DATA SHEET
VOCIA® CI-1
CONTROL INTERFACE
The CI-1 Control Interface is a device that serves as a companion product to the Vocia LSI-16 and LSI-16e Life
Safety Interfaces. The CI-1 requires an LSI-16 or LSI-16e for operation. Once the required interconnections
have been established, the CI-1 will operate with the LSI-16 and LSI-16e to provide the necessary life safety
functionality. The CI-1 also facilitates the necessary connections to the LSI-16 and LSI-16e for EN 54-16
standards compliance.
FEATURES
•High reliability switches for Local Sounder Silence, System
Test and System Fault Reset
•Provides terminating resistors for any unused monitored
outputs for Vocia Life Safety Interface devices
• High level sounder for Fault and Alarm warning
• Current limited reference voltage output
• Dual 24V DC power inputs with uninterrupted failover on
power loss
• Rack mountable (1RU)
•Provides terminating resistors for Alarm and Fault Inputs
for LSI-16 and LSI-16e Life Safety interface devices
• Covered by Biamp Systems’ 5-year warranty
• CE marked, UL listed and RoHS compliant
ARCHITECTS & ENGINEERS SPECIFICATION
The control interface shall be designed exclusively for use with Biamp® Vocia systems in conjunction with the Vocia Life
Safety Interface. The control interface shall provide a sounder to deliver audible notification of alarm, fault or trouble
conditions. It shall provide switches for local sounder silence, system test and system fault reset and shall provide
pass-through interconnections for connection of the Life Safety Interface to fire detection equipment, connections for
Ethernet fault and power supply fault signals, required termination resistors and summing for dual 24V power supplies.
The life safety interface shall be EN 54-16 Certified Product 082-CPD-1401, UL listed and shall be compliant with the
RoHS directive. Warranty shall be five years. The control interface shall be a Vocia CI-1.
A: 9300 S.W. Gemini Drive Beaverton, OR 97008 USA
T: +1 503.641.7287
W: www.biamp.com
VOCIA CI-1 SPECIFICATIONS
Alarm Inputs:
Assertion:
Overall Dimensions:
Height:
Width:
Depth:
Weight:
Transition from 0V to 12-24V
Fault Inputs:
Assertion:
Maximum pull-up resistor:
Transition from +V to 0V
2.2kΩ
Environment:
Ambient Operating
Temperature Range: Humidity:
Altitude: Outputs:
Assertion:Low
Pull-up Load:
max 2.2kΩ
Maximum External Supply:35V
Maximum Continuous Current
350mA
Current Limit:
800mA
Power: 1.75 inches (44.5 mm)
19.0 inches (483 mm)
10.0 inches (254 mm)
6.4 lbs (2.8 kg)
32-113° F (0 – 45° C)
0 – 100% non-condensing
0-10,000 Feet (0-3000 Meters) MSL
Compliance:
Dual 24V DC, 15W each
EN 54-16 certified
CE marked (Europe)
UL and C-UL listed (USA and Canada)
RINA (Italy)
RoHS Directive (Europe)
EN 60849, AS 60849 verified
VOCIA CI-1 BACK PANEL
BIAMP SYSTEMS
10
Designed in Australia
Assembled in USA
0832-CPD-1401
CIE (Fire Detection System)
A1 A2 A3 A4
Rs Si
Fault Inputs
VA GF
P
N24138
52SJ
To LSI-16 Monitored Outputs
UE
W
5
6
7 4 8 10V
3
To LSI-16
System Fault
To LSI-16 Control Inputs
2
1
3
4 2
1 5
6
7
8
C NC NO
A: 9300 S.W. Gemini Drive Beaverton, OR 97008 USA
To LSI-16
24V
Input
2 x 24V
15W Class 2 or LPS
Model CI-1
Power Supply
1
T: +1 503.641.7287
2
Vref. 24V 100mA
W: www.biamp.com