Download CIM800 Contact Input Module Datasheet

Survey
yes no Was this document useful for you?
   Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Document related concepts

Power MOSFET wikipedia , lookup

Oscilloscope history wikipedia , lookup

Phase-locked loop wikipedia , lookup

Wien bridge oscillator wikipedia , lookup

Test probe wikipedia , lookup

Immunity-aware programming wikipedia , lookup

Index of electronics articles wikipedia , lookup

CMOS wikipedia , lookup

Printed circuit board wikipedia , lookup

Resistive opto-isolator wikipedia , lookup

Schmitt trigger wikipedia , lookup

Transistor–transistor logic wikipedia , lookup

Valve RF amplifier wikipedia , lookup

Regenerative circuit wikipedia , lookup

Operational amplifier wikipedia , lookup

Rectiverter wikipedia , lookup

Opto-isolator wikipedia , lookup

Surge protector wikipedia , lookup

Multimeter wikipedia , lookup

RLC circuit wikipedia , lookup

Integrated circuit wikipedia , lookup

Flexible electronics wikipedia , lookup

Network analysis (electrical circuits) wikipedia , lookup

Ohm's law wikipedia , lookup

Transcript
CIM800
Generation 6 MX Detection Range - Contact Input Module
Features
// MX Addressable Module
// Supervise Two Circuits
// Supervise Multiple Contacts per Circut
// Up to 250 Devices per Loop2
Description
The CIM800 Addressable Contact Input Module supervises two
circuits of voltage-free contacts such as outputs from extinguishing
systems, ventilation controls, fire door controls, sprinkler flow
switches, non indicating detectors, etc. The LED illuminates when
any input goes into alarm, and can also be programmed to blink
when polled by the Tyco MX Control and Indicating Equipment
(CIE.). The CIM800 can be configured to supervise:
· Two circuits of multiple normally-open contacts; with short
circuit alarm.
· Two circuits of multiple normally-closed contacts; open circuit
alarm.
· Two circuits with a single normally-open contact closing
for alarm; with short circuit fault. This requires a resistor in
series with the alarm contact and special programming at the
MX4428 CIE.
On the MX4428, the two circuits are presented as a single
addressable point; either circuit in alarm puts the point into alarm,
any circuit in fault puts the point into fault.
Mounting
The CIM800 is supplied as an open circuit board (PCB) with
mounting hardware and End of Line (EOL) resistors. It must be
fitted in a suitable enclosure. It may be mounted on a gear plate
using plastic standoffs, to an M520 Ancillary Cover and K2142
back box, or into the D800 Ancillary Housing. The K2142
mounting box provides a convenient surface mounting enclosure
and the M520 Cover is designed to accommodate the CIM800.
The contacts supervised must be voltage free. Do not connect the
two circuits of a CIM800 together or join with other MX module
inputs. Unused inputs must be terminated with an EOL resistor.
Specifications
Loop Voltage1
20V to 40Vdc
Quiescent Current
275µA
Alarm State Current
2.8mA
Circuit Resistance
10 Ohm
EOL Resistor
200 Ohm
Alarm Resistance (s/c fault)
100 Ohm
Max. CIM800 per Loop2200/250
Ambient Temperature
–25°C to +70°C
Storage Temperature
–40°C to +80°C
Relative Humidity
10% to 95% (non cond.)
Indoor Applications Only
Dimensions (HWD)
61 x 84 x 25 mm
Wire Size (maximum)
2.5sq. mm
ActivFire Listing
afp-1446
FPANZ Listing
VF/640
Part Numbers
CIM800
CIM800 PCB 3
M520
Ancillary Cover
517.035.010
K2142 Back Box
557.201.401
D800 Ancillary
Housing
1. Addressable loop voltage provided by MX CIE.
2. MX4428/MX1, 4100MXP. Refer to appropriate manual: LT0273 (MXP),
LT0313 (4100MXP), LT0360 (MX1-NZ), LT0441 (MX1-Au) for design
specifications.
3. PCB c/w EOL resistor, mounting screws, cover labels.
Address Setting
The CIM-800 is supplied with a default (invalid) address of 255
and must be set to the correct loop address using the 850EMT or
801AP MX Service Tool and programming lead.
Wiring
CIM800 Wiring Options.
MX4428 Requires Param_2 = 176
ANALOG LOOP
PREVIOUS
DEVICE
L+ L- L+ L-
ANALOG LOOP
NEXT
DEVICE
TB1 TB2
PREVIOUS
DEVICE
A+ A- B+ B-
L+ L- L+ L-
CIM800 CONTACT MODULE
200
ohm
EOL
PREVIOUS
DEVICE
L+ L- L+ L-
TB1 TB2
100
ohm
200
ohm
EOL
NEXT
DEVICE
TB1 TB2
A+ A- B+ B-
Normally Open, S/C = Fault
200
ohm
EOL
NEXT
DEVICE
100
ohm
CIM800 CONTACT MODULE
Normally Open
ANALOG LOOP
200
ohm
EOL
200
ohm
EOL
200
ohm
EOL
Unused inputs (A or B) must be terminated with
a 200 ohm EOL resistor.
A and B inputs must be voltage free.
A+ A- B+ B-
CIM800 CONTACT MODULE
Normally Closed
Australia
Tyco Fire Protection Products
Level 3, 95 Coventry Street
Southbank VIC 3006
Tel
: 1300 725 688
Tel
: +61 3 9313 9700
Email
: [email protected]
New Zealand
Tyco Fire Protection Products
17 Mary Muller Drive
Hillsborough PO Box 19-545
Woolston Christchurch 8241
Tel
: +64 9 635 0760
Email
: [email protected]
Copyright © 2015 Tyco Australia Pty Limited. All rights reserved. Tyco reserves the right to make changes to any aspect of this publication at any time without notice. VIGILANT is a trademark of Tyco New Zealand Limited or its affiliates; MX
TECHNOLOGY is a trademark of Thorn Security Limited or its affiliates; VESDA is a trademark of Xtralis Technologies Ltd; TYCO is a trademark of Tyco International Services GmbH.