
FIG. 5 - Test Equipment Depot
... 10. Remove the test leads from the circuit being measured as soon as the test is completed. Never reset the function/range switch to another range while the leads are still in contact with a circuit. 11. Do not measure voltage when the function/range switch is set on the resistance (ohms) settings. ...
... 10. Remove the test leads from the circuit being measured as soon as the test is completed. Never reset the function/range switch to another range while the leads are still in contact with a circuit. 11. Do not measure voltage when the function/range switch is set on the resistance (ohms) settings. ...
Insulation Monitoring Relays
... protection to operate (blow a fuse or trip a circuit breaker). In such case a residual current detector (RCD) is installed to detect the current leaking to ground and interrupt the circuit. ...
... protection to operate (blow a fuse or trip a circuit breaker). In such case a residual current detector (RCD) is installed to detect the current leaking to ground and interrupt the circuit. ...
SAFETY, HEALTH AND WELFARE AT WORK (GENERAL
... which are located in zone (1), as defined by the ElectroTechnical Council of Ireland ‘National Rules for Electrical Installations’, of rooms in a place of work containing a bath or shower basin, are protected by a residual current device having a tripping current not exceeding 30 milliamperes operat ...
... which are located in zone (1), as defined by the ElectroTechnical Council of Ireland ‘National Rules for Electrical Installations’, of rooms in a place of work containing a bath or shower basin, are protected by a residual current device having a tripping current not exceeding 30 milliamperes operat ...
When tow unshielded transmission lines are close together, power
... graph. As all the bends provided in AWR software package are either bulky or EM based, so this solution is only theoretically true. However, as with smaller bends, this is no reason to doubt that the coupling effect due to the bends will be much smaller, which means the end section’s length is much ...
... graph. As all the bends provided in AWR software package are either bulky or EM based, so this solution is only theoretically true. However, as with smaller bends, this is no reason to doubt that the coupling effect due to the bends will be much smaller, which means the end section’s length is much ...
Power Handling Capacity of the 100 Series Probes
... If a specific application requires more that the power shown in figure 3, a more accurate calculation can be done by measuring the complex impedance of the probe at the frequency of interest. With the current rating of the probe from figure 2 and the measured impedance, it is possible to calculate t ...
... If a specific application requires more that the power shown in figure 3, a more accurate calculation can be done by measuring the complex impedance of the probe at the frequency of interest. With the current rating of the probe from figure 2 and the measured impedance, it is possible to calculate t ...
Unit V - SriRajkumar
... The p.f or dissipation factor ‘tan’ is measured at 0.5, 1.0, 1.66 and 2.0 times the rated phase-to-ground voltage of the cable Max. value of p.f and difference in p.f b/w rated voltage and 1.66 times of rated voltage is specified. The difference between the rated voltage and 2.0 times of rate ...
... The p.f or dissipation factor ‘tan’ is measured at 0.5, 1.0, 1.66 and 2.0 times the rated phase-to-ground voltage of the cable Max. value of p.f and difference in p.f b/w rated voltage and 1.66 times of rated voltage is specified. The difference between the rated voltage and 2.0 times of rate ...
Study Guide for the Source Inspection of Electrical Equipment
... inspectors are required to be proficient in all applicable API standards, specifications, and recommended practices. All questions and comments regarding individually referenced works should be addressed to the publishers of the works. This study guide was not adopted according to API’s Procedures f ...
... inspectors are required to be proficient in all applicable API standards, specifications, and recommended practices. All questions and comments regarding individually referenced works should be addressed to the publishers of the works. This study guide was not adopted according to API’s Procedures f ...
Electromagnetic compatibility

Electromagnetic compatibility (EMC) is the branch of electrical sciences which studies the unintentional generation, propagation and reception of electromagnetic energy with reference to the unwanted effects (electromagnetic interference, or EMI) that such energy may induce. The goal of EMC is the correct operation, in the same electromagnetic environment, of different equipment which use electromagnetic phenomena, and the avoidance of any interference effects.In order to achieve this, EMC pursues two different kinds of issues. Emission issues are related to the unwanted generation of electromagnetic energy by some source, and to the countermeasures which should be taken in order to reduce such generation and to avoid the escape of any remaining energies into the external environment. Susceptibility or immunity issues, in contrast, refer to the correct operation of electrical equipment, referred to as the victim, in the presence of unplanned electromagnetic disturbances.Interference mitigation and hence electromagnetic compatibility is achieved by addressing both emission and susceptibility issues, i.e., quieting the sources of interference and hardening the potential victims. The coupling path between source and victim may also be separately addressed to increase its attenuation.