Download D G 220513

Survey
yes no Was this document useful for you?
   Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Document related concepts

Utility frequency wikipedia , lookup

Power engineering wikipedia , lookup

Pulse-width modulation wikipedia , lookup

Mains electricity wikipedia , lookup

History of electric power transmission wikipedia , lookup

Electric machine wikipedia , lookup

Commutator (electric) wikipedia , lookup

Alternating current wikipedia , lookup

Electrification wikipedia , lookup

Voltage optimisation wikipedia , lookup

Three-phase electric power wikipedia , lookup

Brushed DC electric motor wikipedia , lookup

Metadyne wikipedia , lookup

Electric motor wikipedia , lookup

AC motor wikipedia , lookup

Stepper motor wikipedia , lookup

Induction motor wikipedia , lookup

Variable-frequency drive wikipedia , lookup

Brushless DC electric motor wikipedia , lookup

Transcript
DESIGN GUIDELINE 220513
MOTORS
Scope
This sections covers requirements for most motors 200 HP and less. This section does not
apply to fire pumps, elevators and sealed refrigeration motors, nor does it apply to small
motors with stepped down voltage below 115V.
Related Sections
U-M Master Specification Sections:
220513 - Motors
General
U-M Master Specification Section 220513 Motors shall be used as the basis for the motor
specification on all projects. The A/E shall edit (append) the U-M motor specification to make
it project specific; however do not generally modify the fundamental motor attributes described
in the specification. Turn on hidden text and read all spec. editor's notes when editing the
specification.
Phase and Voltage
Motors 1/2 HP and larger should be three phase.
Single phase motors may be rated for 115V, 200V, depending on the application, and building
power.
Three phase motors should be rated for 460V wherever possible. Where building power does
not include 480V distribution, review options with Project Coordinator and consider adding a
step-up transformer, and using 460V motors. The long term objective in most buildings is to
have three phase distribution at 480V.
Power distribution system serving large motors (100HP and larger) should be examined to
ensure across the line motor starting will not adversely impact the system. Consult Project
Coordinator and other appropriate University personnel in these applications.
Three Phase Motor General Requirements
For most applications, including air handlers, motor enclosures for fans and pumps should be
Open Drip Proof (ODP) type. For cooling towers and other harsh environments, use Totally
Enclosed Fan Cooled (TEFC) motors.
SEPTEMBER 2012
MOTORS
DG 220513
PAGE 1 OF 2
Multiple Speed Motors
With the increased viability of variable speed drives, applications for multiple speed motors
are few and far between. Where three phase motors require multiple speeds, there shall be a
separate winding for each speed. Coordinate electrical requirements carefully with electrical
designer.
Motors for Variable Frequency Drives
Review and verify with both the drive and motor manufactueres the maximum cable length for
each drive. Also consider other reuirements such as RFI that may affect the cable length.
Consult manufacture guidelines and provide proper grounding.
For all hospital funded projects, provide AEGIS SGR (Shaft Grounding Ring) for all VFD
motors. In addition for motors 100 HP or above, also prove an insulted ceramic bearing
assembly on the non-drive end of the motor.