Download 3. Service conditions - OPS Schneider Electric

Survey
yes no Was this document useful for you?
   Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Document related concepts

Resistive opto-isolator wikipedia , lookup

Switched-mode power supply wikipedia , lookup

Surge protector wikipedia , lookup

Opto-isolator wikipedia , lookup

Immunity-aware programming wikipedia , lookup

Rectiverter wikipedia , lookup

Transcript
Specification for Tender
565337578
General Specification for Clip-on Fault
Indicator for Medium Voltage Overhead
Line
Those requirements defines :
- General purpose
- fault passage indicator description
- Applicable standards
- basic features
Last update : 2017-06-28
-1-
Specification for Tender
565337578
Table of contents:
1. Scope …………………………………………………………………………………….........
p. 3
2. System parameters …………………………………………………………………………..
p. 3
3. Service conditions ………………………………………………………………………........
p. 3
4. Applicable standards ………………………………………………………………….….....
p. 3
5. Basic features ……………………………………………………………………...................
p. 4
5.1 General………………………………………………………………………….....................
p. 4 - 5
5.2 Equipment Housing……………………………………………………………………….....
p. 5
5.3 Clip-on clamps…………………………………………………………………………….....
p. 5
5.4 Installation…………………………………………………………………………………....
p. 5
5.5 Power supply………………………………………………........ ……………………………
p. 5
6. Quality insurance ………………………………………………………………………….....
p. 5
7. Additional requirements ………………………………………………………………….....
p. 5 - 6
7.1 Rating Plates or Labelin…………………………………………………………...................
p. 6
7.2 Type test reports…………………………………………………..........................................
p. 6
8. Sample for study …………………………………………………………………………….
p. 6
Last update : 2017-06-28
-2-
Specification for Tender
565337578
1. Scope
This specification covers the general requirements of design, manufacture and testing of Fault Indicator
(hereby referred to as FI) for locating phase-to-phase and phase-to-earth faults on an overhead distribution
system of a MV comprised between 4 and 69 kV.
2. System parameters
The FI shall be designed to operate on a Medium Voltage overhead network or different networks with the
following characteristics:
--------------------------------------------------------------------------------------------2.1 Nominal Operation Voltage
4 to 69 kV
2.2 System Maximum Voltage
69 kV
2.3 Frequency
50 Hz (or 60HZ)
2.4 Type of MV neutral earthing
through a resistor or solidly grounded
--------------------------------------------------------------------------------------------One single product shall be proposed to cover the whole range of above characteristics: Particularly, the
same product should be installed on any network from 4 to 69 kV. Offers requiring to have in stock 2 or
more different product references depending on the line Voltage shall not be considered.
3. Service conditions
The FI shall be designed to operate in the following environmental conditions:
Symmetrical Fault Current
Shocks & vibrations
EMC and EMI
Lightning surge
Maximum Ambient Temperature
Maximum annual average temperature
Maximum relative humidity
Environmental conditions
12.5 kA/1s and 25KA/170ms (maximum phase
current that the FI shall withstand)
120 minutes of sine vibrations and 2000 negative and
2000 positive shocks, in OX, OY and OZ axes
must have passed IEC and FCC approval
125kV shocks
85° C
30° C
95% at 30°C according to IEC 68 2 30
Humid tropical climate with polluted atmosphere
according to IEC standard
4. Applicable standards
Electro-magnetic compatibility
IP54 protection level
Damp Heat cycle Test (humidity and heat cycles)
Salty fog
Sinus wave vibrations & chocks
Dielectric test
Temperature aging
short circuit
Last update : 2017-06-28
IEC 61000-6-2 and FCC part 15
IEC 529
IEC 68-2-30
IEC 68-2-11
IEC 68-2-6, IEC 68-2-29
IEC 60060-1
IEC 668-2-14
ANSI 495 (part 4.4.8)
-3-
Specification for Tender
565337578
5. Basic features
5.1 General
5.1.1 The FI shall be suitable for outdoor use in the tropical climate condition stipulated in clause 3 above.
5.1.2 The components used in the FI shall be suitably protected from direct sunlight to prevent
malfunctioning due to solar radiation. The maximum operating temperature shall not be less than 85° C.
5.1.3 The FI shall be suitable for mounting on line conductors of a diameter ranging between 5 and 25 mm.
It shall be fully self-contained type without any external connection, indicator or sensors.
5.1.4 The fault sensing shall be based on detection of the electromagnetic field and its variations.
5.1.5 The FI shall be suitable for use on multiple lines supported by the same pole.
5.1.6 The FI shall be of the programmable type suitable for sensing:
Short-circuit faults up to 12.5 kA for 1s. and 25 kA for 170ms
Low earth leakage fault of maximum sensitivity of 6A.
5.1.7 The FI shall detect faults based on 2 simultaneous tripping criterias:
5.1.7.1 In order to detect strong fault currents (typically phase-to-phase faults), it shall trip when the phase
current exceeds a absolute threshold for a fixed duration of about 20 ms. This absolute threshold must be
configurable to at least 4 different values between 100 and 800A.
5.1.7.2 In order to detect low fault currents (typically resistant phase-to-earth faults), it shall trip when it
detects the phase current increase within a fixed duration (about 20ms) exceeds a relative threshold. This
threshold must be configurable to at least 6 different values between 6 and 160A. It shall be possible to
disable this second tripping criteria.
5.1.8 When a fault occurs on the network, the upstream protection will trip within 70s maximum (inverse
time protection). Therefore, in order to prevent tripping due to a load increase, on detection of one of the
above criteria, the FI shall confirm the fault by checking if the voltage disappears within the next 70s. and
start to indicate the fault only under this condition.
5.1.9 In case of faults, the FIs which are detecting the variation of the electromagnetic field due to fault
current (FIs installed between the circuit breaker and fault point) shall provide a light indication, while FIs
downstream the fault or on non-faulty branches shall not show any indication.
5.1.10 The fault indication shall be provided by the means of a flashing light system offering a good contrast
against sunshine (red color is prefered) and an MTBF of the light emitting system at least 45 000 Hours
(LEDs for instance). It shall provide a light of an intensity of 40 Lumen minimum and give a 360° visibility
from at least 50m in sunny day conditions, and at least 300m at night.
5.1.11 The FI is primarily intended to allow localization of permanent faults. For this purpose, when the line
remains out of power following the fault, the FI shall flash at a frequency of once per 3s and shall remain
flashing:
5.1.11.1 Until the time-out has expired (this time-out must be configurable to at least 4 possible values
between 2 and 16 hours),
5.1.11.2 Until the medium voltage is back,
5.1.11.3 Until the FI is reset manually,
whatever conditions comes first.
Last update : 2017-06-28
-4-
Specification for Tender
565337578
Caution: since the load current might be very low upon MV return, load current reset FI are not acceptable.
5.1.12 The FI shall also provide some means to localize non permanent faults (i.e. faults for which the
protection device trips, and which disappear if the protection device has cleared the fault with a reclosing
cycle).
Such faults shall be shown in a different way than for permanent faults (for instance, slower flashing
frequency is allowed), for the configured time duration mentioned above, and with the same flash power (40
lumen minimum) as for permanent faults.
Caution: FIs using a less powerful flash to indicate transient faults are not acceptable
5.1.13 The FI shall include some self-test possibility usable when the FI is on the line (powered or not).
5.1.14 The FI shall be selective in action as indicated below
5.1.14.1 It shall not respond to any sudden variation (increases/decrease) in load current
5.1.14.2 It shall not respond to a overcurrent not due to a fault
5.1.14.3 It shall not respond to high magnetizing inrush currents, created upon line energizing.
5.2 Equipment Housing
The FI housing shall be made of high strength plastic and shall be of UV stabilized and flame retarding type.
5.3 Clip-on clamps
The FI shall clip on the conductor once its opened spring clamps are pushed onto it. The strength of the
clamps once closed must be sufficient for the FI to withstand winds of 150 km/h without falling from the
line.
5.4 Installation
Installation shall be possible on live lines using an isolated hot stick with shot gun type termination.
5.5 Power supply
The power supply for the operation of the equipment shall be from a lithium battery suitable for at least 10
years trouble-free service. It shall be easily replaceable.. The user must be able to find the battery on the
market. Only adaptation of a wire and connector to a standard battery can be accepted.
Fault Indicators with a specially designed battery are not accepted.
6. Quality insurance
The Bidder shall supply documentary proof that the manufacturer possesses ISO 9001 and ISO 14001
Quality insurance certification, from an independent internationally recognized body, for the design,
manufacture and testing of Clip-On Fault Indicator for medium voltage lines.
7. Additional requirements
7.1 Rating Plates or Labeling
Each fault indicator shall carry a weather and corrosion proof Bating Plate indicating the following
particulars.
7.1.1 Manufacturer’s identification.
7.1.2 Model or type number (as per catalogue)
Last update : 2017-06-28
-5-
Specification for Tender
565337578
7.1.3 Year of manufacture in characters big enough to allow reading from the ground so that to provide
indication of battery age.
7.2 Type test reports
The manufacturer must be able to deliver test reports from independent laboratories, to confirm that his
equipment passed the requested tests and fill-in the hereunder table accordingly:
Test required
Standard required
Electro-magnetic
compatibility
IEC 61000-6-2
Compliance
(Y/N)
Test report Laboratory
number
which made the
test
FCC part 15
IP54 protection level IEC 60529
Damp heat cycle
IEC 60068-2-30
Salty fog
IEC 68-2-11
Sinus wave vibrations IEC 68-2-6
and shocks
IEC 68-2-29
125kV dielectric test IEC 600060-1
12.5kA/ 1s Short
ANSI 495 (4.4.8)
circuit
25kA/ 170ms Short
ANSI 495 (4.4.8)
circuit
Operating
ANSI 495 (4.4.1)
Temperature from IEC 60068-2-14
40°C to +85°
8. Sample for study
One sample of fault indicator offered shall accompany the Bid to facilitate analysis and evaluation. The
Samples of the unsuccessful Bidder will be returned once the award is made. The sample of the successful
Bidder would be retained and set off from the total quantity to be supplied.
Last update : 2017-06-28
-6-