DS507 Manual - Dyne Systems
... DANGER: Follow all guidelines listed in this section to ensure safe system installation and operation. Follow all state and local codes when connecting this equipment. ...
... DANGER: Follow all guidelines listed in this section to ensure safe system installation and operation. Follow all state and local codes when connecting this equipment. ...
PI, Fuzzy Logic Controlled Shunt Active Power Filter for Three
... nonlinear loads [2]. Recently, fuzzy logic controller has generated a great deal of Interest in various applications and has been introduced in the power electronics field [3][4]. The advantages of fuzzy logic controllers over the conventional PI controller are that they do not need an accurate math ...
... nonlinear loads [2]. Recently, fuzzy logic controller has generated a great deal of Interest in various applications and has been introduced in the power electronics field [3][4]. The advantages of fuzzy logic controllers over the conventional PI controller are that they do not need an accurate math ...
E 71 SERIES Monitoring relays 10 A
... The appropriate choise is made by pressing the “SET/RESET” button. The next step will program the appropriate values and the selection of the fault memory function (which is selected with a “YES” or “NO”). If all programming steps are completed the display will read “end”. After repeatedly pressing ...
... The appropriate choise is made by pressing the “SET/RESET” button. The next step will program the appropriate values and the selection of the fault memory function (which is selected with a “YES” or “NO”). If all programming steps are completed the display will read “end”. After repeatedly pressing ...
IEC 60950-1, 1st ED
... Test generators for transient O/V, voltage variations, S EM susceptibility, ESD as outlined in 7.1 through 7.5 of IEC 62040-2. Note: The presence of equipment alone does not indicate a satisfactory situation. Assessors must evaluate the equipment design, calibration, uncertainty and documentation to ...
... Test generators for transient O/V, voltage variations, S EM susceptibility, ESD as outlined in 7.1 through 7.5 of IEC 62040-2. Note: The presence of equipment alone does not indicate a satisfactory situation. Assessors must evaluate the equipment design, calibration, uncertainty and documentation to ...
10A Advanced Power Conditioner
... the form of heat, and absorbing the remaining excess energy. When tested with multiple 6,000V/3,000A surges, the SMP circuit’s maximum let-through voltage is only 376V Pk / 266V RMS on a 230V line. Due to the design of the circuit, it will not degrade over time (unlike most standard surge suppressor ...
... the form of heat, and absorbing the remaining excess energy. When tested with multiple 6,000V/3,000A surges, the SMP circuit’s maximum let-through voltage is only 376V Pk / 266V RMS on a 230V line. Due to the design of the circuit, it will not degrade over time (unlike most standard surge suppressor ...
25471_energy_conversion_11
... • While IA is determined form SCC , where machine is unsaturated at all field currents • Therefore at high field currents (that core is saturated in OC) EA measured from OCC at a specific If ≠ EA measured at same If under short-circuit conditions • This makes resulting value of XS only approximate ...
... • While IA is determined form SCC , where machine is unsaturated at all field currents • Therefore at high field currents (that core is saturated in OC) EA measured from OCC at a specific If ≠ EA measured at same If under short-circuit conditions • This makes resulting value of XS only approximate ...
The DatasheetArchive - Datasheet Search Engine
... Supply voltage, VCC + (see Note 1) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22 V Supply voltage, VCC – (see Note 1) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ...
... Supply voltage, VCC + (see Note 1) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22 V Supply voltage, VCC – (see Note 1) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ...
Automatic Power Factor Correction by Using Synchronous
... Also, with the increased current, voltage drop increases, thereby the voltage at the supply point is reduced. For different loads it causes voltage drop resulting in: a. Lower output of the illumination system. b. Less current is drawn by the heating device so that the operating temperature drops. T ...
... Also, with the increased current, voltage drop increases, thereby the voltage at the supply point is reduced. For different loads it causes voltage drop resulting in: a. Lower output of the illumination system. b. Less current is drawn by the heating device so that the operating temperature drops. T ...
simple "toneburst" detection circuit
... The design presented here is therefore resistant to voltage-steps and includes a time-gate so that it is not activated by tone-bursts of more than about 25 ms, i.e. full DiSEqC Command messages (3 bytes) and the end of a continuous 22 kHz tone. In two-way DiSEqC systems it may be affected by the (1 ...
... The design presented here is therefore resistant to voltage-steps and includes a time-gate so that it is not activated by tone-bursts of more than about 25 ms, i.e. full DiSEqC Command messages (3 bytes) and the end of a continuous 22 kHz tone. In two-way DiSEqC systems it may be affected by the (1 ...
View - Lance Camper
... less than 13.2 Vdc (equivalent to less than 50% of battery charge) the converter will automatically go into the “Bulk mode.” In this mode, the output voltage of the converter will switch to 14.4 Vdc for a maximum of four hours. If the converter cycles between “Absorption and Bulk mode,” there could ...
... less than 13.2 Vdc (equivalent to less than 50% of battery charge) the converter will automatically go into the “Bulk mode.” In this mode, the output voltage of the converter will switch to 14.4 Vdc for a maximum of four hours. If the converter cycles between “Absorption and Bulk mode,” there could ...
NE5534, NE5534A
... Supply voltage, VCC + (see Note 1) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22 V Supply voltage, VCC – (see Note 1) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ...
... Supply voltage, VCC + (see Note 1) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22 V Supply voltage, VCC – (see Note 1) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ...
specifications
... 1. Line Filter & Associated Circuit This is used for suppressing noise of power input line flowing into the monitor and/or some noise generated in this monitor flowing out through the power input line. That is to say, this circuit prevents interference between the monitor and other electric applianc ...
... 1. Line Filter & Associated Circuit This is used for suppressing noise of power input line flowing into the monitor and/or some noise generated in this monitor flowing out through the power input line. That is to say, this circuit prevents interference between the monitor and other electric applianc ...
Electrical substation
A substation is a part of an electrical generation, transmission, and distribution system. Substations transform voltage from high to low, or the reverse, or perform any of several other important functions. Between the generating station and consumer, electric power may flow through several substations at different voltage levels.Substations may be owned and operated by an electrical utility, or may be owned by a large industrial or commercial customer. Generally substations are unattended, relying on SCADA for remote supervision and control.A substation may include transformers to change voltage levels between high transmission voltages and lower distribution voltages, or at the interconnection of two different transmission voltages. The word substation comes from the days before the distribution system became a grid. As central generation stations became larger, smaller generating plants were converted to distribution stations, receiving their energy supply from a larger plant instead of using their own generators. The first substations were connected to only one power station, where the generators were housed, and were subsidiaries of that power station.