ME-AGS-N* or ME-AGS-S wiring diagram –
For Generac (7000EXL)
ON
inside
Gen Run Signal
(input to pin 2 must
be 10 to 40 DC volts
only while generator
is running);
can be the generator
hour-meter or a
12vdc pilot/run light
5 amp
fuse
Dip-switch
configuration
(Portable Mode)
Inside Generator
13A
5
amp
fuse
Battery
Bank
(monitored
for gen
turn on)
86
13A
ELECTRIC
START
SWITCH
30
START
RELAY
85
16
13A
18
87 87A
18
ENGI NE
RUN
SWITCH
GRN
0
85
30
NUT ON
ENGI NE BLOCK
OFF
RELAY
NOTE 1:
If the generator
engine is cold, the
choke knob must be
manually pulled out
to close the choke
or a auto choke kit
may be available
from your Generac
dealer.
Input DC
voltage jumper
(set to battery
bank voltage)
1 2 3 4
inside
IMPORTANT:
Each wire between
the external relays
and generator must
be sized to handle
the required
amperage of that
circuit.
12/24/48V
* ME-AGS-N is shown
86
Already
connected
On Generator
120VAC Out let
87 87A
12V
Gen
Battery
NOTE 2:
The engine switch must be on or
disconnected when used in
conjunction with the AGS. If
engine switch is off and
connected you will not be able to
start the generator with the AGS.
NOTE 3:
The Idle Control
switch must be in
the “off” position.
120V AC I N
12V DC OUT
TRA NSFORM ER
DC Fuse
(5A max)
Relay 2
(pins 6 & 7)
Relay 3
(pins 1 & 8)
OFF
ON
RUN TIME HOURS
START
Delay
Relay 1
(pins 5 & 6)
Delay
START and OFF Relays = SPDT 30 Amp, 12 VDC coil relay; popular in automotive sound and security installations.
Equivalent to Bosch #0 332 209 150 or TYCO #V23234-A1001-X036.
RY3
Delay Time
START Time
RY3 Time
Time between
start attempts
Total Start
attempts
2 seconds
10 seconds
5 seconds
2 minutes
4
Relay timing for Portable Mode
Magnum Energy, Inc. provides this diagram to assist in the installation of the Auto-Generator Start controller.
Since the use of this diagram and the conditions or methods of installation , operation and use are beyond the
control of Magnum Energy, Inc., we do not assume responsibility and expressly disclaim liability for loss,
damage or expense arising out of the installation , operation and use of this unit.
10-30-2014DM