Download DFB Mains supply considerations

Survey
yes no Was this document useful for you?
   Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Document related concepts

Electrical ballast wikipedia , lookup

Ohm's law wikipedia , lookup

Stray voltage wikipedia , lookup

Electrical substation wikipedia , lookup

Three-phase electric power wikipedia , lookup

Mercury-arc valve wikipedia , lookup

Islanding wikipedia , lookup

Opto-isolator wikipedia , lookup

Current source wikipedia , lookup

Resistive opto-isolator wikipedia , lookup

Buck converter wikipedia , lookup

Voltage optimisation wikipedia , lookup

Alternating current wikipedia , lookup

Rectifier wikipedia , lookup

Circuit breaker wikipedia , lookup

Surge protector wikipedia , lookup

Ground (electricity) wikipedia , lookup

Switched-mode power supply wikipedia , lookup

Residual-current device wikipedia , lookup

AC adapter wikipedia , lookup

Mains electricity wikipedia , lookup

Electrical wiring in the United Kingdom wikipedia , lookup

Earthing system wikipedia , lookup

Transcript
Supply considerations for Anytronics DFBs and Lightboxes
1.
Mains Supply Voltage
All Anycolour fittings including DFBs and Lightboxes are designed to work from
220-240 V ac nominal supplies at 50/60Hz. (Note that the output capability of the
DFB outputs on CD01 and DMX to DFB converters are reduced on 220 V supplies.)
2.
Mains Supply Current
The supply used should be capable of supplying at least 1A per fitting,
regardless of the stated rating of the fittings. This is because on connection to the
supply, a short lived surge current will be taken which will trip breakers or blow fuses
of a lower rating. The surge current depends on the total number of fittings, supply
line impedance and the supply voltage at the precise moment of connection of the
supply.
We therefore do not recommend powering any more than ten DFB fittings from
a standard UK mains plug fitted with a 13 Amp fuse. You may get away with more
connected for a while, but sooner or later the fuse will require replacement.
Similarly for trouble free operation on a supply protected by breakers, we do not
recommend using more fittings than the numeric current rating of the breaker. eg no
more than 25 fittings on a 25 Amp breaker circuit.
3.
Earth Leakage Circuit Protection
In many institutions it is a requirement that all supplies be protected by RCCD
earth leakage circuit protection. This can give rise to problems under two separate
conditions, viz during supply connection and then over the longer term.
Due to the complex switch-mode supply circuitry used in DFBs and Lightboxes,
there is an unavoidable injection of high frequency noise as current into the mains
earth connection. This high frequency earth current is very variable and its effect on
RCCDs is unpredictable (dependent on RCCD manufacturer). An earth current figure
equivalent to 1.5mA per complete fitting has been found to work well as a guide for
calculation purposes. For this reason, we recommend that a maximum of 20 fittings
be supplied through a standard 30mA RCCD device. (Note that 100mA trip RCCD
devices are also available but may not comply with your local regulations.)
On connection to supplies, and on entering and leaving ‘blackout’ condition, a
very short current pulse is often injected into the mains earth connection. This current
is quite high, but is so short lived it tends not to trip RCCDs. The cumulative effect of
many DFBs in an installation will still trip RCCDs on supply connection. Fortunately
the same guide rule as that given above has been found to work in practice. Take the
RCCD trip rating in mA, divide by 1.5 and you have the maximum recommended
number of fittings that should be supplied from that circuit. Please remember however
that this is only a guide, and that different RCCDs are more or less sensitive.
Dr M J Crawford
Anytronics Ltd
15
th
Sept 2003