Download Generator Backup Protection System backup for generators and

Survey
yes no Was this document useful for you?
   Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Document related concepts

Fault tolerance wikipedia , lookup

Electric power system wikipedia , lookup

Stepper motor wikipedia , lookup

Mercury-arc valve wikipedia , lookup

Pulse-width modulation wikipedia , lookup

Power inverter wikipedia , lookup

Electrical ballast wikipedia , lookup

Power engineering wikipedia , lookup

Ohm's law wikipedia , lookup

Ground loop (electricity) wikipedia , lookup

Current source wikipedia , lookup

Variable-frequency drive wikipedia , lookup

Resistive opto-isolator wikipedia , lookup

Triode wikipedia , lookup

Islanding wikipedia , lookup

Power MOSFET wikipedia , lookup

Electrical substation wikipedia , lookup

Rectifier wikipedia , lookup

Distribution management system wikipedia , lookup

History of electric power transmission wikipedia , lookup

Ground (electricity) wikipedia , lookup

Voltage regulator wikipedia , lookup

Opto-isolator wikipedia , lookup

Protective relay wikipedia , lookup

Earthing system wikipedia , lookup

Metadyne wikipedia , lookup

Switched-mode power supply wikipedia , lookup

Buck converter wikipedia , lookup

Surge protector wikipedia , lookup

Stray voltage wikipedia , lookup

Voltage optimisation wikipedia , lookup

Three-phase electric power wikipedia , lookup

Alternating current wikipedia , lookup

Mains electricity wikipedia , lookup

Transcript
Generator Backup Protection
3
System backup for generators
and transmission lines.
Features and Benefits
Applications
■
Waveform sampling of current and
voltage inputs
■
Backup protection for generators or
transmission lines
■
High-resolution oscillography and
playback
■
Three-phase tripping applications
■
enerVista.com compatible (see page 275)
■
Four zones of phase and ground mho
distance functions
■
Out-of-step blocking and tripping
available
■
Out-of-step tripping
■
Over and undervoltage functions
■
Phase and ground overcurrent
instantaneous backup
Monitoring and Metering
■
Ground time overcurrent backup
■
User-configurable I/Os
■
Integrated RMS metering
■
Horizontal and vertical models
Protection and Control
■
Fault location, event and fault recording
■
Currents, voltages, watts, vars and
frequency
User Interfaces
■
LCD and keypad
■
RS232 and RS485 serial ports
GE Multilin
1
LPS-O™ Generator Backup Protection
Protection and
Control
The LPS-O provides backup protection for generators and
transmission lines. Advanced
protection functions include:
3
Distance
Four zones of phase step distance
protection are provided. Functions
are positive sequence voltage polarized mho characteristics. The
reach of the three forward looking
zones can be compensated for a
delta-wye transformer.
Zone 4 is reversed and disregards
any transformer between the relay
and the fault in the forward direction. Zones 1, 2, 3, and 4 each
include independent timers for
phase step distance protection.
Out-of-step blocking monitors
swing condition and blocks tripping. Out-of-step tripping logic is
provided with a choice of two or
three mho type characteristics
with adjustable shapes.
Forward and reverse share a
common maximum reach angle.
Loss of synchronism or a power
swing between two areas of the
power system is detected by
measuring the positive sequence
impedance seen by the relay over
a period of time as the power
swing develops.
Directional Ground Overcurrent
The ground directional functions
are forward and reverse negative
sequence current and voltage operated. The ground instantaneous
and TOC functions can be independently set with directional
control.
Overcurrent Backup
The LPS-O provides instantaneous phase and ground
overcurrent functions. The phase
backup consists of an instantaneous
function.
Ground
overcurrent backup consists of
IOC and TOC functions. The TOC
function includes four selectable
and one programmable curve.
The ground overcurrent functions
can be controlled by the directional functions. Both IOC and
TOC functions can be set as nondirectional or directional.
The LPS-O provides an adaptive
sensitive current disturbance detector (fault detector) and an
unbalanced current alarm to detect open or shorted CT leads.
Voltage
Three single-phase under and
overvoltage detectors and a positive sequence overvoltage detector
are provided.
Configurable I/Os
All 12 contact converter inputs
and 20 contact outputs (except
for alarms) are user-configurable.
SCR tripping outputs are available for high speed operation.
Monitoring and
Metering
The LPS-O provides sophisticated
monitoring and metering functions that include:
Trip Circuit Monitor
Fuse failure logic detects a full or
partial loss of AC potential and
blocks tripping of distance and
directional functions. The LPS-O
has a three-wire voltage input
suitable for either delta or wye
connected VTs.
DC battery voltage is monitored
across each open trip contact. An
alarm triggers when the voltage
becomes virtually zero. A current
sensor in series with each trip
contact is provided, to log an
event message on the DC trip
current status following the trip.
Scheme Logic
Metering
The LPS-O provides userprogrammable logic with up to
40 gates and eight timers.
The LPS-O provides the following
RMS metering values:
■ Current (Ia, Ib, Ic, In)
■ Voltage (Vab, Vbc, Vca)
■ Watts (three-phase)
■ Vars (three-phase)
■ Frequency
Manual Breaker Control
Manual circuit breaker tripping or
closing can be done locally or remotely.
Multiple Settings Groups
Two separate groups of protection settings may be stored in the
LPS-O non-volatile memory. The
active settings group can be selected by the user.
The currents are calculated for
each phase, and voltages are calculated between phases. The
accuracy is 1% of rated current
and voltage. The phasor value
(magnitude and angle) of the
phase currents and voltages are
also displayed.
Functional Block Diagram
G
Metering
50P 21P
78
LPS-O
50/
67N 67P 51G
27
59
lpso_fbd.ai
2
www.GEindustrial.com/Multilin
LPS-O™ Generator Backup Protection
The LPS-O stores up to 150 events
with the date and time stamped to
the nearest millisecond. This aids
the user with determining the sequence of events, facilitating
diagnosis and recovery.
Typical Wiring
A
B C
TRIPPING DIRECTION
52
CONNECTION
AS REQUIRED
C1
C2
C3
C4
C5
C6 C13 C14 C9 C10 C11 C12
Vs Va Vb Vc Vn
C(B)
A
CURRENT INPUTS
B(C)
A8
CONTROL
POWER
GE Multilin
T2
LPS
T3
Line Protection System
T5
CC1
T6
CC2
C1
CC3
CC4
CC5
CC6
CC7
CC8
CC9
C2
A1
A2
CC10
CC11
UNMODULATED
IRIG-B
Breaker Health
OUTPUTS
CC12
CONFIGURABLE (SHOWN WITH DEFAULT SETTINGS)
The LPS-O relay can playback
stored waveform files through
the relays processor, allowing the
user to playback faults with different settings.
T4
INPUTS
D2
D18
D3
D19
D4
D20
D5
D21
D6
D22
D7
D23
D8
D24
D9
D25
D10
D26
D11
D27
D12
D28
D13
D29
D1
D17
A3
A4
A5
A6
A7
A8
A9
A10
A11
A12
DB-9
RS232
PL1
(FRONT)
KT1
KT2
PL2A
(REAR)
DB-25
RS-232
KT3
Self-Test Diagnostics
4 WIRE / 2 WIRE
RS-485
DB-25
RS-232
KT4
PL2B
(REAR)
PL3
(REAR)
OPTIONAL
RS-485
OPTIONAL SINGLE POLE MODEL
www.GEindustrial.com/Multilin
FAULT
LOCATION
FIXED
Self-test routines are performed
during power up and continue in
the background during service.
Failures are categorized as either
critical or non-critical alarm and
recorded in the event log.
A2
GROUND
BUS
VOLTAGE INPUTS
T1
Oscillography can be triggered by
internal or external signals.
Internal signals include trip outputs or a programmable logic
signal. The supplied out-of-step
trip logic features a three second
oscillography data file consisting
of phasor values of the currents
and voltages captured at a rate of
one per cycle. The LPS-O has the
capability to store the oscillography files in Comtrade format.
The breaker health threshold is
set by the user to achieve “just in
time” maintenance. When the cumulative value of the three-phase
currents exceeds the threshold,
an alarm occurs. The user can adjust the threshold for breakers
with previous duty.
A1 A17
I A I AR I B I BR I C I CR Vs
CONFIGURABLE (38.5 TO 300 VDC)
The LPS-O captures current and
voltage waveforms and selected
internal logic signals at 64 samples
per cycle. The unit can store from
six events of 72 cycles each to 36
events of 12 cycles each. The time,
date, active settings, and fault report are stored with the data
capture. Prefault data can be set
from one to eight cycles.
3
CONTROL
POWER
SUPPLY
Oscillography
GROUND
SURGE
Event Recording
CRITICAL
ALARM
POWER
SUPPLY
ALARM
I/V
A3
A19
A4
A20
A5
A21
A6
A22
A7
A23
A8
A24
B27
B11
B28
B12
B29
B13
A9
A25
A10
A26
A11
A27
A12
A28
A13
A29
A14
A30
A15
A31
A16
A32
B1
B17
B2
B18
B3
B19
B4
B20
B21
B5
B22
B6
B23
B7
B24
B8
B25
B9
B26
B10
D16
D32
B30
B14
B31
B15
B32
B16
730750A3.CDR
3
LPS-O™ Generator Backup Protection
LPS-O Technical Specifications
Time Synchronization
An IRIG-B input is provided for time
synchronization via satellite signal.
Security
There are separate remote passwords which permit view only,
view and settings changes, or view,
settings, and control capability.
3
Software
Windows®-based software packages are included in the LPS-O
instruction book.
■ LPS-O LINK – allows communication with the relay using GE
protocol
■ XPRESSION BUILDER™ – allows
the user to graphically design
programmable logic settings and
I/O assignments
The user may also obtain GE-DATA
or GE-OSC to analyze oscillography data.
LPS-O Guideform
Specifications
For an electronic version of the LPS-O
guideform specifications, please
visit: www.GEindustrial.com/
Multilin/specs, fax your request
to 905-201-2098 or email to
[email protected].
PROTECTION
In = 1
45 – 90°
45 – 90°
Positive sequence angle:
Zero sequence angle:
Zero sequence current :
Compensation (K0):
Zone 1, 2, 3 and 4 reach:
Zone 4 offset reach:
In = 5
45 – 90°
45 – 90°
1.00 – 7.00
1.00 – 7.00
0.05 – 250 Ω
0.01 – 50 Ω
0.00 – 0.40
0.00 – 0.40
(Zone 4 is reversible)
0.10 – 3.00 sec
0.10 – 3.00 sec
0.10 – 10.0 sec
0.10 – 10.0 sec
0.4 – 32 A
2.0 – 160.0 A
0.1 – 16.0 A
0.5 – 80.0 A
0.04 – 3.00 A
0.20 – 15.00 A
Inverse, very inverse, extremely
inverse, definite and custom
Zone 2 timer:
Zone 3 and 4 timers:
Phase instantaneous OC:
Ground instantaneous OC:
Ground TOC:
TOC curves:
RECLOSURE (OPTIONAL)
Reclose attempts:
Synchronism check:
4
Optional
METERING
Frequency:
Voltage (ph-ph):
Current (In):
Maximum permissible current:
Continuous:
MONITORING
Records:
Record length:
Pre-fault cycles:
Samples per cycle:
3 A for In = 1 A
15 A for In = 5 A
50 x In
100 x In
138 VAC (ph-n)
3.5 x rated
0.02 Ω at 5°
0.12 Ω at 30°
0.20 VA
0.15 VA
In = 1
In = 5
50 Hz
60 Hz
DC battery:
Power supply:
Contact converters:
<20 W
2.5 mA each
POWER SUPPLY
Control voltage:
48 VDC
110/125 VDC
220/250 VDC
High speed (KT1 – KT4):
Continuous = 5 A
Make & carry = 30 A
Interrupting: 25 VA
Pickup <8 ms
Continuous = 0.5 A
Max voltage = 280 VDC =
Pickup <0.5 ms
ENVIRONMENTAL
Ambient temperature range:
Storage:
-30° C to +75° C
Operation:
-20° C to +60° C
Humidity:
95% without condensation
5 – 300 VDC (jumper selectable)
Voltage circuits:
Auxiliary
(A1 – A12):
(C1, C2):
INSTRUCTION BOOK
Single-pole GEK 106202
Three-pole GEK 106159
6 – 36
72 – 12 cycles
1–8
64
INPUTS
Contact converter inputs:
BURDENS
Current circuits:
Trip SCR (T1 – T6):
Continuous = 5 A
Make & carry = 30 A per ANSI C37.90
Interrupting: 25 VA
Pickup <4 ms
Continuous = 5 A
Make & Carry = 30 A per ANSI C37.90
COMMUNICATIONS
Protocol:
ASCII, GE-MODEM
Ports:
Front:
1 DB9, RS232
Rear:
1 DB25, RS232 and 4 pin Phoenix, RS485
(standard): 1 DB25, RS232
or RS485 optional
Display:
4 line liquid crystal display standard
Keypad:
Full numeric keypad standard
50 or 60 Hz
100 – 120 VAC
1 or 5 A
Three sec:
One sec:
Maximum permissible AC voltage:
Continuous:
One minute:
OUTPUTS
CONTACT RATINGS
Trip contact (T1 – T6):
Range:
38.5 – 60.0 VDC
88 – 150 VDC
176 – 300 VDC
TYPE TESTS
Insulation test voltage:
2 kV, 50/60 Hz, 1 min
(high-pot) ANSI C37.90
IEC 255-5
Impulse voltage withstand fast transient:
5 kV peak, 1.2/50 µs, 0.5 J
IEC 255-4
ANSI C37.90.1
Surge withstand capability (SWC):
ANSI C37.90.1
IEC 255-22-1
Radio frequency interference withstand (RFI):
ANSI C37.90.2
IEC 255-22-3
Electrostatic discharge (ESD): IEC 255-22-2
*Specifications subject to change without notice.
Ordering
LPS
* * * * * * * * * * **
LPS
O
B
3
5
U
NOTE: For dimensions see ALPS
brochure.
0
1
2
1
2
3
H
V
E
1
N
enerVista enabled
See page 275.
www.enerVista.com
™LPS-O is a trademark of GE Multilin.
4
Line protection system
Phase distance relay with out-of-step tripping
(system phase backup)
Revision level B
Three-phase tripping logic
5 A rated current
For applications without series capacitors
48 VDC battery voltage
110/125 VDC battery voltage
220/250 VDC battery voltage
SCR trip outputs and contact channel interface
Contact trip outputs and contact channel interface
Front RS232 com port and 2 selectable RS232/RS485 rear port
(GE-MODEM/ASCII)
Horizontal mounting
Vertical mounting
Extended oscillography memory
With out-of-step tripping
No reclosure
Accessories:
158D7358P1
158D7359P1
L2 Flange for vertical mounting
KD Flange for vertical mounting
www.GEindustrial.com/Multilin