Current transducers HOP 200 to 600-SB
IPN = 200 .. 600 A
For the electronic measurement of currents : DC, AC pulsed, mixed,
with a galvanic isolation between the primary circuit (high power) and
the secondary circuit (electronic circuit).
Electrical Data
Primary nominal
Primary current
R.m.s or DC current
measuring range
Type
Features
IPN ( A )
200
IP ( A )
± 300
HOP 200-SB
300
± 450
HOP 300-SB
400
± 600
HOP 400-SB
500
± 750
HOP 500-SB
600
± 900
HOP 600-SB
• Open loop Hall effect transducer
• Busbar mounting and panel
mounting
• Insulated plastic case recognized
according to UL 94-V0.
IOC
V OUT
Overload capacity
Analog output voltage @ ± IPN
30000
± 4
A.t
V
RL
Load resistance
> 10
Vc
Supply voltage (± 5 %)
± 12 ..15
Ic
Current consumption (max)
20
mA
Vd
R.m.s. voltage for AC isolation test 50 Hz / 1 mn
3
KV
KΩ
• Through-hole, no insertion losses.
X
Accuracy 1) @ IPN, @ ± 12 ..15 V(± 5 %), T = 25°C
≤±2
V OE
Linearity error 1)
Electrical offset voltage @ IP = 0, TA = 25°C
≤±1
%
Typ : ± 50 mV
V OM
Max : ± 140 mV
Residual offset voltage @ IP = 0 after an overload of 3 x IPN Typ : ± 20 mV
A
L
V OT
ε
TC
G
• Low power consumption
• Split core easy for mounting
• High isolation between the primary
and the secondary circuits
Accuracy- Dynamic Performance Data
ε
Advantages
V
%
Thermal drift of electrical offset voltage, TA = - 10 .. + 70°C
Max : ± 30 mV
Typ : ± 140 mV
Max : ± 550 mV
Thermal drift of the gain, TA = - 10 .. + 70°C
Typ : ± 160 mV
Max : ± 600 mV
tr
Response time @ 90% of IPN
< 10
di/dt
f
di/dt accurately followed
Frequency bandwidth (- 1 dB)
50
DC .. 8
µs
A/µs
KHz
Application
• Power supply for TELECOM
•
•
•
•
•
(monitoring & measuring )
Uninterruptible power supply (UPS)
Chopper
Electrical chemistry
Battery supplied applications
Switched Mode Power Supplies
(SMPS).
General Data
TA
TS
Ambient operating temperature
Ambient storage temperature
- 10 .. + 70
- 25 .. + 85
m
Mass
110
Standard
EN 50178
Note :
1)
°C
°C
g
Excludes the electrical offset.
BJ-LEM
Beijing LEM Electronics Co., Ltd.
E-mail: [email protected]
Home page: www.lem.com.cn
040122/6
No. 1 Standarded Factory Building
Section B, Airport Industry Area
Beijing 101300, China
TEL: +86 (10) 80490470
FAX: +86 (10) 80490473
Hot Line(24 hrs):+86(10)80490469
Dimensions HOP 200 to 600-SB
( in mm, 1 mm = 0.0394 inch )
Left view
Front view
Secondary connections
Terminal
Terminal
Terminal
Terminal
0M-+
GIN OFS
1 : Supply voltage + 12 .. 15 V
2 : Supply voltage - 12 .. 15 V
3 : Output
4: 0 V
Adjustment :
GIN : Gain
OFS : Offset
Top view
Mechanical characteristics
Remarks
•
•
•
•
• V OUT is positive when IP flows in the direction of the arrow.
• The return busbar and primary conductor elbow must be
General tolerance
± 1 mm
Primary aperture
41 x 12.5 mm
Busbar fastening or panel mounting 2 holes : ∅ 4 mm
Secondary connection
MOLEX 5045-04/AG
"Mating connector provided with the transducer"
located at least at 2.5 x window length more far away from the
transducer case.
• Temperature of the primary busbar can not exceed 90° C.
• Dynamic performance are the best with a primary busbar
completely filling the primary aperture.
• This is a standard model. For different versions (supply
voltages, different outputs, unidirectional measurements...),
please contact us.
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without previous notice.