Programmable Temperature Converter Type ST
Technical Conditions, Installation, and Connection
These technical conditions are valid for the temperature converters type ST. They define
the technical data, method of installation, ordering and verification, and other basic information.
1. Terminology
1.1 Temperature Converter ST
Industrial programmable temperature converter type ST converts of output signal from
temperature sensor to unified or agreed output electrical signal. All types of resistance and voltage
sensors may be used as temperature sensor in this device, eventually, after agreement with the
producer, they may have a different output. It is possible to reprogram the gauging range either with
PC or with a communicating cable KX-1. It is also possible to change the type of used temperature
sensor.
2. Generally
2.1 Usage and Fabrication of the Temperature Converter ST
Temperature converters type ST are used for converting of output signal from temperature
sensor to unified or agreed output electrical signal. Thanks to its possibility of easy resetting or
inverting its gauging range, choosing of temperature sensor type either with PC or with a
communicating cable KX-1 the converter is widely used in automated systems. The converter type
ST is produced in a plastic box so that it could be assembled to a wall.
3. Technical Data ST
3.1 Type
ST
assembling to a wall
standard, different on request
3.2 Variant
in a whole range of used sensor
3.3 Range of Temperature Measurement
3.4 Temperature of Environment – Operational Temperature
Standard
Extended
0 to 60 °C
- 40°C to 60 °C
3.5 Accuracy of Temperature Measurement – Excluding Inaccuracy of sensor
Standard
Selection
Selection
0,5 % of range
0,25 % of range
0,1 % of range
3.6 Electrical Parameters
3.5.1 Plugging
Rated voltage
Range of plugging voltage
Two-conductor plugging of analogue output
Range of plugging voltage
Version: 1-00
24 V/DC
8 V to 36 V/DC
12 V to 36 V/DC
-2-
Three-conductor plugging of analogue output
Current consumption (of the device)
< 4 mA
< 10 mA
two-conductor variant
three-conductor variant
3.5.2 Output signal
Analogue output galvanically non-segregated
two-conductor plugging
three-conductor plugging
plugging voltage must be > than 12 V/DC
4 to 20 mA
0/4mA to 20 mA
0/1 to 5 V
0 to 10 V
while for output current is valid:
RZ = (Unap – 3V)/IOUT
where: RZ is load resistor in kΩ
Unap is plugging voltage in V
IOUT is output current in mA
3.5.3 Communication Line Galvanically Separated
3.7 Ingress Protection according to STN 33 0330
RS-485/9600 Bd
IP 65
pic. n. 1, 2 a 3
3.8 Basic Dimensions
ca. 0,2 kg
3.9 Weight
-3-
Version: 1-00
4. Marking
4.1 Data on the Type Plate
„
„
„
„
„
„
„
„
„
„
Identification mark and the origin of the product
Type designation
Gauging Range
Input temperature sensor
Accuracy
Nominal input voltage
Own consumption
Output signal
The production code number
Ingress protection
5. Ordering
5.1 The Order Should Include Information About
„
„
„
„
„
„
„
The number and the date of the order
Customer’s address (including EIN or TIN)
Particularities acc. to Table n. 1
Required delivery time
The number of goods
Bank account
Form of transportation
6. Installation, Transportation, Package
6.1 Converters type ST are according to ordered quantity placed in an appropriate box. Technical
conditions and a warranty certificate are a part of delivery.
Version: 1-00
-4-
Table n. 1
Specification of technical parameters and requirements
CODE
DESCRIPITON
ST
Temperature converter to be assembled to wall
01
0 °C to + 100 °C
preset by the producer
02
0 °C to + 200 °C
preset by the producer
03
0 °C to + 300 °C
preset by the producer
04
0 °C to + 400 °C
preset by the producer
55
- 50 °C to + 50 °C
preset by the producer
XX
Other range
GAUGING RANGE
VARIANT
S
X
Standard variant
Other
OUTPUT SIGNAL
40
00 43
4 to 20 mA
two-conductor plugging
4 to 20 mA, 0 to 20 mA
10
0 to 10 V
80
RS-485
XX
Other
three- and four-conductor plugging
three- and four-conductor plugging
galvanically separated
transfer rate 300 to 9600 Bd
ACCURACY
W
Selection 0,1 % of range
V
Selection 0,25 % of range
S
Standard 0,5 % of range
OPERATING TEMPERATURE
0
Standard
1
Extended
INPUT SENSOR
P01
PT 100
P05
PT 500
P10
PT 1000
N10
Ni 1000
XXX
Other
RECOMMENDED ACCESSORIES
QQ
Without accessories
KK
Communicating cable
Table n. 1 continues on the next page
-5-
Version: 1-00
Table n. 1. (continuation)
KX
Communicator KX.1-1
PC
Service PC Software for setting convertors
SPECIAL REQUESTS
Q0
Without special requests
XX
Other
X to XXXX – to be specified in an order
Example: ST 55 S 40 W 0 N10 KK Q0
Temperature converter ST, gauging range - 50 °C to + 50 °C, standard variant, output signal 4 to 20 mA, twoconductor plugging, accuracy 0,5% of range, standard operating temperature, input sensor made of Ni 1000,
communication cable, without special requests.
7. Installation and Operation
The ST converter is to be screwed to an appropriate place on a wall. The sensor is to be
connected to the input clamp in the lower part of the terminal box. The output signal and transmitter
plugging are to be connected to the control system or to the visual display unit with the wires
according to the table n. 2.
Plugging of the temperature transmitter according to the table n. 2 must be done only by
a person authorized in terms of the regulation 718/2002 Z. z., while they must observe these
technical conditions and other relevant norms and instructions.
„
The connecting wires must be chosen according to the environment, possibility of
electromagnetic interference, and technical conditions of the temperature transmitter.
In case of using the manometers in conditions, when voltage surges may appear, the
producer recommends to protect the manometers with surge barriers, for example
PBM – MERET.
„
Table n. 2
Plugging of the ST converter
Analogue output
n. of cl.
Serial line
Two-conductor
Three-conductor
RS-485
1
+U
+U
+U
2
Output signal
0V
0V
3
NC
Output signal
A
4
NC
NC
B
Input temperature sensor
Two-conductor plugging
Version: 1-00
Three-conductor plugging
-6-
Pic. n. 1
Input
two-conductor plugging
(temperature sensor)
Inevitable to connect
clamps 5 and 6
Output
two-conductor plugging
4 to 20mA
Pic. n. 2
Input
three-conductor plugging
(temperature sensor Pt, Ni
etc)
Pic. n. 3
Input
three-conductor plugging
(temperature sensor Pt, Ni
etc)
Output
three-conductor plugging
Output
four-conductor plugging
RS-485
-7-
Version: 1-00
Pic. n 4 Basic dimensions of the device
Version: 1-00
-8-