Compliance Sheet of New Doctors Accommodation Building in Tikrit
Educational Hospital
The following Technical data shall be furnished and filled by the bidders:
1- Diesel Generator 500KVA
UNDP specifications
Three phase four wires, output voltages 100-400V, 50HZ, between 0.8
lagging, protection capability abiding by the standards of NEMA1 and
IP23.
General features:
● Composed of western diesel engine
and European Type alternator
● Oil and fuel filter fitted, water separator
● Lube-oil drain valve fitted
● Electric starter motor 24 V. D.C
● Output range: Prime-500kVA / Standby-550KVA
● Engine model: 2506(A or C)-E15TAG2
● Induction system: Turbocharged
● 8-hour operation base tank
● Key start / auto start
● Mechanical /Electrical governor
● 4 pole MCCB, set mounted starting battery
● Soundproof or weatherproof canopy
● Operation & Maintenance manual
● Special Integrated Steel Base tank and sprayed overall in gloss enamel
paint
Engine Specifications
In-line direct injection 6-cylinder diesel engine.
Type
Water cooled, four cycle, Turbocharged
Construction
Two valves per cylinder, forged steel crankshaft and
connecting rods,
cast iron block.
Starting 24 volt negative earth. battery charging
alternator 35 amp on engine. Cranking current 640
amps at 0oc.
Fuel System
24 volt fail safe actuator. Spin-on paper
element fuel filters with Bosch fuel pump injection
system with integral
Bidders’
Offered
specifications
Electronic governor. Dual flexible fuel lines
And connectors. Standard fuel water
separator. Filters.
Air cleaner with dry element and restriction indicator.
Spin full flow lube oil
filter. Oil cooler. Drain
Tap
Control Panels
Standard Control Function
● Under / Over
Mains
Volts
/Frequency
● External
Remote
control start output
(load /
un-load)
● Configurable
relay outputs
● Synchronization
auto
/
synchronization
output
● All
function
telecom
remote
control
● Engine and Alternator instrumentation monitor
● Configurable input trip point by 9 users
● 4 user output trip point
● Control LCD brightness in low
brightness environment
● PIN password
● Send SMS via GSM modem
● Reflect load relay output
•Control vary trip point
● AC ALTERNATOR
Alternator Technical
Data European Type AC
alternator
● Brushless, self exciting
● Class ‘H’ insulation
● Standard degree of protection is IP23
● Self regulating
● With fan cooling
● Resist humid grease
● AC excitation, rotating rectification tube
● Stator grease insulation covered
● Rotator and excitation high polymer, Resist
the corruption of oil and acid.
● Rotator balance is in accordance with
BS5625 standard 12.5
● High-quality lubrication sealed long-time bearing
● Rotator silicon steel close tight
2- Electrical Distribution Transformer 400 KVA
# UNDP specifications
1- Transformer:
 Make: ABB, Schneider, Siemens ,LS or
equivalent …… wound, 3-phase
 Rated Power:400KVA,
 Voltage :11000 V /416 V
 Current : 52.49 A / 1387.86 A
 Vector Group : Dyn11
 Cooling type : ONAN
 Frequency:50Hz
●Temperature rise ………( i ) 45 K in
top oil by thermometer
( ii ) 50 K in winding by resistance
●The efficiency (at unity power factor
and 100% of rated power) of the
transformer should be not less than
98.8%
● The duration of the short circuit to
raise the temp. of windings from 1050 C
to 2500 C should be not less than (5 Sec.)
according to IEC 60076-part 5 –clause
(4.1.5)
● The thickness of the radiator plates
should be shock resistant and don’t
affect heat dissipation according to
tender requirements.
● The noise level should be ≤ 55 dB at
0.3 meter distance according to IEC
standards.
● The low voltage winding must be of
copper foil
● Off-load tap changer . . . . . five
tapping for (± 2.5%, ± 5%) on the H.T
winding for off-circuit operation
Bidders’ Offered
specifications
externally. The mechanical operation
must be of the robust and definite
position type with a click indicating
position arrived during tap changing
with suitable pad-lock.
● System Highest Voltage. . H.V side 12
kV
● The 11 kV side terminal is to be flat bar only
● For 400 kVA transformers should be
either box-type or plug-in type for H.V.
side (according to the tender
requirements) with glands and cable
holes suitable for cable size of 1 x 50
mm2 , 12/20 kV.
● For L.V. side with glands and cable
holes suitable for cable size of 1 x 240
mm2
● The cables arrangement as specified
below:
For 400 KVA transformer 11x1x240
mm2 copper (4 holes per phase).
3- Window Air-Conditioner 24,000 BTU Heat/Cool
UNDP specifications
Performance
EER
Dehumid. (Pts/Hr)
Dry Air Flow (CFM)
dBA Level (Indoor / Outdoor)
Est. Cooling Area (Sq. Ft.)
BTU Performance
9.4
7.8
540
65/68
1001-1500
23,500 / 24,000
FEATURES
Heating & Cooling
Air Deflection
Auto Swing
Programmable Timer
Fan Only Speed
Indoor Fan Type
Outdoor Vent / Exhaust
Thermostat Control
Remote Control
Energy Saver Function
Fan Speed: Cooling (Heating)
Yes
4-Way
Yes
12Hr, On/Off
3
Blower
Yes
Electronic
Yes
Yes
3 (3)
Compressor
Rotary
Type Air Discharge
Side by side
Chassis Type
ELECTRICAL RATINGS
Voltage / 60 Hz
Watts (Cooling)
Rated Amps (Cooling)
Slide In-Out
208/230
2,500/2,550
12.1/11.1
Bidders’ Offered
specifications