Download File - ELECTRICAL ENGINEERING DEPT, DCE

Survey
yes no Was this document useful for you?
   Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Document related concepts

Pulse-width modulation wikipedia , lookup

Ohm's law wikipedia , lookup

Power factor wikipedia , lookup

Voltage optimisation wikipedia , lookup

Immunity-aware programming wikipedia , lookup

Buck converter wikipedia , lookup

Switched-mode power supply wikipedia , lookup

Electric power system wikipedia , lookup

Stray voltage wikipedia , lookup

Variable-frequency drive wikipedia , lookup

Mains electricity wikipedia , lookup

Electrification wikipedia , lookup

Two-port network wikipedia , lookup

Amtrak's 25 Hz traction power system wikipedia , lookup

History of electric power transmission wikipedia , lookup

Ground (electricity) wikipedia , lookup

Islanding wikipedia , lookup

Electrical substation wikipedia , lookup

Power engineering wikipedia , lookup

Alternating current wikipedia , lookup

Three-phase electric power wikipedia , lookup

Fault tolerance wikipedia , lookup

Earthing system wikipedia , lookup

Transcript
DHANALAKSHMI COLLEGE OF ENGINEERING
CHENNAI
DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING
EE 2351 – POWER SYSTEM ANALYSIS
Year / Semester: III/VI
UNIT – I
PART A
1.
2.
3.
4.
5.
6.
7.
What is meant by transient and steady state conditions?
Draw the equivalent circuit of a three winding transformer.
What are the components of a power system?
If the reactance is 15 ohm, find the p.u. value for a base of 15 kVA and 10 kV.
What is meant by single line diagram?
How are the loads represented in reactance or impedance diagram?
What are the different types of buses in power systems? What are the quantities specified in
each bus?
8. What is the need for system analysis in planning and operation of power system?
9. Draw the single line diagram showing the essential parts in the power system network.
10. A Generator rated at 30 MVA, 11 kV has a reactance of 20% calculate it’s per unit reactance
for a base of 50 MVA and 10 kV.
PART B
16marks
1. (i) The one-line diagram of a power system is shown below.
G1:80 MVA
22 kV
X = 9%
T1: 50 MVA
22/220 kV
X = 10%
T2: 40 MVA
220/22 kV
X = 6.0%
T3, T4: 40 MVA
22/110 kV
X = 6.4%
Line 1
200 kV
X = 121
Line 2
110 kV
X = 42.35
M: 68.85 MVA
20 kV
X = 22.5%
Load: 10 MVA
4 kV
Δ – Connected Capacitor
Draw an impedance diagram showing all impedances in per unit on a 100 MVA base.
Choose 22 kV as the voltage base for generator.
(ii) State the applications of bus admittance matrix.
(16)
2. Form the bus impedance matrix for the network shown by building algorithms.
(16)
2. (i) What are the advantages of per unit computations?
(ii) Draw the reactance diagram for the power system shown in figure. Neglect resistance
and use a base of 100 MVA, 220 kV in 50Ω line the ratings of the generator motor and
transformer are given below
Generator
: 40 MVA, 25 kV, X11 = 20%
Synchronous motor : 50 MVA, 11 kV, X11 = 30%
Y- Y transformer
: 40 MVA, 33/220 kV, X = 15%
Y- Δ transformer
: 30 MVA, 11/220 kV (Δ/Υ)
(16)
3. Find the bus impedance matrix for the 4-bus system shown in figure. Consider bus 4 as the
reference bus.
(16)
4. (i) The parameters of a 4 – bus system are as under.
Bus code
1-2
2-3
2-4
3-4
1-3
Line impedance
(p.u.)
0.2 + j 0.8
0.3+j0.9
0.25+j1
0.2+j0.8
0.1+j0.4
Charging
admittance
(p.u.)
j 0.02
j 0.03
j 0.04
j 0.02
j 0.01
Draw the network and find bus admittance matrix.
(ii) A three phase, Δ/Υ transformer with rating 100 kVA, 11 kV / 400 V has its primary and
secondary leakage reactance as 12 Ω / phase and 0.05 Ω / respectively. Calculate the p.u.
reactance of transformer.
(16)
5. Determine Zbus for system whose reactance diagram is shown in figure. Where the
impedance is given in p.u. preserve all the nodes.
(16)
6. (i) Derive the Π model for a transformer with off nominal tap-ratio.
(8)
(ii) Sketch and explain electric power system and mark the voltage level at various points
from generator to load.
(8)
7. Describe the modern power system in detail.
(16)
8. Determine the positive, negative and zero sequence networks for the system shown in
figure. Assume zero sequence reactance for the generator and synchronous motors as 0.06
p.u. Current limiting reactors of 2.5 Ω are connected in the neutral of the generator and
motor number 2. The Zero sequence reactance of the transmission line is j300 Ω.
(16)
9. (i) Fine the by impedance matrix for the system whose reactance diagram is shown in figure.
All the impedances are in p.u.
(ii) Explain briefly about bus incidence matrix with an illustration.
UNIT – II
PART A
1. What is the need for swing bus?
2. What is meant by acceleration factor in load flow solution? What is its best value?
3. List out the advantages of Gauss-Siedal method.
4. List out the advantages of Newton-Raphson method.
5. What is meant by P-Q bus in power flow analysis?
6. Define – Primitive matrix
7. Define – Load bus
8. How is load flow study performed?
9. What is meant by slack bus?
10. List the disadvantages of Gauss-Siedal method.
(16)
PART B
16marks
1. Derive load flow algorithm using Gauss-Siedel method with flow chart and discuss the
advantages of the method.
2. Derive load flow algorithm using Newton-Raphson method with flow chart and state the
importance of the method.
3. Explain with a flow chart, the GS method of load flow analysis with PQ and PV buses.
4. Derive load flow algorithm using Fast Decoupled method with flow chart and write the
advantages of the method.
5. Illustrate the Newton-Raphson algorithm for the solution of the load flow problem, when no
PV buses are present. Show how the technique may be modified to handle PV buses also.
6. Describe formulation of power flow equations using Y – matrix.
7. Solve for load flow solution for the given three bus system by Gauss-Siedal method. Carry
out 2 iterations. Also neglect limits on reactive power.
Bus data:
Bus 1: Slack bus, V = 1.05 0 p.u.
Bus 2: PV bus, V= 1.0 p.u., Pg = 3 p.u.
Bus 3: PQ bus, PL = 4 p.u., QL = 2 p.u.
Line data:
Line No.
1
2
3
From
1
2
1
To
2
3
3
Impedance
j0.4
j0.2
j0.3
8. The following are the system data for a load flow solution. The line admittances are as
follows:
Line No.
1
2
3
4
5
From
1
2
1
2
3
To
2
3
3
4
4
Admittance
2 – j8.0
0.606 – j2.664
1 – j4.0
1 – j4.0
2 – j8.0
The schedule of active and reactive powers are as follows:
Bus Code
1
2
3
4
P
-0.5
0.4
0.3
Q
-0.2
0.3
0.1
V
1.06
1 + j0.0
1 + j0.0
1 + j0.0
Remarks
Slack
PQ
PQ
PQ
Determine the bus voltages at the end of first iteration using Newton-Raphson
method.
9. The following are the system data for a load flow solution. The line admittances are as
follows:
Line No.
1
2
3
4
5
From
1
2
1
2
3
To
2
3
3
4
4
Admittance
2 – j8.0
0.606 – j2.664
1 – j4.0
1 – j4.0
2 – j8.0
The schedule of active and reactive powers are as follows:
Bus Code
P
Q
V
Remarks
1
--
--
1.06
Slack
2
0.5
0.1  Q2  1.0
1.04
PV
3
0.4
0.3
1 + j0.0
PQ
4
0.3
0.1
1 + j0.0
PQ
Determine the bus voltages at the end of first iteration using Newton-Raphson method.
10. For the following system solve load flow using Fast Decoupled method.
Bus data:
Bus Code
P
Q
V
Remarks
1
--
--
1.05
Slack
2
3
0.1  Q2  1.0
1.00
PV
3
4
2
1 + j0.0
PQ
From
1
2
1
To
2
3
3
Line data:
Line No.
1
2
3
Impedance in Ω
j0.4
j0.2
j0.3
UNIT – III
PART A
1. List out the various types of faults occur in a power system.
2. What is the need for short circuit studies or fault analysis?
3. What is meant by symmetrical fault or balanced three phase fault?
4. What is meant by doubling effect?
5. What is meant by synchronous reactance or steady state condition reactance?
6. What is meant by sub transient reactance?
7. What is meant by transient reactance?
8. Define – Short circuit capacity
9. Define – DC off set current
10. What is meant by bolted fault or solid fault?
PART B
16marks
1. A generator is connected through a transformer to a synchronous motor. The sub transient
reactances of generator and motor are 0.15 p.u. and 0.35 p.u.. respectively. The leakage
reactance of the transformer is 0.1 p.u.. all the reactances are calculated on a common base.
A three phase fault occurs at the terminals of the motor when the terminal voltage of the
generator is 0.9 p.u.. the output current of the generator is 1 p.u.. and 0.8 p. f. leading. Find
the sub transient current in p.u. in the fault, generator and motor. Use the terminal voltage of
generator as reference vector.
2. Derive the expression for fault current in Line-to-Line fault on an unloaded generator in
terms of symmetrical components.
3. Explain symmetrical fault analysis using Z-bus matrix with neat flow chart
4. A 11 kV, 100 MVA alternator having a sub-transient reactance of 0.25 p.u. is supplying a
50 MVA motor having a sub-transient reactance of 0.02 p.u. through a transmission line. The
line reactance is 0.05 p.u. on a base of 100 MVA. The motor is drawing 40 MW at 0.8 p.f.
leading with a terminal voltage of 10.95 kV When a 3-phase fault occurs at the generator
terminals. Calculate the total current in generator and motor under fault conditions.
5. A 3 phase, 5 MVA, 6.6 KV alternator with a reactance of 8% is connected to a
feeder of series impedance of (0.12 + j 0.48) ohm/phase/km. The transformer is rated at
3MVA, 6.6 KV/ 33 KV and has a reactance of 5%. Determine the fault current supplied by
the generator operating under no-load with a voltage of 6.9 kV, when a 3 phase symmetrical
fault occurs at a point 15 km along the feeder.
6. The bus impedance matrix of 4-bus system with values in p.u is given by ,
Z bus = j
0.15
0.08
0.04
0.07
0.08
0.15
0.06
0.09
0.040.060.130.05
0.07
0.09
0.05
0.12
In this system generators are connected to buses 1 and 2 and their sub-transient
reactances were included when finding Z bus. If pre-fault current is neglected, find sub-transient
current in p.u. for a 3 phase fault on bus-4. Assume pre fault voltage as 1 p.u. if the sub transient
reactance of generator bus-2 is 0.2 p.u., find the sub transient fault current supplied by
generator.
7. (i) What are the basic assumptions made in fault calculations?
(ii) How can the fault current be determined using Zbus?
8. Explain with the help of a detailed flow chart, how can a symmetrical fault be analyzed
using Z-bus?
9. Explain the procedure for making short-circuit studies of a large power system networks
using digital computers.
10. Derive the equations to find the π-equivalent circuit of transformer with off-nominal tap
ratio.
11. Explain the modelling of generator, load, shunt capacitor and transmission line for short
circuit studies.
UNIT – IV
PART A
1. What are the symmetrical components of a 3 phase system?
2. What are the positive sequence components?
3. What are the negative sequence components?
4. What are the zero sequence components?
5. What is meant by sequence operator?
6. What is meant by sequence impedance and a sequence network?
7. Draw the positive, negative and zero sequence network of all power system components
8. Write the equation to determine fault current for L-G, L-L and L-L-G fault with impedance.
9. Write the equations to convert symmetrical currents into unbalanced phase currents.
10. Write the equations to convert unbalanced phase currents into symmetrical components.
PART B
16marks
1. Explain the step by step procedure for systematic fault analysis using bus impedance matrix
2. What are the assumptions to be made in short circuit studies? Deduce and thaw the sequence
network for a line to line fault at the terminals of an unloaded generator.
3. Two 11 kV, 20 MVA, 3-phase, star connected generators operate in parallel as shown in
figure 14.b : the positive, negative and zero sequence reactance’s of each being, respectively,
j0.18, j0.15, j0.10 pu. The star point of one of the generators is isolated and that of the other
is earthed through a 2 ohms resistor. A single line to ground fault occurs at the terminals of
the generators.
Estimate
(i) the fault current,
(ii) current in grounding resistor, and
(iii) the voltage across grounding resistor.
4. (i) Derive the necessary equation to determine the fault current for a single
line to ground fault. Draw a diagram showing the inter connection of sequence networks.
(ii) A 30 MVA, 11 KV generator has Z1 = Z2 =j0.2 p.u. Z0 = j 0.05 p.u. A
line to ground fault occurs on the generator terminals. Find the fault
current and line to line voltages during fault conditions. Assume that the generator neutral is
solidly grounded and that the generator is operating at no-load and at rated voltage at the
occurrence of fault.
5. A 50 MVA, 11 KV, 3-ph alternator was subjected to different types of
faults. the fault currents are ; 3-ph fault 1870 A, line to line fault 2590 A, single line to
ground fault 4130 A. The alternator neutral is solidly grounded. find the p.u values of the
three sequence reactances of the alternator
6. Draw the sequence network connected for a double line to ground fault at any point in a
power system and from that obtain an expression for the fault current.
7.
(i) Derive an expression for the total power in a three phase system in terms of sequence
components of voltages and currents.
(ii) Explain in detail about the sequence impedances of transmission lines.
8. A 30 MVA, 11 kV generator has Z1=Z2=j.02 pu. A line to ground fault occurs on the
generator terminals. Find the fault current and line to line voltages during limit conditions.
Assume that the generator neutral is solidly grounded and that the generator is operating at
no load and at rated voltage at the occurrence of fault.
9. Derive the expression for three phase power in terms of symmetrical components.
10. The currents flowing in the lines toward a balanced load connected in delta are Ia = 1000ْ,
Ib = 141.4225ْ and Ic = 10090ْ. Find the symmetrical components of the given line
currents and draw phasor diagrams of the positive and negative sequence line and phase
currents.
11. Derive the equations of fault currents in terms of symmetrical components when there is a
L-L-G fault
12. Draw the zero sequence equivalent circuits for the various possible transformer connections
UNIT – V
PART A
1.
2.
3.
4.
5.
6.
7.
8.
How is the power system stability classified?
What is meant by rotor angle stability?
What is meant by transient stability?
What is meant by steady state stability limit?
What is meant by dynamic stability?
Define – Critical Clearing Angle
Write the power angle equation and draw the power angle curve.
Write the swing equation for a SMIB (Single Machine connected to an Infinite Bus bar)
system.
9. Define – Swing Curve
10. What is meant by Equal Area Criterion
PART B
16marks
1. Derive swing equation used for stability studies in power system.
2. Explain in detail, the modified Euler method of analyzing multi-machine power system for
stability.
3. Explain in detail, the Runge-Kutta method of solving swing equation for multi-machine
systems.
4. Derive an expression for the critical clearing angle and clearing time.
5. Derive the power angle equation for SMIB system. Also draw the power-angle curve.
6. A 3 phase generator delivers 1.0 p.u., power to an infinite bus through a transmission
network when a fault occurs. The maximum power which can be transferred during pre-fault
and post fault conditions is 1.75 p.u., 0.4 p.u., 1.25 p.u. find critical clearing angle
7. Explain in detail, the equal area criterion. How can the equal area criterion be applied to find
the maximum additional load that can be suddenly added?
8. Derive the swing equation of a single machine connected to an infinite bus system and
explain the steps of solution by Runge-Kutta method
9. A generator is operating at 50 Hz delivers 1 p.u. power to an infinite bus through a
transmission circuit in which resistance is ignored. A fault takes place reducing the
maximum power transferable to 0.05 p.u. whereas before the fault, this power was 2.0 p.u.
and after the clearance of the fault, it is 1.5 p.u. By the use of equal area criterion, determine
the critical clearing angle.