Download TC-PP5LT T Cable Specification Sheet

Survey
yes no Was this document useful for you?
   Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Document related concepts
no text concepts found
Transcript
MWS
D ES C R IPTION
MWS-5LT, Modular Wiring Systems with DALI Control, provides low
cost installation of both power for lighting and Class 1 control wiring for
use with Fifth Light DALI systems. Using modular components that plug
together, MWS-5LT can be installed in a fraction of the time of hardwiring
both lighting and control. Plus, MWS-5LT offers the advantage of
relocating fixtures and DALI control devices for future renovations.
Catalog #
The MWS T Cable with DALI Control Only (TC-PP5LT) feeds only the control wiring to wall or ceiling mounted DALI controls, while feeding both
power and control downstream to another fixture. Compatible MWS
Extender Cables (EC) are used connect either end of the TC-PP5LT. See
the Extender Cable specification sheet for compatible models.
Prepared by
®
Type
Project
Date
Comments
MWS Extender Cables feed power to each T Cable.
D ES IGN FEA TUR ES
• UL Listed under Standard 183 for
make or break under load.
• Copper conductors are THHN
insulated wire rated 90°C.
• Meets requirements of Article 604
of the National Electrical Code.
• Galvanized steel exterior with
integral keying for voltage and
amperage.
• MWS components assembled
with 12 AWG conductors rated at
20 amperes with full size ground
wire.
• Allows downstream feeding
of circuits to another electrical
component or fixture.
• Cable end supplied with 1/2”
connector with locknut and 6” prestripped leads.
• Valox 365 constructed contact
housings are approved for
environmental air plenums.
All unused outlets require a MWS
dust cover. MWS ST, S P, S D , C T
and TC are shipped with one dust
cover attached.
TC-PP5LT
T CABLE
Modular Wiring System
D IMENS IONA L D A TA
SYSTEM VIEW (not to scale)
Extender Cable
T Cable
Extender Cable
Side
2-1/4"
[57mm]
Front
5-5/16"
[136mm]
Top
MWS AUTOCAD DRAFTING
MWS offers AutoCAD drafting to layout
MWS, providing the contractor with
additional benefits.
ORD ER ING INFOR M AT I O N
S A M P L E N U M B E R : 2 7 T C 1 2 /4 G 0 9 P P 5 L T
MWS design layout time is reduced.
TC
Component
TC=T Cable
Conductors and Size
12/4G=#12, 4 Conductors Plus Ground
Cable Length (Feet)
01=1'
09=9'
15=15'
MWS drawing symbols and details
standardized.
Options
PP5LT
Layouts are available on CD or e-mail.
To utilize this service and for additional
information, contact the MWS Sales
Department (888) 487-4887.
Specifications & dimensions subject to change without notice. Consult your Cooper Lighting Representative
for availability and ordering information.
SH IP P ING D A T A
Install dust covers on unused open ends.
Scale is exaggerated on fixtures and
MWS system applications.
Specifications and
dimensions subject to
change without notice.
YS
ER
TEM
S
Eaton’s Cooper Lighting Business
1121 Highway 74 South
Peachtree City, GA 30269
P: 770-486-4800
www.eaton.com/lighting
All electrical boxes, conduit, connections
and switches by others.
C
Eaton
1000 Eaton Boulevard
Cleveland, OH 44122
United States
Eaton.com
UnitStandard
Wt.Qty./Carton
1.0 lbs.
12
3.5 lbs.
8
4.5 lbs.
6
S
Cable
Length
1’
9’
15’
D
Voltage
12=120V
27=277V
Bills of material are computer-generated
guaranteeing accuracy.
TIFIE
PS510005EN
2015-04-06 13:49:18