Download Utilization of power factor correction capacitors in circuits

Survey
yes no Was this document useful for you?
   Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Document related concepts

Fault tolerance wikipedia , lookup

Decibel wikipedia , lookup

Standby power wikipedia , lookup

Power inverter wikipedia , lookup

Coilgun wikipedia , lookup

Islanding wikipedia , lookup

Three-phase electric power wikipedia , lookup

Stepper motor wikipedia , lookup

Brushless DC electric motor wikipedia , lookup

Power over Ethernet wikipedia , lookup

Voltage optimisation wikipedia , lookup

Audio power wikipedia , lookup

Brushed DC electric motor wikipedia , lookup

Wireless power transfer wikipedia , lookup

Mains electricity wikipedia , lookup

Surface-mount technology wikipedia , lookup

Electrical substation wikipedia , lookup

Amtrak's 25 Hz traction power system wikipedia , lookup

Switched-mode power supply wikipedia , lookup

Metadyne wikipedia , lookup

Electric power system wikipedia , lookup

History of electric power transmission wikipedia , lookup

Capacitor wikipedia , lookup

Rectiverter wikipedia , lookup

Alternating current wikipedia , lookup

Variable-frequency drive wikipedia , lookup

AC adapter wikipedia , lookup

Induction motor wikipedia , lookup

Power factor wikipedia , lookup

Electrification wikipedia , lookup

Power engineering wikipedia , lookup

Transcript
Application Notes AP03902017E
Effective August 2012
Utilization of power factor correction
capacitors in circuits with soft starters
Control of power factor
correction capacitors in
circuits with soft starters
Application
In three-phase electric power distribution
systems, capacitors are often used for power
factor correction. The purpose of these capacitors
is to counteract inductive loading from devices
such as electric motors and transmission lines.
While individual motors may have capacitors
for power factor correction, larger electrical
distribution systems often have banks of
capacitors that can be switched in or out
of the circuit to apply the desired degree of
capacitance to achieve the required correction.
Power factor correction capacitors (PFCCs) are
used to increase the power factor to a higher
level. A circuit with a power factor of 1, for
example, is the most efficient, and all the power
in the circuit is real power consumed by the load
to do work. A circuit with a power factor of 0.85
is less efficient and takes more apparent power
to do the same amount of work as a circuit with
a higher power factor. As such, a circuit with a
low power factor is more expensive due to higher
energy consumption.
Power factor correction may be applied to one or
more motors in a circuit.
Considerations
On circuits with Eaton reduced voltage soft
starters, power factor correction capacitors
should be installed in accordance with the
following considerations:
•
Installation to be only on the line side of the
soft starter
•
A minimum cable distance of 10 feet of cable
between the capacitor(s) and the soft starter
•
The power factor correction capacitors
may be switched with a separate contactor.
NEMAT ICS2-1988 Part 2-210.81.01 provides
recommendations for when a separate
contactor should be used to switch the power
factor correction capacitor, including high inertia
loads, reversing motors, frequently jogged
motors, and multi-speed motors
•
In cases of multiple motors on a single branch,
it is recommended that the power factor
correction capacitors for any other motors
that are running be switched out of the circuit
for the duration of the start. When the motor
being started is up to synchronous speed
and the internal bypass contactors close, the
capacitors may be switched back into the
circuit. Capacitors used for a single motor
are switched into the circuit after the internal
bypass contactors close.
NNote: In case of multiple motors on a single branch or
a single motor alone, it is recommended that the power
factor correction capacitors be switched out of the circuit
during the ramp-up phase of any motor. When the motor
being started is up to synchronous speed and the internal
bypass contactors close, the capacitors may be switched
back into circuit. Capacitors may affect the proper
operation of the SCRs.
Application Notes AP03902017E
Utilization of power factor correction
capacitors in circuits with soft starters

Effective August 2012
It is not recommended that the power factor correction capacitors
be used on the load side of the soft starter. If used on the load side,
power factor correction capacitors may contribute to soft starter
operating difficulties for the following reasons:
•
Overload protection will not function correctly due to the
combination of capacitor and motor current, resulting in improper
or inadequate overload protection. This condition will exist both
during the start period and when in bypass
•
SCR failure may occur due to excessive current flow that exceeds
the rating of the SCR. If the power factor correction capacitor
is in the load circuit when the soft starter begins the start ramp,
the initial current surge as the capacitor is initially charging may
far exceed the current transmission capacity of the SCR
•
During operation of the soft starter in bypass, failure of the
internal bypass contactors may occur due to the apparent power
exceeding the rating of the internal bypass contactor
•
During the start ramp, the soft starter is monitoring counter
emf from the motor. The phase shift caused by the power factor
correction capacitor may interfere with the ability of the soft
starter to detect the zero cross point, resulting in SCR misfiring
of the unit
•
PFCC contactor control may be accomplished by utilizing the
auxiliary contacts of the soft starter. By factory default, contacts
13/14 close when the motor is at synchronous speed. These
contacts may be used to control the contactor
Supporting documentation
Manuals
Reference Number
S811+ User Manual
S801+ User Manual
MN03900001E
MN03900002E
Additional help
In the event that additional help is needed, please contact
the Technical Resource Center at 1-877-ETN-CARE, Option 2,
Sub Option 2.
Mains
S811+/S801+
RVSS
PFCC
Isolation
Contactor
Motor
PFCC
Bank
Figure 1. PFCC Orientation with RVSS Control
Eaton Corporation
Electrical Sector
1111 Superior Avenue
Cleveland, OH 44114 USA
Eaton.com
© 2012 Eaton Corporation
All Rights Reserved
Printed in USA
Publication No. AP03902017E / Z12599
August 2012
Eaton is a registered trademark
of Eaton Corporation.
All other trademarks are property
of their respective owners.