Download 2033D Facility Planning Data Sheet

Survey
yes no Was this document useful for you?
   Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Document related concepts

Stepper motor wikipedia , lookup

Ohm's law wikipedia , lookup

Switch wikipedia , lookup

Solar micro-inverter wikipedia , lookup

Power engineering wikipedia , lookup

Phone connector (audio) wikipedia , lookup

Islanding wikipedia , lookup

Power inverter wikipedia , lookup

History of electric power transmission wikipedia , lookup

Pulse-width modulation wikipedia , lookup

Electrical substation wikipedia , lookup

Ground loop (electricity) wikipedia , lookup

Resistive opto-isolator wikipedia , lookup

Ground (electricity) wikipedia , lookup

Voltage optimisation wikipedia , lookup

Stray voltage wikipedia , lookup

Current source wikipedia , lookup

Surge protector wikipedia , lookup

Rectifier wikipedia , lookup

Single-wire earth return wikipedia , lookup

Variable-frequency drive wikipedia , lookup

Earthing system wikipedia , lookup

Integrating ADC wikipedia , lookup

Overhead power line wikipedia , lookup

Voltage regulator wikipedia , lookup

Schmitt trigger wikipedia , lookup

Power electronics wikipedia , lookup

Three-phase electric power wikipedia , lookup

Mains electricity wikipedia , lookup

Distribution management system wikipedia , lookup

Alternating current wikipedia , lookup

Switched-mode power supply wikipedia , lookup

Buck converter wikipedia , lookup

Electrical wiring in the United Kingdom wikipedia , lookup

Uninterruptible power supply wikipedia , lookup

Electrical wiring wikipedia , lookup

Opto-isolator wikipedia , lookup

National Electrical Code wikipedia , lookup

Transcript
Facility Planning Data Sheet
2033D Series 30 - 80 kVA UPS (480in/480out, 480in/208out)
Power
Rating
kVA
kW
30
30
50
50
80
80
24
24
40
40
64
64
Voltage
Vac/ Freq.
480 / 60Hz
480 / 60Hz
480 / 60Hz
480 / 60Hz
480 / 60Hz
480 / 60Hz
kVA
UPS AC Input
Current
Nom. Max. Nom. Max.
26.7
26.7
44.1
44.1
70.7
70.7
Notes:
30.0
30.0
50.0
50.0
80.0
80.0
Minimum
Input
AWG
External
Overcurrent
Protection
Nominal
Voltage
VDC
32.8
32.8
54.1
54.1
86.8
86.8
36.1
36.1
60.1
60.1
96.2
96.2
8 AWG or larger
8 AWG or larger
4 AWG or larger
4 AWG or larger
1 AWG or larger
1 AWG or larger
45A
45A
80A
80A
125A
125A
480
480
480
480
480
480
1
2
3,4,10,13,A,B,C
4,7,9
5
Battery System
Full Load Maximum Voltage
Discharge
kW
A
Vac
Notes:
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
26.3
26.3
43.8
43.8
69.9
69.9
65.5
65.5
109.2
109.2
174.5
174.5
AC Output
Current
External
Nominal Overcurrent
Protection
A
480
208
480
208
480
208
6,10
36.1
83.3
60.1
138.9
90.2
208.2
45A
110A
80A
175A
125A
300A
1
4,7,8,11
Dimensions
WxDxH
Inch
34x31.5x70.9
34x31.5x70.9
34x31.5x70.9
34x31.5x70.9
34x31.5x70.9
34x31.5x70.9
11,12
Mechanical Information
Floor
Heat
Weight Loading
Rejection
Lbs
Lbs/ Ft2
kBTU/ Hr
2060
2060
1580
1580
1990
1990
278
278
213
213
269
269
9.3
9.3
13.8
13.8
22.9
22.9
Cooling
Air
CFM
990
990
1470
1470
2430
2430
Additional Notes:
Nominal (Nom.) current based on rated load.
Maximum (Max.) current based on converter overload rating.
Input and output cables typically run in separate conduits.
If initial load is less than UPS’ rated output, it is recommended that AC input, battery, and AC
output wiring and overcurrent protection be sized to UPS’ full load rating to accommodate
possible future expansion.
Nominal battery voltage assumed to be 2.0 volts/cell (lead technology).
DC cables should be sized for not more than a 2.0% line drop at maximum discharge current.
Suggested AC output overcurrent protection based on continuous full load current per NEC
210-20. 80% rated breakers assumed.
Grounding conductors to be sized per NEC Article 250-122 and NEC Table 250-122. Neutral
conductors to be sized per NEC Article 310-15.
 AC Input:
3 , 3 wire, ground.
For single input feed, jumper bypass and converter phase conductors.
 Bypass Input: 3 , 3 wire + ground.
 AC Output: 3 , 4 wire + ground.
 DC Input:
2 wire (Positive and Negative) + ground.
Input neutral conductor not required.
All wiring to be in accordance with all applicable national and/or local electrical codes.
Minimum access clearance per UPS drawings or Owner’s Manual.
Cable entry from top or bottom. Punch plates accordingly. (Side access possible. Consult
MEPPI for specifics.)
Control wiring and power wiring to be run in separate conduits.
i.
ii.
iii.
A.
B.
C.
D.
For site configurations including emergency generators, engine generator to be sized and equipped
for UPS applications. Generator equipped with governor for frequency regulation and regulator for
voltage stability reconmmended. Note: UPS’ reflected current distortion is 4% max at full load
and 7% max at 50% load.
For site configurations equipped with an external Maintenance Bypass Switch circuit, UPS must
be on internal Static Bypass before transferring to external Maintenance Bypass. Consult Factory
for further information.
For site configurations including automatic transfer switches, transfer switch to be equipped with
“neutral delay position” option to minimize phase shift during operation. Transfer switch
equipped with auxiliary contact for control of UPS input current when on generator recommended.
Consult transfer switch manufacturer for required transfer switch options and sizing.
Not more than 3 conductors in raceway sssumed; ambient temperature of 30 C (86 F) assumed.
Temperature rating of conductors: 75 C (167 F). Reference Table 310-16 of NEC, 75 C column,
using copper conductors. 75 C (167 F) cable terminal connectors assumed.
Reference: NEC handbook 2005. Consult local codes for possible variations.
RATINGS OF CABLES AND OVERCURRENT DEVICES SUPPLIED FOR
INFORMATION ONLY. USER TO CONSULT WITH ITS ENGINEERING
SERVICES BEFORE ADOPTING.
Mitsubishi Electric Power Products, Inc.
UPS Division
Phone: (724) 772-2555 Fax: (724) 778-3146
Rev. 4.0 (12/08)
U-ENS00044 2033D_fpds480-480or208_rev40