, pressure (for SF6 circuit breakers) As an option, monitoring the temperature (motors, transformers) storage of information (even during control power supply outages). 1 analog output and 8 temperature sensor inputs will be available as an extension to the Protection and Control unit. Disturbance recording: Triggered on event (automatic or manual) Each record will allow to store data for at least 80 periods, 12 values per period, with a number of periods before the event according to the setup The content of the record will be, as a minimum, the date, channel characteristics, 4 current channels (I1, I2, I3, I0) and the digital inputs The number of records will be as a minimum 2 events The event format shall be COMTRADE 97 The unit will provide time-tagging of minimum 64 events within an accuracy of 1ms. Communication The Protection and Control unit will be supplied with a Communication interface option of the RS 485 type, up to 38 400 baud speed, Modbus Protocol. The response time for a control order will be less than 15 ms (time from order sent to the unit up to order acknowledgement) The Protection and Control unit will communicate the metering data, enable the remote readings of the protection settings, the remote setting of protection and the transfer of the disturbance recorded data. Remote control orders shall be carried out in 2 modes : Direct mode "SBO" (select before operate) mode A RS232 connection port shall be available in the front of the relay, allowing to communicate between the relay and a PC with the appropriate software. Software Appropriate software (using standard Windows 95 or NT operating system) will allow to collect: all metering and operating data, alarm messages breaker diagnostics data (cumulative tripping current, operating counter…) protection and parameter settings, logic status of inputs, outputs and signal LEDs. (download to/from the relay) disturbance recording: single or multi curve display, 2 pointers for differential measurement, zooming, printing. Transformer specification (Medium power transformer) Protection and control unit Since the Protection and Control unit is installed in the switchgear, it must meet the severest environmental withstand requirements, in particular: IEC standards: 60255-5 impulse withstand: 5 kV 60255-22-1 1Mhz wave: Class III 60255-22-4 fast transients: Class IV 61000-4-3 electromagnetic radiation: Class III 60529 degree of protection: IP 52 on front panel 60255-21-1,2,3 vibration, shocks, earthquakes: class II 60068-2-52 Salt mist The operating temperature shall be between -25°C and + 70° C. The Protection and Control unit range shall be designed to accommodate all types of control power supply voltages: 24, 48, 127 & 220 Vdc and 110 & 230 Vac. The design and manufacturing process shall be ISO 9001 certified. The Protection and Control Unit shall have UL and CSA certification. It should be possible to withdraw the unit without prior current circuit short-circuiting The control output relays shall be capable of withstanding steady state current of 8 A. Operating dependability The Protection and Control unit shall include: an internal function self-monitoring mechanism, which activates one fail-safe watchdog changeover contacts an automatic device for switching to the fail-safe position, disabling output controls when a major internal failure is detected indication of self test status of the device by LED and text. Installation The Protection and Control unit should be compact and easy to install reduced depth (<100 mm) remote optional modules shall be prewired Protection The Protection and Control Unit shall contain all the necessary protections for the specific application: Transformer protection 50/51 Phase overcurrent 50N/51N Earth fault (or neutral) 50BF Breaker failure 46 Unbalance / negative sequence 67 Directional overcurrent 67N/67NC Directional earth fault 49 RMS thermal overload 27 Undervoltage (phase-to-phase or phase-to-neutral) 59 Overvoltage (phase-to-phase or phase-to-neutral) 59N Neutral voltage displacement 47 Negative sequence overvoltage 81H Overfrequency 81L Underfrequency Thermostat / Buchholz Temperature monitoring Each protection device shall have wide setting ranges, in particular for current protections, providing a choice of curve types between definite time curve (DT), with time delay settings from instantaneous to 300 s, and IDMT curves (SIT, VIT, LTI, EIT, UIT, RI, IEC SIT / A, IEC VIT or LTI / B, IEC EIT / C, IEEE moderately inverse, IEEE very inverse, IEEE extremely inverse, IAC inverse, IAC very inverse, IAC extremely inverse) adjustable either by time delay or TMS factor. Phase overcurrent and earth fault protection shall have an adjustable timer hold to allow restriking faults detection. Earth fault protection shall integrate a harmonic 2 restraint, which can be inhibited or activated. Alternative overcurrent setting groups will be selectable by logical conditions to adapt fast protection plan change as well as remote setting facilities for thresholds and time delay adjustments. The unit shall allow for the use of upstream and downstream logic discrimination in order to discriminate correctly when used in a cascade scheme. Overload protection will be based on RMS current value (up to a minimum 17th harmonic) and will take into account the ambient temperature. The protection and control unit shall include learnt cooling time constant. Alternative overload setting groups will be selectable by logical conditions to adapt operating mode change. Setting shall be performed by the direct input of actual current values. Protection tripping shall be indicated on the front of the device by a LED and text indicating the cause of the fault. The protection and control unit shall include voltage transformer and current transformer circuit supervision. Metering Each Protection and Control unit shall include the Measurements needed for operation and commissioning, i.e. at least the following : RMS 3-phase current measurement residual current measurement average and maximum phase current demand measurement of fault current broken in each phase Measurement of voltage, frequency, power and energy. For power and energy data, the unit shall measure real and reactive values and takes into consideration the direction energy flow. In addition, the protection and control unit shall include 4 logic inputs allowing energy measurement by means of impulses coming from an external meter. additional measurements such as unbalance ratio, thermal capacity used, ... The unit shall provide one of the measurement on an analog output Man Machine Interface (front panel) The Protection and Control unit shall include a display unit that indicates: measurement values operating messages (choice of language English or local) device maintenance messages The display unit shall have as a minimum 2 lines for clear annunciation of alarm conditions. 8 Signals LEDs will be available for alarms and status, including: breaker position (opened/closed), relay self test, phase fault and earth fault alarms. It shall be possible to customize the assignment of the signal LEDs. The display indication shall be in 2 languages English Local The Protection and Control unit shall include a keypad to allow to perform the following operations: display of metering and operating data, alarm messages clearing of alarms and resetting, acknowledgement access to protection settings access to the unit parameter settings Access to setting mode will be protected by 2 different customized passwords of at least 4 characters: 1 to protect access to the protection settings, the other to protect access to the unit parameter settings. Control and monitoring It shall be possible to remote the MMI to allow installation of the Protection and Control unit in a different place than the MMI for the most advantageous location for operation & monitoring. The Protection and Control unit shall include the logic inputs and outputs resources required for control of the breaking devices (circuit-breaker or contactor) and for interfacing with the monitoring or logic process. The unit shall have at least 4 relay outputs, with extension capability up to 10 logic inputs and 8 relay outputs Extension of the number of logic inputs and outputs will be possible to : CB open and close control, whatever the type of shunt trip or undervoltage release coil control ANSI 69 / Inhibit closing Remote tripping Modification of the control logic program by using logic equation editor. storage of information (even during control power supply outages). As an option, monitoring of the circuit breaker for maintenance statistics purpose: operating time, charging time, trip circuit supervision (covering power supply, wiring and coil) cumulative total of tripping currents for 5 current ranges, operation counter, pressure (for SF6 circuit breakers) As an option, 8 or 16 temperature sensors inputs shall be available (motors, transformers, generators) Disturbance recording: Triggered on event (automatic or manual) Each record will allow to store data for at least 400 periods, 12 values per period, with a number of periods before the event according to the setup Total recording time will be 800 periods The content of the record will be, as a minimum, the date, channel characteristics, 4 current channels (I1, I2, I3, I0), 3 voltage channels and the digital inputs The event format shall be COMTRADE 97 The unit will provide time-tagging of minimum 200 events within an accuracy of 1ms. Communication The Protection and Control unit will be supplied with a Communication interface option of the RS 485 type, up to 38 400 baud speed, Modbus Protocol. The response time for a control order will be less than 15 ms (time from order sent to the unit up to order acknowledgement) The Protection and Control unit will communicate the metering data, enable the remote readings of the protection settings, the remote setting of protection and the transfer of the disturbance recorded data. Remote control orders shall be carried out in 2 modes : Direct mode Software "SBO" (select before operate) mode A RS232 connection port shall be available in the front of the relay, allowing to communicate between the relay and a PC with the appropriate software. Appropriate software (using standard Windows 95 or NT operating system) will allow to collect: all metering and operating data, alarm messages breaker diagnostics data (cumulative tripping current, operating counter…) protection and parameter settings, logic status of inputs, outputs and signal LEDs. (download to/from the relay) disturbance recording: single or multi curve display, 2 pointers for differential measurement, zooming, printing. Transformer specification (High power transformer) Protection and Control unit Since the Protection and Control unit is installed in the switchgear, it must meet the severest environmental withstand requirements, in particular: IEC standards: 60255-5 impulse withstand: 5 kV 60255-22-1 1Mhz wave: Class III 60255-22-4 fast transients: Class IV 61000-4-3 electromagnetic radiation: Class III 60529 degree of protection: IP 52 on front panel 60255-21-1,2,3 vibration, shocks, earthquakes: class II 60068-2-52 Salt mist The operating temperature shall be between -25°C and + 70° C. The Protection and Control unit range shall be designed to accommodate all types of control power supply voltages: 24, 48, 127 & 220 Vdc. The design and manufacturing process shall be ISO 9001 certified. The Protection and Control Unit shall have UL 508 certification. It should be possible to withdraw the unit without prior current circuit short-circuiting. The control output relays shall be capable of withstanding steady state current of 8 A. Operating dependability The Protection and Control unit shall include: an internal function self-monitoring mechanism, which activates one fail-safe watchdog changeover contacts an automatic device for switching to the fail-safe position, disabling output controls when a major internal failure is detected indication of self test status of the device by LED and text. Installation The Protection and Control unit should be compact and easy to install: reduced depth (<210 mm) remote optional modules shall be prewired Protection The Protection and Control Unit shall contain all the necessary protections for the specific application: Transformer protection 50/51 Phase overcurrent 50N/51N Earth fault (or neutral) 50BF Breaker failure 46 Unbalance / negative sequence 67 Directional overcurrent* 67N/67NC Directional earth fault* 32P Reverse real power 49 RMS thermal overload 24 Overfluxing 27 Undervoltage (phase-to-phase or phase-to-neutral) 27D Positive sequence undervoltage 27R Remanent undervoltage 59 Overvoltage (phase-to-phase or phase-to-neutral) 59N Neutral voltage displacement 47 Negative sequence overvoltage 81H Overfrequency 81L Underfrequency 87T 2 windings current differential* 64REF Restricted earth fault Thermostat / Buchholz Temperature monitoring * 87T or 67, 67N/67NC Each protection device shall have wide setting ranges, in Particular for current protections, providing a choice of curve types between definite time curve (DT), with time delay settings from instantaneous to 300 s, and IDMT curves (SIT, VIT, LTI, EIT, UIT, RI, IEC SIT / A, IEC VIT or LTI / B, IEC EIT / C, IEEE moderately inverse, IEEE very inverse, IEEE extremely inverse, IAC inverse, IAC very inverse, IAC extremely inverse) adjustable either by time delay or TMS factor. Phase overcurrent and earth fault protection shall have an adjustable timer hold to allow restriking faults detection. Earth fault protection shall integrate a harmonic 2 restraint, which can be inhibited or activated. Alternative overcurrent setting groups will be selectable by logical conditions to adapt fast protection plan change as well as remote setting facilities for thresholds and time delay adjustments. The unit shall allow for the use of upstream and downstream logic discrimination in order to discriminate correctly when used in a cascade scheme. Overload protection will be based on RMS current value (up to a minimum 13th harmonic) and will take into account the ambient temperature. Alternative overload setting groups will be selectable by logical conditions to adapt operating mode change. Setting shall be performed by the direct input of actual current Values. Protection tripping shall be indicated on the front of the device by a LED and text indicating the cause of the fault. The protection and control unit shall include voltage transformer and current transformer circuit supervision. Metering Each Protection and Control unit shall include the Measurements needed for operation and commissioning, i.e. at least the following: RMS 3-phase current measurement residual current measurement phase current demand and maximum demand measurement of fault current broken in each phase Measurement of voltage, frequency, power and energy. For power and energy data, the unit shall measure real and reactive values and takes into consideration the direction energy flow. In addition, the protection and control unit shall include 4 logic inputs allowing energy measurement by means of impulses coming from an external meter. additional measurements such as unbalance ratio, thermal capacity used, ... The unit shall provide one of the measurement on an analog output. User Machine Interface (front panel) The Protection and Control unit shall include a display unit that indicates: measurement values operating messages (choice of language English or local) device maintenance messages The display unit shall have as a minimum 2 lines for clear annunciation of alarm conditions. 8 Signals LEDs will be available for alarms and status, including: breaker position (opened/closed), relay self test, phase fault and earth fault alarms. It shall be possible to customize the assignment of the signal LEDs. The display indication shall be in 2 languages English Local The Protection and Control unit shall include a keypad to allow to perform the following operations: display of metering and operating data, alarm messages clearing of alarms and resetting, acknowledgement Access to setting mode will be protected by 2 different customized passwords of at least 4 characters: 1 to protect access to the protection settings, the other to protect access to the unit parameter settings. It shall be possible to remote the MMI to allow installation of the Protection and Control unit in a different place than the MMI for the most advantageous location for operation & monitoring. Control and monitoring The Protection and Control unit shall include the logic inputs and outputs resources required for control of the breaking devices (circuit-breaker or contactor) and for interfacing with the monitoring or logic process. The unit shall have at least 5 relay outputs, with extension capability up to 43 logic inputs and 23 relay outputs Extension of the number of logic inputs and outputs will be possible to : CB open and close control, whatever the type of shunt trip or undervoltage release coil control ANSI 69 / Inhibit closing Remote tripping Modification of the control logic program by using logic equation editor. storage of information (even during control power supply outages). As an option, monitoring of the circuit breaker for maintenance statistics purpose: operating time, charging time, trip circuit supervision (covering power supply, wiring and coil) cumulative total of tripping currents for 5 current ranges, operation counter, pressure (for SF6 circuit breakers) As an option, 8 to 16 temperature sensors inputs shall be available (motors, transformers, generators) Disturbance recording: Triggered on event (automatic or manual) Each record will allow to store data for at least 400 periods, 12 values per period, with a number of periods before the event according to the setup Total recording time will be 800 periods The content of the record will be, as a minimum, the date, channel characteristics, 4 current channels (I1, I2, I3, I0), 3 voltage channels and the digital inputs The event format shall be COMTRADE 97 The unit will provide time-tagging of minimum 200 events within an accuracy of 1ms. Communication The Protection and Control unit will be supplied with two communication ports providing RS 485 type, up to 38 400 baud speed, Modbus Protocol. The response time for a control order will be less than 15 ms. (time from order sent to the unit up to order acknowledgement) The Protection and Control unit will communicate the metering data, enable the remote readings of the protection settings, the remote setting of protection and the transfer of the disturbance recorded data. Remote control orders shall be carried out in 2 modes : Direct mode "SBO" (select before operate) mode Software A RS232 connection port shall be available in the front of the relay, allowing to communicate between the relay and a PC with the appropriate software. Appropriate software (using standard Windows 95 or NT operating system) will allow to collect: all metering and operating data, alarm messages breaker diagnostics data (cumulative tripping current, operating counter…) protection and parameter settings, logic status of inputs, outputs and signal LEDs. (download to/from the relay) disturbance recording: single or multi curve display, 2 pointers for differential measurement, zooming, printing.