200 Series
Mounting Base Options
System Sensor mounting bases and kits provide a
variety of ways to install detectors in any application.
Features
•Easy plug-in of detector to base
•SEMS screws, 12-24 AWG (14-24 for B224RB and B224BI)
•Multiple accessories for mounting flexibility
•UL 464 and UL 864 Compliant Sounder Bases
200 Series detectors can be mounted in either flanged or flangeless
bases depending on junction box selection (see junction box
selection guide).
Features. Relay, isolator, and sounder bases can be used to meet
local code requirements. Relay bases provide one form C contact
relay for control of auxiliary functions such as door closure and
elevator recall. Isolator bases allow loops to continue to operate
under fault conditions and automatically restore when the fault is
removed. Sounder bases are available in temporal and non-temporal
pattern versions depending on whether the signal is to be used for
evacuation purposes.
Mounting. The recessed mounting kit provides the most
aesthetically pleasing installation. Surface mounting boxes are
available when flush mounting isn’t possible. Whatever the
installation challenge, System Sensor has the solution.
Agency Listings
Model
Listings
B501
UL, ULC,* FM, CSFM, MEA
B210LP
UL, ULC, FM, CSFM, MEA
B501BH, B501BH-2, and B501BHT-2
UL, ULC, CSFM, MEA
B501BHT
UL, ULC, CSFM
B224RB
UL, ULC, CSFM, MEA
B224BI
UL, ULC, FM, CSFM, MEA
* For ULC listed products, add “A” to the model number (e.g., B501A).
Specifications, 200 Series Bases
Physical Specifications
Diameter
B501: 4.1 in (104 mm); B210LP, B224RB, B224BI: 6.1˝ (155 mm); B501BH, B501BHT, B501BH-2, B501BHT-2: 6.0 in (152 mm)
Wire Gauge
B224BI, B224RB: 24 to 14 AWG; B501, B210LP, B501BH, B501BHT, B501BH-2, B501BHT-2: 24 to 12 AWG
Temperature Range
32°F to 120°F (0°C to 49°C); B501, B210LP: –4°F to 150°F (–20°C to 66°C)
Humidity Range
10% to 93% RH non-condensing
B224RB/B224BI Electrical Ratings
B501BH/B501BHT/B501BH-2/B501BHT-2 Electrical Ratings
Operating Voltage
15 to 32 VDC (powered by SLC)
External Supply Voltage
17 to 32 VDC
Standby Ratings
<500 µA maximum @ 24 VDC
Standby Current
1.0 mA max.
Set Time (B224RB only)
Short Delay: 55 to 90 msec
Set Time
B501BH/B501BHT: 6 to 15 sec
Long Delay: 6 to 9 sec
B501BH-2/B501BHT-2: 0.75 to 5.7 sec
Reset Time (B224RB only)
20 msec max.
Maximum Ripple Voltage 10% of supply voltage
Relay Characteristics
2 coil latching relay
Sound Output
Greater than 90 dBA measured in anechoic
(B224RB only)
1 Form C contact
room at 10 feet, 24 volts. 85 dBA minimum in UL
UL/CSA Rating: reverberant room
0.9 A @ 125 VAC Alarm Current
15 mA max.
0.9 A @ 110 VDC Start-up Capacitance
200 µF
3 A @ 30 VDC
200 Series Junction Box Selection Guide
Model
Single
Gang
3.5 in
Octagonal
4 in
Octagonal
4 in
Square
4 in
Square*
50
mm
60
mm
70
mm
75
mm
B501
No
Yes
No
No
Yes
Yes
Yes
Yes
No
B210LP
Yes
Yes
Yes
Yes
Yes
No
No
No
No
B224RB
No
Yes
Yes
Yes
No
No
Yes
Yes
Yes
B224BI
No
Yes
Yes
Yes
No
No
No
Yes
Yes
B501BH /B501BH-2
No
No
No
Yes
No
No
No
No
No
B501BHT /B501BHT-2
No
No
No
Yes
No
No
No
No
No
* with 3.0 in mud ring
Note: Box depth contingent on base and wire size. Refer to National Electric Code or applicable local codes for appropriate recommendations.
Ordering Information, 200 Series Bases
Model
Description
B501*
Flangeless Mounting Base
B210LP*
Flanged Mounting Base
B501BH*
Standard Sounder Base
B501BHT*
Temporal Tone Sounder Base
B501BH-2
Standard Sounder Base, UL 864 9th edition compliant
B501BHT-2
Temporal Tone Sounder Base, UL 864 9th edition compliant
B224RB*
Relay Base
B224BI*
Isolator Base
RMK400
Recessed Mounting Kit
SMK400
Surface Mounting Kit (flangeless)
SMB600
Surface Mounting Kit (flanged)
F110
Retrofit flange for B501B/B524
200 Series Accessories
RA400Z* /
Remote LED Annunciator
RA100Z*
M02-04-01
Detector Test Magnet
M02-09-00
Test Magnet with Telescoping handle
XR2B
Detector Removal Tool (T55-127-000 Included)
XP-4
Extension Pole for XR2B (5 to 15 ft.)
T55-127-000
Detector Removal Head
BCK-200B
Black Detector Kit
WCK-200B
White Detector Kit
Recessed Mounting Kit Product Overview
Used with B501, the RMK400 provides a simple installation solution
in applications that demand a lower profile smoke detector. Kit is
suitable for use with 4˝ octagon, 50mm, and 60mm junction boxes
connected­ to flexible conduit. Junction boxes are not included in kit.
•Drywall or suspended ceiling
•Standard junction boxes
•Aesthetically pleasing
* Add “A” to model number for ULC listed product (e.g., B501A)
3825 Ohio Avenue • St. Charles, IL 60174
Phone: 800-SENSOR2 • Fax: 630-377-6495
©2009 System Sensor.
Product specifications subject to change without notice. Visit systemsensor.com for
current product information, including the latest version of this data sheet.
A05-1020-005 • 7/09 • #2206