Download Operating and installation instructions FM100

Survey
yes no Was this document useful for you?
   Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Document related concepts

Oscilloscope history wikipedia , lookup

Power electronics wikipedia , lookup

Power MOSFET wikipedia , lookup

Switched-mode power supply wikipedia , lookup

Opto-isolator wikipedia , lookup

Immunity-aware programming wikipedia , lookup

Rectiverter wikipedia , lookup

Transcript
Operating and Installation
Manual
Fume hood monitor
FM100
SCHNEIDER Elektronik GmbH
Phone: +49 (0) 6171 / 88 479 - 0
Fax:
+49 (0) 6171 / 88 479 - 99
Industriestraße 4
e-mail:
[email protected]
61449 Steinbach • Germany
www.schneider-elektronik.com
DECLARATION OF CONFORMITY
DECLARATION OF CONFORMITY
SCHNEIDER Elektronik GmbH hereby declares that the device:
FM100 FUME HOOD MONITOR
complies with the basic requirements of the European Council Directive for
electromagnetic compatibility (89/336/EEC) and the CE Marking Directive
(93/68/EEC).
You may request a copy of the declaration of conformity at the address given
below.
SCHNEIDER Elektronik GmbH
Industriestraße 4
61449 Steinbach
Tel.:
+49 (0) 6171 / 88 479 - 0
Fax:
+49 (0) 6171 / 88 479 - 99
e-mail: [email protected]
www.Schneider-Elektronik.com
© Copyright 2008 SCHNEIDER Elektronik GmbH
61449 Steinbach ● Germany
Translation, reproduction and other uses, etc. - in whole or in part - are only
allowed with the explicit permission of Schneider Elektronik GmbH.
In the course of continuous product improvements we reserve the right to
make technical and and design changes.
All rights reserved.
Operating Manual ● FM100
1
SAFETY INSTRUCTIONS
1.0
SAFETY INSTRUCTIONS
Before installing and using the FM100 fume hood monitor, please read and
follow this operating and installation manual carefully.
• Installation and wiring may only be done by qualified specialists.
• Check whether the operating voltage shown on the nameplate corresponds
with the supply voltage at the site where the device will be installed.
• During installation, wiring and operation, recognized technical precepts,
particularly regulations regarding safety and accident prevention, must be
followed.
• The device should only be returned to the manfacturer for repair in the
original box.
• When you see the symbol CAUTION, we
recommend that you pay careful attention
to the explanatory text and notes.
ELECTRICAL CONNECTION
OPERATING SAFETY
• The electrical connection must be done by a qualified electrician in
accordance with the safety precautions.
• The following rules and regulations must be followed:
VDE guidelines
Local power supplier regulations
Manufacturer wiring instructions and terminal connection
diagrams
• Connect the FM100 fume hood controller to its own, separate circuit to pro
tect against overload.
• Do not do any electrical work on the device when the power supply
is switched on.
• Follow the safety regulations at all times:
- Disconnect the FM100 fume hood monitor
- Ensure that the controller cannot be switched on again
- Ensure that the controller is voltage-free
• Do not use the FM100 device immediately after bringing it from
an unheated room into a warm room. Condensation on the electronic circuits
can lead to severe damage. The device reaches room temperature after
approximately 2 hours.
• Only place the device in a dry room on a firm, flat surface (e.g, the roof of the
fume hood) or screw it to the side wall of the fume hood.
• Never pull the mains plug or disconnect the device from the power
supply if objects or fluids have permeated the device or if you notice a smell
or smoke. Have the manufacturer check the device.
• Never pull the mains plug or disconnect the device from the power
supply if the case or lid of the device has to be opened.
• The FM100 fume hood controller is intended solely for controlling volume
flows in fume hoods in accordance with EN 14175, Part 2.
• Do not use the FM100 fume hood monitor in areas that are vulnerable to
explosion.
PROPER USE
2
Operating Manual ● FM100
TABLE OF CONTENTS
TABLE OF CONTENTS
1.1
Page
1.0
1.1
DECLARATION OF CONFORMITY . . . . . . . . . . . . . . . . . . .
1
SAFETY INSTRUCTIONS . . . . . . . . . . . . . . . . . . . . . . . .
2
TABLE OF CONTENTS . . . . . . . . . . . . . . . . . . . . . . . . .
3
FUNCTIONAL DESCRIPTION . . . . . . . . . . . . . . . . . . . . .
4
2.1
FUNCTION DISPLAY PANEL . . . . . . . . . . . . . . . . . . . . . .
4
2.2
FUNCTIONAL DIAGRAM . . . . . . . . . . . . . . . . . . . . . . . . . .
5
2.3
PERFORMANCE FEATURES . . . . . . . . . . . . . . . . . . . . . . . .
5
2.4
2.0
CE NOTE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5
3.0
SCOPE OF DELIVERY • INSTALLATION AND SETUP INSTRUCTIONS
6
4.0
TERMINAL DIAGRAM . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
7
5.0
INSTALLATION • THE FIRST FIVE STEPS. . . . . . . . . . .
8
5.1
STEP 1 • OPEN THE CASE COVER . . . . . . . . . . . . . . .
8
5.2
STEP 2 • CONNECT PVC HOSES TO THE SENSOR . . . . . . . . . .
8
5.3
STEP 3 • CONNECT THE FUNCTION DISPLAY . . . . . . . .
8
5.4
STEP 4 • CONNECT CURRENT AND LIGHTING . . . . . . . . . . . . . . . . . . .
9
5.5
6.0
6.1
6.2
STEP 5 • CONNECT EMERGENCY POWER PACK . . . . . . . . . . . . . .
9
INSTALLATION OF ADDITIONAL FUNCTIONS . . . . . . . . . . . . . .
10
CONNECTING THE MOTOR ON RECOGNITION. . . . . . . . . . . . . .
10
CONNECTING THE DIGITAL INPUTS . . . . . . . . . . . . . . . . . .
10
6.2.1
On/Off (In 1) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
11
6.2.2
Daytime/night-time control (In 2). . . . . . . . . . . . . . . . . . . .
11
6.2.3
Sash > 50cm (In 3). . . . . . . . . . . . . . . . . . . . . . . . .
11
6.3
CONNECTING THE ANALOGUE OUTPUT. . . . . . . . . . . . . . . . . . .
12
6.4
CONNECTING THE ANALOGUE INPUT . . . . . . . . . . . . . . . . .
12
6.5
CONNECTING THE FLOW SENSOR . . . . . . . . . . . . . . . . .
13
6.6
CONNECTING THE RELAY OUTPUTS . . . . . . . . . . . . . . . . . . .
14
6.6.1
Light (K3) relay. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
14
6.6.2
Motor (K2) relay. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
14
6.6.3
Alarm (K1) relay. . . . . . . . . . . . . . . . . . . . . . . . .
14
7.0
FUNCTION DISPLAY AND CONTROL PANEL . . . . . . . . . . . . . . . . . . . . . .
15
8.0
PROGRAMMING INSTRUCTIONS . . . . . . . . . . . . . . . . . . . . . . . . .
16
9.0
MAINTENANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
22
9.1
ANNUAL FUME HOOD MAINTENANCE . . . . . . . . . . . . . . . . . . .
22
9.2
POWER PACK . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
22
TROUBLESHOOTING . . . . . . . . . . . . . . . . . . . . . . . .
22
10.0
11.0
TECHNICAL DATA . . . . . . . . . . . . . . . . . . . . . . . . . .
23
11.1
DIMENSIONS CASE . . . . . . . . . . . . . . . . . . . . . .
23
11.2
DATA VENTURI MEASURING TUBE . . . . . . . . . . . . . . . . . . . . . .
24
DATA MEASURING TUBE . . . . . . . . . . . . . . . . . . . . . . . . . . .
24
12.0
11.3
INDEX .
.
25
A1
APPENDIX A1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
A1
.
Operating Manual ● FM100
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
3
FUNCTIONAL DESCRIPTION
2.0
FUNCTIONAL DESCRIPTION
For use as a monitoring and alarm system for exhaust air volume flows in various
applications, such as fume hoods, safety cabinets and other extraction units.
Okay
Air volume or Air velocity
green
Alarm
Okay
red
green
Overshoot
yellow
oberer Grenzwert
Actual value
Microprocessor controlled security system to monitor the
containment-safe operating status of fume hoods. An
acoustic and optical alarm is activated as soon as the
exhaust air volume flow falls below the programmable
thresholds. When the threshold is exceeded, only an
optical alarm is signalled (yellow LED).
FM100 fulfills the standards DIN 12924, Part 1 and EN
14175, Part 2. That means security for the laboratory
worker. FM100 is suitable for all types of fume hood,
making it easy to implement new installations and retrofit
existing fume hoods.
unterer Grenzwert
time
2.1
FUNCTION DISPLAY
AND CONTROL PANEL
A suitable measurement system is vital for precise
and safe monitoring. For safe operation with the static
differential pressure transmitter and reproducible
and exact measurement results we recommend the
SCHNEIDER measuring tube (suitable for retrofitting) or
the SCHNEIDER venturi measuring tube.
The function and control panel is available with its own case or as a built-in
version in different variations. In addition to client-specific designs a wide range
of different function displays are available (see the data sheet Standard function
displays).
Basic functions:
Acoustic and optical alarm (LOW=red LED) for insufficient exhaust air or
excess supply air (when used for supply air monitoring)
Optical display (OK=green LED) for sufficient exhaust/supply air
RESET button to acknowledge the acoustic alarm
Service plug for programming via the service module SVM100 or laptop
Addition optional functions:
Button VMAX only for SCHNEIDER fume hood controllers
Optical display (HIGH=yellow LED) for exceedance of the maximum
exhaust air
Yellow flashing LED as an optical alarm for the operating status
“Sash > 50cm”
Status display VMIN for day/night display
Button Light ON/OFF (fume hood interior)
Button I/O for switching the control function ON or OFF
Function display type: 0010
4
Operating Manual ● FM100
FUNCTIONAL DESCRIPTION
Battery backup
FUNCTIONAL DIAGRAM
2.2
PERFORMANCE
FEATURES
2.3
CE NOTES
2.4
2
1
+
Fume hood
monitor
p
FM100
230 VAC Power
Day/Night operation
Digital In-/Outputs
4
Analogue Output
5
3
Fume hood
Functional
display
Air volume display
High
m3
h
Okay
6
Low
Reset
RS 232
Monitoring according to
EN 14175
Servicemodule
SVM-100
Supply
air
1
Venturi measuring tube
2
1
2
3
3
Static differential pressure transmitter
or alternate
Air flow sensor
4
5
6
4
Digital In-/Outputs for special application
7
8
9
5
Analogue Output (0...10 VDC) for room group controller
*
0
,
6
Optional air volume (m3/h) or air flow (m/s) display
F1
F2 F3
Laptop
Microprocessor controlled monitoring system
Integrated power supply 230V AC
All system data are saved mains voltage failure-safe in the EEPROM
Programming and retrieval of all system values via the service module
SVM100 or software PC2000
Monitoring of supply air and exhaust air systems
Static differential pressure transmitter with high long-term stability.
Measuring range: 6...240 (optional 20...800) pascal or face velocity
(optional)
Monitoring of fume hood operation to EN 14175, Part 2 with acoustic and
optical alarm
Optional monitoring of exceedance of a programmable volume flow with
optical alarm
Optical and optionally acoustic alarm for the operating status “Sash >
50cm”
Programming of a second monitoring value (reduced volume flow/nighttime operation
Emergency power pack (optional) for mains voltage failure-safe operation
Integrated power pack charging connection
Suitable for all types of fume hood
The FM100 fume hood controller complies with the safety requirements of the
EMC law and the CE Marking Directive and therefore disposes of a CE Marking.
Operating Manual ● FM100
5
DELIVERY AND INSTALLATION
3.0
SCOPE OF DELIVERY • INSTALLATION AND SETUP INSTRUCTIONS
SCOPE OF DELIVERY FM100 FUME HOOD MONITOR
The following components are included in the delivery of the FM100 fume hood
monitor:
Pos.
4
Number Object
1
1
Evaluation electronics in housing with sensor (static differential pressure transmitter) and integrated power pack
(230V AC)
2
1
Function display and control panel with green and red lightemitting diodes (yellow LED and other functional elements
optional), as well as an acoustic alarm with acknowledgement button
3
1
8-pole connection cable (3m, optionally 5m)
4
1
Optional accessories:
SCHNEIDER measuring device or venturi measuring tube
3
1
2
DN
The following mounting methods are permissible for the FM100 fume
hood monitor:
• Mounted level on the roof of the fume hood monitor (horizontal mounting
position).
Always with the lid facing upwards.
• Screwed to the wall of the fume hood (vertical mounting position).
Air connections at the side or facing downwards.
CAUTION!
NOTE
With all other mounting methods the output signal of the
differential pressure transmitter changes.
In all events, after installation of the evaluation electronics and before
initial operation, a zero-point calibration of the static differential pressure
transmitter must be carried out .
The evaluation electronics with sensor must be mounted in such a way that
vibrations cannot be transmitted to the housing.
During installation and operation it is essential to ensure that no shavings,
dirt or contaminants get into the static differential pressure sensor.
6
Operating Manual ● FM100
TERMINAL DIAGRAM
TERMINAL DIAGRAM
4.0
Measuring tube
FLOW SENSOR
(optional)
+
Monitoring
according
to EN 14175
Fume hood
FUNCTIONAL
DISPLAY
standard or
customer version
High
Okay
Low
Servicemodule
SVM-100
Reset
F1 F2 F3
Supply air
1
2
3
4
5
6
7
8
9
*
0
,
Laptop
Battery backup
- = underpressure
+ = overpressure
STATIC DIFFERENTIAL PRESSURE
TRANSMITTER
Measuring range: 5...240 Pa
In1
In2
X7
FAZ 1
X6
FAZ 2
JP1
X5
X10
JP2
X8
In 1
On/Off
In 2
Day/Night
monitoring
X4
FAULT
K1: max. 3A/250V AC
NO
Fault
NC
In 3
LED-Sash
position >50cm
- (black)
+ (red)
K1
COM
VENTILATOR ON/OFF
K2: max. 3A/250V AC
MOTOR ON
X9
X2
NO
DIGITAL INPUTS
Max. cable length <5m
Run
TRANSFORMER
2
NC
K2
1
L
K3
L
ANALOGUE INPUT
0...5/10V DC, 1mA
3
COM
LIGHT FUME HOOD
ON/OFF
K3: max. 12A/250V AC
ANALOGUE OUTPUT
2...10V DC, 10mA
Serial
Parallel
Operation
Exhaust air actual value
2...10V DC
GND
0...5/10V DC
GND
N
PRIM: 230 VAC, 50/60Hz
SEK I: 9 V~/5 VA
N
X1
MAKE SURE TO
USE THE RIGHT
FUSES
EARTH
X3
EARTH
N
L
N L
FUME HOOD MONITOR
according to EN 14175
Terminal diagram
FM100
Rev.:
0.2
Operating Manual ● FM100
Date:
15. December 2005
7
INSTALLATION
5.0
INSTALLATION • THE FIRST FIVE STEPS
STEP 1
5.1
OPEN THE CASE
COVER
Unscrew the two screws on the case cover and lift the cover upwards to remove
it.
STEP 2
5.2
CONNECT PVC HOSES
TO THE SENSOR
Exhaust
air
For proper installation you need a suitable damming body such as a measuring
device with connection nipples (outer Ø 6mm) and two sufficiently long PVC
hoses (inner Ø 6mm).
1. Fit the venturi measuring tube or measuring device into the exhaust pipe.
Measuring tube
-
2. Attach one PVC hose to the positive connector (+ = red) of the differential
pressure transmitter and the other end of the hose to the connection nipple
(+) on the measuring device. Attach the second PVC hose to the negative
connector (- = blue) of the differential pressure transmitter and connect the
other end of the tube to the connection nipple (-) on the measuring device.
+
Fume hood
The PVC hoses must be leak-proof and must not be bent or buckled.
Supply
air
-
+
- = underpressure
+ = overpressure
STATIC DIFFERENTIAL PRESSURE
TRANSMITTER
Measuring range: 5...240 Pa
CPU
X8
X10
JP2
20 21 22
In1
In2
FAZ 1
X7
STEP 3
CONNECTING THE
FUNCTION DISPLAY
1. Attach the function display and control unit in an easily visible position on
the front side of the fume hood.
2. Attach the connection cable (3m, optionally 5m) to the side of the
case and to the function display panel. A maximum of two function
display panels can be connected (suitable for pass-through fume
hoods).
Exhaust
air
5.3
Measuring tube
+
CONTROL
PANEL
Standard or
customized
Monitoring acc. to
EN 14175
Fume hood
high
3. Check that jumper JP1 has the correct function display type.
okay
JP1 Serial plug: complex function displays,
e.g. Type: 0010
low
Service module
SVM-100
Reset
F1 F2 F3
1
Supply
air
-
+
- = underpressure
+ = overpressure
2
3
4
5
6
7
8
9
*
0
,
Laptop
JP1 Parallel plug: simple function displays,
e.g. Type: 0060
Please refer to the datasheet Function displays standard for
details.
STATIC DIFFERENTIAL PRESSURE
TRANSMITTER
Measuring range: 5...240 Pa
X6
FAZ 2
X5
JP1
Parallel
8
X8
CPU
FAZ 1
Serial
X10
JP2
16 17 18 19 20 21 22
In1
In2
X7
Operating Manual ● FM100
INSTALLATION
STEP 4
CONNECT POWER
AND LIGHTING
The electrical connection must be carried out by a qualified electrician and
safety regulations and the VDE guidelines must be followed.
5.4
The power feed-in generates the supply voltage for the control electronics.
Check whether the operating voltage shown on the nameplate corresponds with
the supply voltage at the site where the device will be installed.
Important!
It is essential to ensure that PHASE, ZERO and EARTH are connected
correctly!
Ensure proper protection against short circuiting!
FAZ 1
X6
FAZ 2
JP1
X5
X8
CPU
X7
Serial
Parallel
X4
9 10 11 12
- (black)
+ (red)
K1
X9
X2
TRANSFORMATOR
2
8
Run
3
7
K2
LIGHT FUME HOOD
ON/OFF
K3: max. 12A/250V AC
L
N
PRIM: 230 VAC, 50/60Hz
SEC I: 9 V~/5 VA
N
X1
LOAD MUST BE
FUSED ACC. TO
RULES
EARTH
X3
EARTH
N L
FEED-IN POWER
VOLTAGE
230V AC, 50/60Hz
Follow the safety regulations at all times:
- Disconnect the FM100 fume hood monitor
- Ensure that the controller cannot be switched on again
- Ensure that the controller is voltage-free
- Connect the mains connector (230 VAC) with a
3x1,5mm² cable
1
L
K3
STEP 5
CONNECT EMERGENCY
POWER PACK
5.5
If supplied, connect the emergency power pack. The red wire is connected to the
positive pole (+) and the blue (black) wire to the negative pole (-).
According to the standard EN 14175 an emergency power pack is no longer
compulsory.
In the case of a mains voltage failure the emergency power pack provides the
supply voltage for the fume hood controller. A mains voltage failure alarm is
signalled (red flashing LED and acoustic alarm). This alarm cannot be acknowledged. With a 6V/1.2 Ah emergency power pack the FM100 mains voltage
failure alarm remains active for at least 4 hours (provided that regular annual
maintenance is carried out on the power pack).
Important!
When connecting the emergency power pack it is
essential to ensure that the polarity (+) and (-) is
correct!
The components required for basic functioning have now been connected. If no
further additional functions or relay outputs are needed, you can now move on
to the programming instructions (Chapter 8.0).
The terminal connections for the additional functions and relay outputs
are described from Chapter 6 onwards.
Operating Manual ● FM100
9
INSTALLATION • DIGITAL INPUTS • ADDITIONAL FUNCTIONS
6.0
INSTALLATION OF ADDITIONAL FUNCTIONS
6.1
CONNECTING THE
MOTOR ON
RECOGNITION
X7
FAZ 1
X6
FAZ 2
X8
JP1
X5
The motor on recognition function can be activated or deactivated via the service module SVM100 or laptop (see Chapter 8.0 Programming instructions).
When the motor on recognition is activated (= On) terminal block X2 is checked
to see whether the exhaust fan is switched on (230V AC on terminal X2.2 and
X2.3). When the exhaust fan is switched on the FM100 fume hood controller is
ready for use and controls the safe exhaust air volume flow for the fume hood
that is connected to it.
Serial
Parallel
X4
9 10 11 12
- (black)
+ (red)
K1
X2
3
TRANSFORMATOR
8
2
7
K2
1
L
K3
PRIM: 230 VAC, 50/60Hz
SEC I: 9 V~/5 VA
N
X1
When the exhaust fan is switched off (no current on terminal connector X2.2
and X2.3) the FM100 controller is deactivated (red LED is on, the acoustic alarm
and and all other LEDs are off), i.e. an optical alarm is only signalled when the
exhaust fan is switched off (=without current).
X3
EARTH
L
MOTOR-ON-RECOGNITION
Feed back signal exhaust fan=On
230V AC, optional 24V AC/DC
N
The mains voltage (230V AC) of the corresponding exhaust fan can be directly
connected to terminal X2.2 and X2.3.
Important!
It is essential to ensure that PHASE and ZERO are connected correctly!
Ensure proper protection against short circuiting!
Optionally terminal input X2.2 and X2.3 is also available for a voltage of
24V AC (please request this on your order).
6.2
CONNECTING THE
DIGITAL INPUTS
The following additional functions can be implemented with the digital inputs on
terminal block X9.
X9
10
The digital inputs In 1, In 2 and In 3 have no galvanic separation. Activation is
done directly via potential-free contacts.
X10
JP2
13 14 15 16 17 18 19 20 21 22
In1
In2
In 1
On/Off
In 2
Monitoring
Day/Night
In 3
LED-Sash
position >50cm
DIGITAL INPUTS
Max. cable length <5m
With activation via potential-free contacts the maximum
cable length is limited to 5m.
The current per input is ≤ 2mA (bei 5V DC).
Run
Operating Manual ● FM100
INSTALLATION • DIGITAL INPUTS • ADDITIONAL FUNCTIONS
On/Off (In 1)
6.2.1
Switches the FM100 fume hood controller ON and OFF via terminal X9.17 and
X9.18. When the FM100 is switched on, the relay K2 Motor on/off is activated.
When the contact is open the FM100 fume hood controller is switched on, while
a closed contact switches the device off (relay K2 Motor on/off drops out). This
relay serves as feedback to a building services management system (BSM) or
for direct activation of an exhaust fan (via a contactor).
Daytime/night-time control (In 2)
6.2.2
Daytime/night-time switching of the control setpoints via terminal X9.15 and
X9.16. The Day and Night control setpoint is programmed via the service module SVM100 or laptop (see Chapter 8.0 Programming instructions).
The Day setpoint controls safe exhaust air volume flow during daytime operation, while the fume hood‘s Night setpoint controls the fume hood during nighttime operation (reduced operation). That means that during reduced operation
an alarm is only signalled when the reduced exhaust air volume flow falls below
the Night setpoint.
When the contact is open the FM100 fume hood monitor is in Day setpoint control mode, while a closed contact switches the device to Night setpoint control
mode.
A relay as feedback for the building management system (BMS) is only supplied
with the FM500 model.
Sash >50cm (In 3)
6.2.3
According to EN 14175 fume hood sashes must be equipped with a mechanical
lock at a sash opening of 50cm. If the sash is opened more than 50cm, the mechanical lock must be released. In accordance with this standard, a flashing LED
on the function display signals the condition „Sash opening > 50cm“ (alarm).
When the contact on terminal X9.13 and X9.14 is open (switch type=normally
closed contact) or shut (switch type=normally open contact) the LED „Close
sash“ flashes on the function display.
The switch type (normally closed contact or normally open contact), the acoustic
alarm delay time as well as an acoustic alarm in addition to the optical alarm can
be programmed via the service module SVM100 (see Programming instructions,
steps 8.9, 8.10 and 8.11).
Operating Manual ● FM100
11
INSTALLATION • ANALOGUE OUTPUT • ANALOGUE INPUT • ADDITIONAL FUNCTIONS
6.3
CONNECTING THE
ANALOGUE OUTPUT
X10
JP2
Actual value
0...10V DC
GND
13 14 15 16 17 18 19 20 21 22
In1
In2
X9
ANALOGUE OUTPUT
0...10V DC, 10mA
CONNECTING THE
ANALOGUE INPUT
X10
JP2
13 14 15 16 17 18 19 20 21 22
In1
In2
Room monitoring and control can be achieved using the exhaust air
actual value signal. The maximum output current is 10mA.
Run
6.4
X9
12
The analogue output (terminal X9.21 = GND and X9.22 = 2...10V DC) provides
the exhaust air actual value as a voltage signal 2...10V DC. The voltage range
2...10V DC corresponds to an exhaust air volume flow of 0...2000m³/h.
The analogue input on terminals X9.19 (GND) and X9.20 (0...5/10V
DC) is free and reserved for special functions.
Combined supply air and exhaust air control can be achieved with this
input, for example. The maximum input current is 1mA.
0...5/10V DC ANALOGUE INPUT
GND
0...5/10V DC, 1mA
Run
Operating Manual ● FM100
INSTALLATION • AIR FLOW SENSOR
CONNECTING THE
FLOW SENSOR
Exhaust
air
The air flow sensor measures the flow velocity in the fume hood.
The FM100 fume hood controller has two different monitoring options:
6.5
1. Monitoring of safe exhaust air volume flow
2. Monitoring of safe flow velocity
AIR FLOW SENSOR
The static differential pressure transmitter and the necessary
measuring system is not required if the flow sensor is used. Low
flow velocities of 0,3 m/s can be monitored, whereby this system
is very vulnerable to disturbance variables, i.e. air turbulence, the
type of fume hood, the installation point of the flow sensor and air
temperature changes may distort the measuring result.
Fume hood
A considerably more robust and accurate measuring method is a
static differential pressure transmitter with a suitable measuring
system. The disturbance variables mentioned above have no influence on the result of the volume flow measurement. This method
is therefore well established for measuring low volume flows (=low
flow velocities).
Supply
air
X7
FAZ 1
X6
FAZ 2
JP1
X5
X8
Serial
Parallel
9 10 11 12
X4
K1
X2
3
8
2
7
K2
1
L
K3
N
X1
X3
Operating Manual ● FM100
13
INSTALLATION • RELAY OUTPUTS
6.6
CONNECTING THE
RELAY OUTPUTS
X7
FAZ 1
X6
FAZ 2
JP1
X5
The complete system is populated with max. 3 relays. The potential-free relay
outputs are for malfunction notification and feedback to the building services
management system. The maximum ohmic contact load of the relay Light K3 is
12 A (230V AC), which means that it is also suitable for controlling fluorescent
tubes. The maximum ohmic contact load of the relay K1 and K2 ist 3 A (230V
AC).
X8
Serial
Parallel
NO
9 10 11 12
NC
8
FAULT ALARM
K1: max. 3A/250V AC
COM
7
X4
FAULT
NO
OKAY
NC
COM
MOTOR ON/OFF
K2: max. 3A/250V AC
LIGHT FUME HOOD
ON/OFF
K3: max. 12A/250V AC
MOTOR ON
- (black)
X2
3
2
K2
1
L
K3
L
Important!
Ensure that connected consumer loads
are properly protected against short
circuiting!
+ (rot)
K1
N
N
X1
LOAD MUST BE
FUSED ACC. TO
RULES!
EARTH
X3
EARTH
FEED-IN POWER
VOLTAGE
230V AC, 50/60Hz
N L
L
MOTOR-ON-RECOGNITION
Feed back signal exhaust fan=On
230V AC, optional 24V AC/DC
N
The meaning of the relay outputs K1 to K3 is as follows:
6.6.1
CONNECTING THE LIGHT RELAY (K3)
The Light relay (K3) is activated when the Light on/off button on the function display and control panel is pressed and is inactiveted when the button is pressed
again.
With this relay the lighting in the fume hood is switched on and off. The phase
is switched from terminal X1.1 to X3.L via the relay contact K3 and may be a
separate mains from the power line (3 phases). When the phase is the same,
terminal X1.L is bridged to X1.1.
The fluorescent light is connected to terminal X3.L (phase L), X3.N (neutral) and
X3.earth.
6.6.2
CONNECTING THE MOTOR ON RELAY (K2)
The Motor on/off relay K2 is activated when the FM100 fume hood controller is
switched on. This may be done by pressing the I/O (in/out) button (if this function
is enabled) on the function display and control panel or via the remote activation input X9.17 and X9.18 (see digital inputs). The digital in/out output has a
higher priority than the button and overrides it. This relay switches the exhaust
fan on or off and also serves as feedback for the building management system
(BMS).
6.6.3
CONNECTING THE ALARM RELAY (K1)
In the case of a fault alarm, the Alarm relay (K1) drops out and thus signals the
malfunction status. Malfunctions may be, for example, insufficient exhaust air
volume, mains voltage failure and internal errors.
14
Operating Manual ● FM100
FUNCTION DISPLAY AND CONTROL PANEL
FUNCTION DISPLAY AND CONTROL PANEL
7.0
In some cases client-specific function and display panels require a different arrangement of the elements on the function
display and control panel than the universal function display panel shown here. However, the operation and meaning of
the functions is exactly the same and can therefore be compared with the universal function display panel. With complex
function display panels like the one shown here, the jumper JP1 must be plugged to serial, while with simple function
display panels (two LEDs, a Reset button and a service plug) the jumper JP1 must be plugged to parallel.
X button is only acduring fume hood
During fume hood
monitoring it has no
This yellow
and lights
cess exha
flow.
RESET button the
alarm (malfunction
nsufficient exhaust
me flow) can be
edged. The optical
annot be acknownd is only switched
n sufficient exhaust
me flow is available.
This green
the normal
i.e. the fum
ting with s
air volume fl
fore within a
This red L
signal a m
the fume h
with insuffi
volume flow
not contam
acoustic ala
due to insu
air volume fl
nowledged
Reset butt
alarm cann
ledged and
off when s
air volume fl
ow LED flashes to
n optical alarm when
is opened >50cm.
D indicates to the
t safest operation is
d when the sash is
The service plug has an RS
232 interface. The service
module SVM100 or a laptop
can be connected here.
With the I/O button monitoring can be switched on or
off. The green LED lights up
to signal that the controller is
switched on.
Status display mains voltage failure:
In the case of a mains voltage failure the red LED flashes briefly once every
2 s. Simultaneously the acoustic alarm is signalled. Mains voltage failure is
also signalled when the device is switched off, but in this case without an
acoustic alarm. The following LEDs are off: green LED (OK), yellow LED (excess), yellow LED (close sash). The Alarm relay (K4) drops out.
ton VMIN can only
ated on the FM500
This button has no
function on the FM100 model. The yellow status LED
lights up to show the nighttime reduction status when
the terminals Day/night control X9.15 and X9.16 are
activated. FM100 monitors
the Night setpoint (reduced
operation).
With the LIGHT button the
interior lighting of the fume
hood can be switched on
and off.
Status display night-time reduction:
The night-time reduction display depends on the type of function display:
Function display and control panel with LED VMIN
When the night-time reduction is activated via the digital input Day/night or the Motor on signal:
LED VMIN = static on.
Function display and cotnrol panel without an integrated LED VMIN
The red LED (underrun) flashes.
In both cases the green LED (OK) is off. The Alarm relay (K3) only drops out if the underrun value for night-time operation is not reached.
Operating Manual ● FM100
15
PROGRAMMING INSTRUCTIONS
8.0
PROGRAMMING INSTRUCTIONS
Programming of project-specific data is done via the service module SVM100 or PC. Plug the service module data cable
into the service plug of the function display and plug in the service module mains plug. The fume hood controller power
supply must also be switched on.
After selecting the FM product from the main menu with the F1 button on the service module, the following settings are
available for selection:
STEP
SETTINGS VIA THE SERVICE MODULE
8.1
Select function display type
8.2
Pressure sensor zero-point calibration
8.3
Shield factor of the measuring system and fume hood type
8.4
Enter setpoints
8.5
Set alarm delay time
8.6
Set piezo duration
8.7
Set motor on recognition (optional)
8.8
Alarm delay after start-up
8.9
Define switch type „Sash > 50cm“
8.10
Piezo „Sash > 50cm“ on/off
8.11
Set delay time „Sash > 50cm“
When steps 1 to 11 have been programmed and checked, the FM100 fume hood monitor is ready for use. All settings are
saved mains voltage failure-safe.
The programming instructions described here are for the service module SVM100. If programming of the FM100 fume
hood monitor is carried out via PC/laptop and the SCHNEIDER software PC-2000 the settings and their explanations are
identical.
The programming options of the service module SVM100 are clearly structured. The buttons needed are described below.
ENT
F1
Selects the previous menu item
+
Value selection or value increment
Selects the next menu item
-
Value selection or value decrement
Menu item selection, entry confirmation and selection
of the previous (sub-) menu item
SPACE
Cancellation of zero-point calibration
F1...F10 Selection of a sub-menu item
The red button function is selected by pressing the SHIFT key and the desired key together.
8.1
Select function display type
Type selection
(see Overview function display type)
Menu item in the
service module
+
FAZ-Type
ENT
-
Type xxx
ENT
Several FAZ types are available for selection (see appendix: Function display type selection). The type selection is a preprogrammed factory setting and refers to the model of the function display and control panel. Please check whether the
correct FAZ type is programmed for the function display type that you use.
16
Operating Manual ● FM100
PROGRAMMING INSTRUCTIONS
8.2
Zero-point calibration of the pressure sensor
Menu item in the
service module
SPACE = Cancel
SPACE
Zero point sensor
ENT
ENTER = Zero point sensor
The static differential pressure transmitter is position-dependent, so calibration may only be carried out in its final mounting position (vertical sensor or horizontal sensor).
CAUTION!
Detach both measuring hoses if zero-point calibration is
to be performed.
Press the SPACE key to cancel the zero-point calibration and the ENTER key to
carry out the zero-point calibration.
8.3
Shield factor of the measuring system and fume hood type
Menu item in the
service module
Setting range
+
Shield factor
-
10 to 250
ENT
ENT
The shield factor is necessary to calculate the exhaust air volume flow (actual value). This actual value is constantly
compared with the programmed setpoints. If the setpoints are exceeded or underrun, an alarm or warning message is
signalled. Selection of the correct shield factor is very important for the efficient functioning of the FM100 fume hood monitor.
The following table illustrates the relationship between the Venturi measuring tube from SCHNEIDER the nominal diameter (DN), the C-value (C), the shield factor (B) and the overall length (L).
C-value=C, Shield factor=B, Overall length=L [mm]
Measuring system
SCHNEIDER venturi
measuring tube
DN160
DN200
DN250
DN315
C
B
L
C
B
L
C
B
L
C
B
L
40
32
190
61
49
210
92
73
230
148
118
600
The C-value of the measuring tube MT depend on fume hood type and must be calculatet once for each type (e.g.
1200, 1500, 1800) by reference measuring (e.g. Venturi measuring tube) according to formula on page 18.
The shield factor must be programmed. It is calculated on the basis of the C value (C) of the measuring system
used, whereby: B = C • 0,8
Operating Manual ● FM100
17
PROGRAMMING INSTRUCTIONS
Using a SCHNEIDER measuring tube, determination of the
volume flow and measuring accuracy can be considerably
improved. The differential pressure will be measured room
pressure independend on the masuring tube. The static
differential pressure transmitter is connected to the (+)
connector and the (-) connector of the measuring tube.
- Connection
p
Differential pressure
+ Connection
Measuring tube
+
Depending on the model and the connection diameter
(DN), each type of fume hood also has a specific shield
factor (C value). This can easily be calculated using the
measuring reports that are available for each fume hood
type.
Flow hood with measuring tube
Calulation formula:
C =
Assumption:
Air density ς = 1.2 kg/m³
V
p
C = Shield factor (C-value)
V = Air volume flow [m3/h]
P = Differential pressure [pa]
The shield factor required for fume hood control is calculated as follows:
B = C 0,8
Sample calculation:
From your test report you establish that the fume hood has a static pressure loss of 42 pascal (pa) at a volume flow
of 480 m³/h.
Thus C is calculated as:
C =
480
= 74
42
B = 74 0,8 = 59
and the shield factor S:
Set the calculated value of 59 for this type of fume hood.
8.4
Enter setpoints for the volume flows
Menu item in the
service module
Settings [m3/h]
Submenu items
+
Setpoint cbm/h
ENT
ENT
Minimum day F1
F1
0 to 2500
Maximum day F2
F2
0 to 2500
Minimum night F3
F3
0 to 2500
Maximum night F4
F4
0 to 2500
-
ENT
Enter the underrun value (Minimum day F1) and, if necessary, the exceedance value (Maximum day F2) for daytime
operation in m³/h. To monitor in night-time reduction mode (reduced operation = non-working time) enter the appropriate
underrun (Minimum night F3) or exceedance (Maximum night F4) value for reduced operation as well.
18
Operating Manual ● FM100
PROGRAMMING INSTRUCTIONS
8.5
Set the alarm delay time
Menu item in the
service module
Settings [s]
+
Delay time
ENT
-
1 to 240
ENT
The alarm delay time defines how long the predefined setpoint must be underrun or exceeded before an alarm or warning
is signalled. The delay time is entered in seconds.
8.6
Set the duration of the acoustic alarm
Menu item in the
service module
Submenu item
Settings [s]
+
Piezo setting
ENT
Piezo duration F1
-
10 to 900
F1
ENT
ENT
The piezo duration defines how long an acoustic is signalled before it is automatically acknowledged. This is entered in
units of 10 seconds.
When an acoustic alarm is signalled, either it switches off automatically after the predefined piezo duration (automatic
alarm acknowledgement) or it can be switched off manually (manual acknowledgement) by pressing the acknowledgement button (Reset). Setting 900 suppresses automatic acknowledgement and allows only manual acknowledgement.
8.7
Set the motor on recognition
Menu item in the
service module
Setting range
+
Motor-On
ENT
-
On/Off
ENT
The Motor on recognition is used to recognize and analyze various operating modes of the fume hood controller.
Motor on recognition OFF
The control function is always active. An alarm (optical and acoustic) is signalled
when the ventilation system is shut down.
Motor on recognition ON
The control system is only active when the Motor on signal (230V AC, optionally 24V AC) is connected to terminal X2.2 and X2.3 (ventilation system is
switched on).
If a Motor on signal is not present, only an optical and not an acoustic alarm is
signalled (ventilation system is switched off).
Operating Manual ● FM100
19
PROGRAMMING INSTRUCTIONS
8.8
Alarm delay after start-up
Menu item in
service module
Setting [s]
+
Delay start
ENT
-
5 to 120
ENT
After start-up, the red LED (underrun) always lights up first. When the volume of air reaches or exceeds the underrun
threshold, the green LED lights up and the red LED goes out. During the predetermined alarm delay time the malfunction relay K1 does not drop out even if the volume of air is too low. It is only activated after the predetermined time (5 to
120s).
This is true for all for methods of switching on and over:
Connection of the supply voltage
Button On/Off
Signal Motor on
Switch to Day/night
This function does not generate an alarm for example, if the exhaust fan is switched on but only reaches its full volume
flow rate after a specific period of time. The alarm delay time after start-up is entered in seconds.
8.9
Define the switch type „Sash > 50cm“
Menu item in the
service module
Type selection
+
Switch type
ENT
-
NC/NO
ENT
The switch type on terminal X7.13 and X7.14 is defined as a normally closed contact (NC) or a normally open contact
(NO).
According to EN 14175 fume hood sashes must be equipped with a mechanical lock at a sash opening of 50cm. If the
sash is opened more than 50cm the mechanical lock must be released. In accordance with this standard, a flashing LED
on the function display signals the condition „Sash > 50cm“ (alarm).
When the contact on terminal X9.13 and X9.14 is open (switch type=normally closed contact) or shut (switch type=normally
open contact) the LED „Close sash“ flashes on the function display.
20
Operating Manual ● FM100
PROGRAMMING INSTRUCTIONS
8.10
Set the piezo Sash > 50cm on/off
Menu item in the
service module
Setting
+
Piezo sash
ENT
-
On/Off
ENT
For a sash opening > 50cm an acoustic alarm (=On) can be programmed in addition to the optical alarm.
8.11
Set the delay time Sash > 50cm
Menu item in the
service module
Settings [min]
+
Delay time
ENT
-
1 to 240
ENT
The delay time defines how long the contact on terminal X9.13 und X9.14 must be open (switch type=normally closed
contact, NC) or shut (normally open contact, NO) before an acoustic alarm (see 8.10 Piezo sash) is signalled. The delay
time is entered in minutes.
The optical alarm is signalled directly without delay.
Operating Manual ● FM100
21
MAINTENANCE • TROUBLESHOOTING
9.0
MAINTENANCE
The FM100 fume hood monitor requires no special maintenance.
However, you must ensure that the PVC measuring hoses are not damaged or
buckled and that they are securely attached to the measuring system and the
sensor.
9.1
ANNUAL FUME HOOD
MAINTENANCE
Annual fume hood maintenance must include a function test that signals the
acoustic and optional alarm (detach the measuring hoses). Following zero-point
calibration of the differential pressure transmitter (only to be carried out when
the measuring hoses are detached), see Chapter 8.2, the setpoints must be
checked via the service module or laptop. Finally, select the menu item Actual
value in the SVM100 service module and compare the exhaust air actual value
(reattach the measuring hoses first) with a redundant measuring value (hot-wire
or vane anemometer).
9.2
POWER PACK
The 6V/1.2 Ah power pack must undergo maintenance checks at regular intervals and must be exchanged after a maximum of five years. The FM100 fume
hood monitor has an integrated power pack charging connection.
10.0
TROUBLESHOOTING
Use the following table to analyze problems and their possible causes and to correct them.
PROBLEM
LEDs do not light up.
LEDs flashing.
CAUSE
Power supply not connected or faulty.
Check the cable connection between the function display panel and the sensor
box.
Wrong setting for FAZ display type.
Jumper JP1 function display parallel/serial incorrectly connected or not connected at all.
Check the cable connection between the function display panel and the sensor
box.
Carry out or repeat the zero-point calibration (see Chapter 8.2).
Actual value (via service module)
is not identical with the externally
measured actual value.
Check the shield factor (see Chapter 8.3).
Check that the PVC measuring hoses are firmly attached (measuring system
and differential pressure transmitter) and are not bent or buckled.
Check the data cable connection between the service module and the function
display panel.
Check whether the Motor on recognition is activated. (=On).
Function display is not working
properly (LED always red).
If Motor on recognition = On. Check whether current is not connected to the
Motor on terminal or is faulty.
Check the Minimum day and Minimum night setpoints.
Function display is not working
properly (LED always green).
Check the Minimum day and Minimum night setpoints.
Function display is not working
properly (LED always yellow).
Check the setpoints Maximum day and Maximum night.
The red and green LEDs are flashing alternately.
The differential pressure transmitter or the flow sensor is faulty.
22
Operating Manual ● FM100
TECHNICAL DATA • DIMENSIONS
TECHNICAL DATA
General
Nominal voltage
Max. charging rate
Max. power input
Reactivation time
Operating temperature
Humidity
Case
Protection type
Material
Colour
Dimensions (LxWxH)
Weight
Terminals
Relay outputs
Number
Contact type
Max. switching voltage
Max. continuous current
Number
Contact type
Max. switching voltage
Max. continuous current
230 V AC/50/60Hz/+-15%
200 mA
10 VA
600ms
0 OC bis +55 OC
max. 80 % relative, noncondensing
IP 20
Sheet steel
white, RAL 9002
(185 x 167 x 92) mm
approx. 1.4 kg
Screw terminal 1.5 mm2
caged spring terminal
1.5 mm2
Digital inputs
Number
Activation
11.0
3 inputs, 5 V DC/2 mA
potential-free contact, maximum cable length < 5 m
Analogue output
Exhaust air actual value
0(2)...10VDC, 10 mA
Analogue input
Setpoint value
0(2)...5/10VDC, 1 mA
Differential pressure transmitter
Measuring principle
static
Pressure range
6...240 pascal
20...640 pascal optional
Response time
<10 ms
Overpressure max.
500 mbar
Optional measuring system
1 relay (K3)
normally open contact
250 V AC
12 A
2 relays (K1, K2)
changeover contact
250 V AC
3A
Material
Measuring system
Polypropylene (PPs)
Measuring device or venturi
measuring tube
DIMENSIONS
CASE
Case FM100
Top view
11.1
Case FM100
Side view
185
92
Static differential
pressure transmitter
+ = overpressure
- = underpressure
-
167
Case
earthing
+
Cable entry point
and pull relief
Operating Manual ● FM100
23
TECHNICAL DATA • MEASURING SYSTEM
11.2
DATA VENTURI
MEASURING TUBE
Measuring device with integrated venturi
measuring tube, model: PPs, Socket/socket
DN
Nominal diameter [mm]
DN 160
DN 200
DN 250
DN 315
11.3
Socket/socket
length
[mm]
190
210
230
600
Flange/flange
length
[mm]
160
160
180
500
VMIN
[m3/h]
VMAX
[m3/h]
C value
Shield factor
S
100
180
250
400
480
800
1200
1950
40
61
92
148
32
49
73
118
DATA MEASURING
TUBE
Available lengths [mm]
160, 200, 250
315, 400, 500
600, 700, 800
The C-value of the measuring tube MT depend on fume hood type and
must be calculatet once for each type (e.g. 1200, 1500, 1800) by reference
measuring (e.g. Venturi measuring tube) according to formula on page
18.
The shield factor must be programmed. It is calculated on the basis of the
C value (C) of the measuring system used, whereby:
B = C • 0,8
24
Operating Manual ● FM100
INDEX
INDEX
A
P
Alarm delay time after start-up 16, 20
Alarm delay time, setting 16, 19
ANNUAL MAINTENANCE 22
Attachment A1
PERFORMANCE FEATURES 5
Piezo duration, setting 16, 19
Piezo Sash > 50cm“, setting 16, 20
POWER PACK 22
PROGRAMMING INSTRUCTIONS 16
PVC HOSES, ATTACHING TO THE SENSOR 8
C
CASE COVER, OPENING 8
CE NOTE 5
CONNECTION ANALOGUE INPUT 12
CONNECTION ANALOGUE OUTPUT 12
Connection cable 6
CONNECTION DIGITAL INPUT 10
CONNECTION FLOW SENSOR 13
CONNECTION FUNCTION DISPLAY 8
CONNECTION MAGNETIC VALVE 12
CONNECTION MOTOR ON RECOGNITION 10
CONNECTION RELAY ALARM (K1) 14
CONNECTION RELAY LIGHT (K§) 14
CONNECTION RELAY MOTOR (K2) 14
CONNECTION RELAY OUTPUTS 14
CONNECTION SUPPLY VOLTAGE
ANALOGUE INPUT 12
D
12.0
R
RELAY OUTPUTS 14
S
Safety instructions 2
SAMPLE CALCULATION 18
Sash >50cm (In 3) 11
SCOPE OF DELIVERY 6
Selection of the function display type 16
Setpoint specification 16
Setpoint specification of volume flows 16, 18
Shield factor of the measuring system
or fume hood type 16, 17
Static differential pressure transmitter 6
Switch type „Sash > 50cm“, setting 16, 20
DATA MEASURING TUBE 24
DATA VENTURI MEASURING TUBE 24
Day/night (In 2) 11
Declaration of conformity 1
Delay time „Sash > 50cm“, setting 16, 21
Differential pressure transmitter 6
DIMENSIONS CASE 23
Duration of the acoustic alarm, setting 16, 19
T
E
Zero-point calibration of the pressure sensor 16, 17
TABLE OF CONTENTS 3
TECHNICAL DATA 23
TERMINAL DIAGRAM 7
TROUBLESHOOTING 22
Z
Electrical connection 2
EMERGENCY POWER PACK 9
Errors, overview 22
F
FUNCTIONAL DESCRIPTION 4
FUNCTIONAL DIAGRAM 5
FUNCTION DISPLAY PANEL 4, 15
I
INSTALLATION AND SETUP INSTRUCTIONS 6
INSTALLATION OF ADDITIONAL FUNCTIONS 10
INSTALLATION • THE FIRST FIVE STEPS 8
M
MAINS CONNECTION 9
MAINTENANCE 22
Motor on recognition, setting 16, 19
O
On/off (In 1) 11
Operating Manual ● FM100
25
SCHNEIDER Elektronik GmbH
Phone: +49 (0) 6171 / 88 479 - 0
Fax:
+49 (0) 6171 / 88 479 - 99
Industriestraße 4
e-mail:
[email protected]
61449 Steinbach • Germany
www.schneider-elektronik.com
26
Operating Manual ● FM100