High Reliability
... four-layer devices and all forms of latch-up, including SEL. The device design rules constrain operating voltages to less than one-third BVox and operating at these voltages prevents any SEGR. SEB is not observed in this technology, where high-current bipolar junction transistors (BJT) gain is absen ...
... four-layer devices and all forms of latch-up, including SEL. The device design rules constrain operating voltages to less than one-third BVox and operating at these voltages prevents any SEGR. SEB is not observed in this technology, where high-current bipolar junction transistors (BJT) gain is absen ...
Basic Diode Electronics
... two currents would be present. First, a small current, called reverse saturation current, is, exists because of the presence of the contact potential and the associated electric field. In addition, it also happens that holes and free electrons with sufficient thermal energy can cross the junction. T ...
... two currents would be present. First, a small current, called reverse saturation current, is, exists because of the presence of the contact potential and the associated electric field. In addition, it also happens that holes and free electrons with sufficient thermal energy can cross the junction. T ...
Write-up
... 3. Measure the voltage and current into the lamp at 0.1 V intervals starting at 0.1 V and going to 5.0 V. Note the current-voltage readings where the bulb begins to glow and where it is red, orange, yellow and white. [Caution: Do not exceed 5.0 V. Doing so may burn out the bulb. All of your measurem ...
... 3. Measure the voltage and current into the lamp at 0.1 V intervals starting at 0.1 V and going to 5.0 V. Note the current-voltage readings where the bulb begins to glow and where it is red, orange, yellow and white. [Caution: Do not exceed 5.0 V. Doing so may burn out the bulb. All of your measurem ...
DECS-200N Negative Forcing Digital Excitation Control System
... DECS-200N to meet specific operating characteristics and requirements for the machine under DECS-200N control. Two more methods of set point control may be achieved via the RS232 communication port by using the Windows® based PC software or by the RS-485 port using Modbus™ protocol. Regardless of wh ...
... DECS-200N to meet specific operating characteristics and requirements for the machine under DECS-200N control. Two more methods of set point control may be achieved via the RS232 communication port by using the Windows® based PC software or by the RS-485 port using Modbus™ protocol. Regardless of wh ...
AN-916 APPLICATION NOTE
... This application note describes the single-phase multifunction energy meter design based on the ADE7569. This meter is designed for single-phase, 2-wire distribution systems. The ADE71xx/ADE75xx family of devices, which includes the ADE7569, integrates the analog front end and fixed function DSP of ...
... This application note describes the single-phase multifunction energy meter design based on the ADE7569. This meter is designed for single-phase, 2-wire distribution systems. The ADE71xx/ADE75xx family of devices, which includes the ADE7569, integrates the analog front end and fixed function DSP of ...
WellPilot® Controllers for Rod Pump Optimization
... surface load and position sensors and uses the MEJ calculation engine to calculate downhole data to determine pump fillage and fluid level for each stroke. In fixed-speed applications, this information is used to detect pump-off and minimize fluid pound by stopping the unit for a user-configured tim ...
... surface load and position sensors and uses the MEJ calculation engine to calculate downhole data to determine pump fillage and fluid level for each stroke. In fixed-speed applications, this information is used to detect pump-off and minimize fluid pound by stopping the unit for a user-configured tim ...
IOSR Journal of Electrical and Electronics Engineering (IOSR-JEEE)
... The index value (> 1) indicates that the system is on the verge of instability. So as to prevent the system collapse its value should always be (< 1). ...
... The index value (> 1) indicates that the system is on the verge of instability. So as to prevent the system collapse its value should always be (< 1). ...
Complete Paper
... Power converters have required improvement in the power efficiency as well as reduction of size and weight especially in mobile information/communication devices, traction converters, power control units for electric/hybrid vehicle, etc. Passive components and cooling devices usually occupy a much l ...
... Power converters have required improvement in the power efficiency as well as reduction of size and weight especially in mobile information/communication devices, traction converters, power control units for electric/hybrid vehicle, etc. Passive components and cooling devices usually occupy a much l ...
Progress in On-Line Measurement of PD in G.C. Stone I. Culbert
... electromagnetic coupler [5]. To date such detectors are limited to 0-to-peak total voltages of 5 kV or less. Alternatively, microwave “horn” antennae mounted close to the stator within the motor enclosure, or patch antennae mounted on the motor power supply leads, have been successfully used [6]. As ...
... electromagnetic coupler [5]. To date such detectors are limited to 0-to-peak total voltages of 5 kV or less. Alternatively, microwave “horn” antennae mounted close to the stator within the motor enclosure, or patch antennae mounted on the motor power supply leads, have been successfully used [6]. As ...
DC2431A - Linear Technology
... within ±10% of final regulation voltage. The LT8390’s proprietary peak current mode buck-boost architecture ensures DC2431A runs either in discontinuous conduction mode (DCM) or pulse-skipping mode (PSM) without reversed inductor current. Both of them enhance the light load efficiency. The demo circ ...
... within ±10% of final regulation voltage. The LT8390’s proprietary peak current mode buck-boost architecture ensures DC2431A runs either in discontinuous conduction mode (DCM) or pulse-skipping mode (PSM) without reversed inductor current. Both of them enhance the light load efficiency. The demo circ ...
Off-Grid Series User Manual
... UL/ETL certified automatic transfer switch (ATS) is installed, the unit may start at any time when utility/grid power is lost. When this occurs, load circuits are transferred to the STANDBY (HUMLESS unit) power source. If this unit is used to power electrical load circuits normally powered by a util ...
... UL/ETL certified automatic transfer switch (ATS) is installed, the unit may start at any time when utility/grid power is lost. When this occurs, load circuits are transferred to the STANDBY (HUMLESS unit) power source. If this unit is used to power electrical load circuits normally powered by a util ...
TB#106 Altitude De-rating of Components Placed
... the maximum fuse voltage rating. The maximum permissible overvoltages for various rated maximum voltages are listed in ANSI C37.46, Table 5. However, most of the fuse manufacturers design for the peak arc voltage to be around three times that of the rated maximum fuse voltage. The peak of the arc vo ...
... the maximum fuse voltage rating. The maximum permissible overvoltages for various rated maximum voltages are listed in ANSI C37.46, Table 5. However, most of the fuse manufacturers design for the peak arc voltage to be around three times that of the rated maximum fuse voltage. The peak of the arc vo ...
IOSR Journal of Electrical and Electronics Engineering (IOSR-JEEE) e-ISSN: 2278-1676,p-ISSN: 2320-3331
... grid through a series transformer [3-5], and could help to minimize any voltage fluctuations. However, a large short-circuit current will be induced into the voltage-source inverter (VSI) through the series transformer during faults. To overcome this problem, one alternative is a bypass scheme. It i ...
... grid through a series transformer [3-5], and could help to minimize any voltage fluctuations. However, a large short-circuit current will be induced into the voltage-source inverter (VSI) through the series transformer during faults. To overcome this problem, one alternative is a bypass scheme. It i ...
PQ1 Power Quality Relay Full Data Sheet 1.20
... The wire cross section must be adequate for 100mA, and insulation must be adequate for the rated voltage. The PQ1 may be connected line-to-neutral or line-to-line. Do not connect any load, including the PQ1, from line-to-ground. If your PQ1 will be monitoring 277 Vrms, 400 Vrms, 480 Vrms, or higher, ...
... The wire cross section must be adequate for 100mA, and insulation must be adequate for the rated voltage. The PQ1 may be connected line-to-neutral or line-to-line. Do not connect any load, including the PQ1, from line-to-ground. If your PQ1 will be monitoring 277 Vrms, 400 Vrms, 480 Vrms, or higher, ...
usa 1310 specifications
... the back to front. Each channel shall have the following controls, indicators, and connectors: Rear mounted gain control calibrated in dB. Clipping indicator, responding proportionally to any distortion in excess of 0.1%. Balanced/unbalanced input jack of the Neutrik "Combo" (combined 1/4" TRS and X ...
... the back to front. Each channel shall have the following controls, indicators, and connectors: Rear mounted gain control calibrated in dB. Clipping indicator, responding proportionally to any distortion in excess of 0.1%. Balanced/unbalanced input jack of the Neutrik "Combo" (combined 1/4" TRS and X ...
Evaluates: MAX5943A/B/C/D/E MAX5943A Evaluation Kit General Description Features
... Maxim cannot assume responsibility for use of any circuitry other than circuitry entirely embodied in a Maxim product. No circuit patent licenses are implied. Maxim reserves the right to change the circuitry and specifications without notice at any time. ...
... Maxim cannot assume responsibility for use of any circuitry other than circuitry entirely embodied in a Maxim product. No circuit patent licenses are implied. Maxim reserves the right to change the circuitry and specifications without notice at any time. ...
Evaluates: MAX1873 MAX1873 Evaluation Kit General Description Features
... data sheet for more information about the IOUT pin. The ICHG/EN pin can also be used to set the charge current or to disable the charger. To disable the charger, place a shunt across jumper JU1 or set the voltage at the ICHG/EN PC board pad below 500mV. The charger is automatically enabled when the ...
... data sheet for more information about the IOUT pin. The ICHG/EN pin can also be used to set the charge current or to disable the charger. To disable the charger, place a shunt across jumper JU1 or set the voltage at the ICHG/EN PC board pad below 500mV. The charger is automatically enabled when the ...
technical memo on power-frequency electric and magnetic fields
... high-voltage transmission lines because it gives guidelines for acceptable electrical parameters (conductor surface gradients) that engineers can use to evaluate design options. The IEEE guide is based on many years of research and practical experience. Engineers can control the conductor gradients ...
... high-voltage transmission lines because it gives guidelines for acceptable electrical parameters (conductor surface gradients) that engineers can use to evaluate design options. The IEEE guide is based on many years of research and practical experience. Engineers can control the conductor gradients ...
Draft Information Document Generating Unit Technical Requirements ID# 2011-012R
... minus five percent (+/- 5%%) for N-0 (normal system) and plus or minus 10%ten percent (+/- 10%) for N1 contingencies. Based on the AESO’s operating practices, it is necessary for the AESO to ensure that the generating units will remain on-lineonline during N-1 contingencies. The length of time that ...
... minus five percent (+/- 5%%) for N-0 (normal system) and plus or minus 10%ten percent (+/- 10%) for N1 contingencies. Based on the AESO’s operating practices, it is necessary for the AESO to ensure that the generating units will remain on-lineonline during N-1 contingencies. The length of time that ...
Power engineering
Power engineering, also called power systems engineering, is a subfield of energy engineering that deals with the generation, transmission, distribution and utilization of electric power and the electrical devices connected to such systems including generators, motors and transformers. Although much of the field is concerned with the problems of three-phase AC power – the standard for large-scale power transmission and distribution across the modern world – a significant fraction of the field is concerned with the conversion between AC and DC power and the development of specialized power systems such as those used in aircraft or for electric railway networks. It was a subfield of electrical engineering before the emergence of energy engineering.Electricity became a subject of scientific interest in the late 17th century with the work of William Gilbert. Over the next two centuries a number of important discoveries were made including the incandescent light bulb and the voltaic pile. Probably the greatest discovery with respect to power engineering came from Michael Faraday who in 1831 discovered that a change in magnetic flux induces an electromotive force in a loop of wire—a principle known as electromagnetic induction that helps explain how generators and transformers work.In 1881 two electricians built the world's first power station at Godalming in England. The station employed two waterwheels to produce an alternating current that was used to supply seven Siemens arc lamps at 250 volts and thirty-four incandescent lamps at 40 volts. However supply was intermittent and in 1882 Thomas Edison and his company, The Edison Electric Light Company, developed the first steam-powered electric power station on Pearl Street in New York City. The Pearl Street Station consisted of several generators and initially powered around 3,000 lamps for 59 customers. The power station used direct current and operated at a single voltage. Since the direct current power could not be easily transformed to the higher voltages necessary to minimise power loss during transmission, the possible distance between the generators and load was limited to around half-a-mile (800 m).That same year in London Lucien Gaulard and John Dixon Gibbs demonstrated the first transformer suitable for use in a real power system. The practical value of Gaulard and Gibbs' transformer was demonstrated in 1884 at Turin where the transformer was used to light up forty kilometres (25 miles) of railway from a single alternating current generator. Despite the success of the system, the pair made some fundamental mistakes. Perhaps the most serious was connecting the primaries of the transformers in series so that switching one lamp on or off would affect other lamps further down the line. Following the demonstration George Westinghouse, an American entrepreneur, imported a number of the transformers along with a Siemens generator and set his engineers to experimenting with them in the hopes of improving them for use in a commercial power system.One of Westinghouse's engineers, William Stanley, recognised the problem with connecting transformers in series as opposed to parallel and also realised that making the iron core of a transformer a fully enclosed loop would improve the voltage regulation of the secondary winding. Using this knowledge he built a much improved alternating current power system at Great Barrington, Massachusetts in 1886. In 1885 the Italian physicist and electrical engineer Galileo Ferraris demonstrated an induction motor and in 1887 and 1888 the Serbian-American engineer Nikola Tesla filed a range of patents related to power systems including one for a practical two-phase induction motor which Westinghouse licensed for his AC system.By 1890 the power industry had flourished and power companies had built thousands of power systems (both direct and alternating current) in the United States and Europe – these networks were effectively dedicated to providing electric lighting. During this time a fierce rivalry in the US known as the ""War of Currents"" emerged between Edison and Westinghouse over which form of transmission (direct or alternating current) was superior. In 1891, Westinghouse installed the first major power system that was designed to drive an electric motor and not just provide electric lighting. The installation powered a 100 horsepower (75 kW) synchronous motor at Telluride, Colorado with the motor being started by a Tesla induction motor. On the other side of the Atlantic, Oskar von Miller built a 20 kV 176 km three-phase transmission line from Lauffen am Neckar to Frankfurt am Main for the Electrical Engineering Exhibition in Frankfurt. In 1895, after a protracted decision-making process, the Adams No. 1 generating station at Niagara Falls began transmitting three-phase alternating current power to Buffalo at 11 kV. Following completion of the Niagara Falls project, new power systems increasingly chose alternating current as opposed to direct current for electrical transmission.Although the 1880s and 1890s were seminal decades in the field, developments in power engineering continued throughout the 20th and 21st century. In 1936 the first commercial high-voltage direct current (HVDC) line using mercury-arc valves was built between Schenectady and Mechanicville, New York. HVDC had previously been achieved by installing direct current generators in series (a system known as the Thury system) although this suffered from serious reliability issues. In 1957 Siemens demonstrated the first solid-state rectifier (solid-state rectifiers are now the standard for HVDC systems) however it was not until the early 1970s that this technology was used in commercial power systems. In 1959 Westinghouse demonstrated the first circuit breaker that used SF6 as the interrupting medium. SF6 is a far superior dielectric to air and, in recent times, its use has been extended to produce far more compact switching equipment (known as switchgear) and transformers. Many important developments also came from extending innovations in the ICT field to the power engineering field. For example, the development of computers meant load flow studies could be run more efficiently allowing for much better planning of power systems. Advances in information technology and telecommunication also allowed for much better remote control of the power system's switchgear and generators.