* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project
Download Document
Control system wikipedia , lookup
Power factor wikipedia , lookup
Electrification wikipedia , lookup
Mercury-arc valve wikipedia , lookup
Audio power wikipedia , lookup
Electric power system wikipedia , lookup
Electrical ballast wikipedia , lookup
Current source wikipedia , lookup
Pulse-width modulation wikipedia , lookup
Three-phase electric power wikipedia , lookup
Resistive opto-isolator wikipedia , lookup
Schmitt trigger wikipedia , lookup
Amtrak's 25 Hz traction power system wikipedia , lookup
Power engineering wikipedia , lookup
History of electric power transmission wikipedia , lookup
Distributed generation wikipedia , lookup
Electrical substation wikipedia , lookup
Power MOSFET wikipedia , lookup
Variable-frequency drive wikipedia , lookup
Opto-isolator wikipedia , lookup
Surge protector wikipedia , lookup
Solar micro-inverter wikipedia , lookup
Voltage regulator wikipedia , lookup
Stray voltage wikipedia , lookup
Buck converter wikipedia , lookup
Distribution management system wikipedia , lookup
Electrical grid wikipedia , lookup
Power inverter wikipedia , lookup
Switched-mode power supply wikipedia , lookup
Alternating current wikipedia , lookup
Voltage optimisation wikipedia , lookup
Research on Non-Directional Voltage Ride-through Control Technology of Household PV Grid-Connected Inverter CHEN Kun, ZHOU You-bin, XU Hua-an, DU Zhen-an, WANG Xiao-kai State Grid Hubei Electric Power Research Institute, Wuhan 430077, China I. INTRODUCTION With recent rapid development and wide application of photovoltaic power generation, its status improves greatly. When the grid fails, the routine off-grid operations on large-scale PV power supply cannot meet the requirements of normal operation of power system. The State Grid Corporation of China has made explicit requirements for this problem in 2011[1]. Therefore, it is vitally important to improve the ride-through capability of PV grid-connected power. The current research on grid-connected inverter ride-through technology mainly focuses on wind power low voltage ride-through (LVRT)[2], and the research on PV grid-connected power ride-through technology also focuses on LVRT in large-scale PV power plants[3], but the corresponding high voltage ride-through (HVRT) technology has not received enough attention. At present, off-grid operation is applied according to relevant regulations in China. Unlike wind power, PV grid-connected power generation application is not affected by geographical restrictions, and it is mostly in urban distribution side, so it is often faced with non-directional voltage fluctuations. As household PV grid-connected power generation is widely used, once the power grid suffers failure of sudden voltage rise, the routine off-grid operation will do harm to the safe and stable operation of the grid. Therefore, research on PV grid-connected power HVRT also has great practical significance. This paper firstly analyses the current household PV grid-connected power ride-through requirements in China and proposes a non-directional ride-through control strategy of household PV grid-connected inverter based on voltage feed-forward control. Then, based on analysis of grid-connected inverter output power control, this paper has achieved dynamic adjustment of active power output and reactive power compensation according to needs, and the role and control principles of Crowbar circuit in this strategy are described. Finally, the feasibility and effectiveness of this strategy is verified by the experiment in which sudden and non-directional change of grid voltage is simulated. II. ANALYSIS OF RIDE-THROUGH REQUIREMENT At present, the State Grid clearly states, PV grid-connected power should have certain capacity to withstand voltage anomalies to avoid separation from the grid, causing grid power loss, as shown in Fig. 1. 电网故障引起电压跌落 1.1 1.0 0.9 光伏电站必须 保持并网运行 U / (p.u.) Abstract—On account of present situations in which the government greatly promote household PV grid-connected application and the increasing demands for the control technology of grid-connected inverters, this paper proposes a non-directional ride-through control strategy of household PV grid-connected inverter based on voltage feed-forward control and carries out research on the active power output and reactive power compensation. Based on voltage feed-forward control, this strategy enables instantaneous tracking of grid voltage to be achieved and suppresses sudden grid current change caused by PI close-loop control delay and power balance principle when sudden and non-directional change of grid voltage occurs. Combing research on the active power output and reactive power compensation, this strategy is able to achieve dynamic adjustment of active power output and reactive power compensation according to needs. The feasibility and effectiveness of this strategy is verified by the experiment in which sudden and non-directional change of grid voltage is simulated. Index Terms—PV; grid-connected inverter; ride-through; voltage feed-forward. 光伏电站可以从 电网切出 0.2 0 0 1 2 t/s 3 4 Fig. 1 The requirement for low voltage tolerant capacity of PV power plant As shown in Fig. 1, during the period when the grid voltage drops to 20% of rated voltage and recovers within 3s to 90% of rated voltage, PV power shall continue to run, so the capacity of PV grid-connected inverter LVRT directly determines the operating state of PV grid-connected power and is also related to the security and stability of the system. Although China has not yet specific requirements for PV grid-connected power HVRT, relevant regulations issued by State Grid [4] can be used for reference, as shown in Tab. 1. for actual operation of the PV grid-connected power. III. THE NON-DIRECTIONAL RIDE-THROUGH Tab.1 The requirement for response time of distributed power voltage Voltage at PCC CONTROL STRATEGY Requirements According to the PV characteristics of PV cells, the DC bus voltage rise of PV grid-connected system will be accompanied by reduced power output of PV cells, and PV cell output power of the open circuit voltage will drop to zero. Therefore, the restriction on grid-connected current is generally considered as the key to ride-through control research, as shown in Fig. 2. Maximum breaker-separating time U < 50%UN ≤ 0.2s Maximum breaker-separating time 50%UN ≤ U < 85%UN ≤ 2.0s 85%UN ≤ U < 110%UN Continuous operation (1)UN is the Pmax ≤ 2.0s Maximum breaker-separating time 135%UN ≤ U Note: P/kW Maximum breaker-separating time 110%UN ≤ U < 135%UN ≤ 0.2s rated voltage at PCC; (2)The maximum 0 breaker-separating time refers to the time length from when abnormal Udc/V Fig.2 PV curve of Photovoltaic cell conditions occur to when power supply to the grid stops. Similar to LVRT, at the moment of sudden grid voltage rise, the output voltage must be enabled to track the grid voltage, and the grid-connected current must be restricted in order to achieve PV grid inverter HVRT. Therefore, this paper applies double PI close-loop control of output voltage and grid-connected current as the basic strategy for the non-directional ride-through of household PV grid-connected inverter. Take the single-phase bridge voltage source inverter as an example. The block diagram of basic control principle is shown in Fig. 3 where uo, io, ug are PV grid-connected inverter output voltage, grid-connected current, grid voltage respectively, Kvp, Kvi are PI control parameters, Ks is the inverter gain, and Kg is the grid voltage tracking compensation factor. The following conclusions can be drawn from Tab. 1: When the voltage of Point of Common Connection (PCC) to PV power is within 100% ~ 110%UN, the grid requires it to run continuously while staying connected to the grid. If the PV grid-connected inverter does not have HVRT capacity, the inverter itself will be seriously damaged; When the voltage at PCC to PV power reaches 110%UN and above, the grid allows off-grid operation. If in this case the PV power can continue to run uninterruptedly while staying connected to the grid, it can significantly reduce the number of PV power getting off-grid and improve the stability of power grid operation. Thus, the non-directional ride-through capability of PV grid-connected inverter has great practical significance Kvp+Kvi/s 1/L1s Ks + + - uo + 1/Cs 1/L2s + - ug io Kg Fig. 3 The basic principle diagram of non-directional voltage ride-through control A. Instantaneous prediction algorithm In order to achieve instantaneous tracking of the grid voltage by the grid-connected inverter, this strategy controls grid voltage amplitude and phase separately. For tracking grid voltage amplitude, taking into account that the PI closed loop is not non-static error tracking, this strategy adopts instantaneous prediction algorithm [5] in order to improve the instantaneity in tracking grid voltage amplitude. Assume that the sample values for sampling time t1, t2, t3 are n1, n2, n3, wherein t3-t2=t2-t1=Tc,and Tc is carrier period. According to Taylor series, the following formula can be obtained: f ( x3 t ) f ( x3 ) f ' ( x3 )t 1 '' f ( x3 )t 2 (t 3 ) 2 (1) As Tc is small enough in actual control, the derivative in Formula (1) be linearized as: f ' x3 t n3 n2 (2) f ( x3 )t (n3 n2 ) (n2 n1 ) n3 2n2 n1 (3) '' 2 Formula (2) and Formula (3) are placed into Formula (1), and if ∆t=Tc, then there will be: operating normally, namely: f ( x3 Tc ) 1 n3 (n3 n2 ) (n3 2n2 n1 ) 2 1 2(n3 n2 ) (n3 n1 ) 2 (4) As shown in Formula (4), if the grid voltage is sampled with Tc as the unit and taking ∆t=Tc, in there three consecutive sampling values can be used to predict the subsequent sampling value Tc of grid voltage, which will compensate a Tc for PI closed-loop control delay. It thus can be seen the compensation time length for PI closed-loop control delay is determined by ∆t. By setting ∆t according to needs, the instantaneous value of future grid voltage at ∆t moment can be predicted. However, as this algorithm is based on linearization of the existing sample values, the bigger Δt is, the greater the deviation of the predicted result will be, which is not conducive to accurate tracking of grid voltage amplitude. Meanwhile, in order to increase the accuracy of this prediction algorithm, the number of sampling values and expanded terms in Taylor series can be increased. As the grid voltage amplitude and the PV grid-connected inverter output voltage amplitude have the same sampling delay, the results of for comparison of both will not be affected, but the grid voltage sampling delay will cause judgment error of grid working state by this algorithm. Therefore, the difference value between the prediction value of grid voltage amplitude and its rated value can serve as the criteria for whether the grid is E (t ) U g (t ) u g (t ) (5) wherein ug(t) is the instantaneous value of grid voltage at t moment obtained by the prediction algorithm, and Ug(t) is the rated instantaneous value of the grid voltage at t moment obtained by looking up the table. B. Voltage feed-forward control Also, as the closed-loop control delay is affected by its proportional factor and integral factor, it is not enough to rely solely on the instantaneous prediction algorithm to compensate. Therefore, sudden change of grid-connected current caused by PI closed-loop control delay and the power balance principle at the moment of sudden change of grid voltage still needs to be taken into account. This strategy applies feed-forward control [6] at the same time to suppress sudden change of grid-connected current at the above-mentioned moment. As shown in Fig. 3, the transfer function of grid voltage and grid-connected current is: I o ( s) ( K g 1) K v K s L1sCs 1 U g ( s) L2 s(1 K v K s ) L1sL2 sCs (6) wherein Kv=Kvp+Kvi/s. According to the design principles of feed-forward control, the block diagram after adding the feed-forward control is shown in Fig. 4, in which G1(s)=(Kg-1)KvKs-L1sCs-1, G2(s)=1/(L2s(1+KvKs)+L1sL2sCs)。 Kg G1(s) G3(s) + - + Kvp + Kvi /s Iref1 Kip + + Ks 1/L1s 1/Cs uo + G2(s) io Grid + - - + + ug - Fig. 4 The block diagram based on voltage feed-forward control To simplify deduction, when Kg=1, the following can be obtained from Fig. 4: I o ( s) G1 ( s)G2 ( s)(1 L1sCs G3 ( s) K s ) U g ( s) L1s 1 G2 ( s) K v K s L1sG2 ( s) 218V with a drop rate of about 30%, and the simulation results are shown in Fig. 5. (7) As shown in Formula (7), to completely eliminate disturbances of grid voltage to grid-connected current, there is: G3 ( s ) 1 L1sCs Ks (8) Formula (8) is the transfer function of feed-forward control of grid-connected current. In order to verify the effectiveness of the feed-forward control, LVRT is taken as example in simulation. Grid voltage drop is simulated at 0.3s, the PV grid-connected inverter LVRT, the peak voltage value falls from 311V to (a) (b) Fig. 5 Simulation results Fig. 5(a) shows that, before adopting the voltage feed-forward control, sudden current change occurs at the moment of sudden voltage change; Fig. 5(b) shows that, after adopting the feed-forward control, sudden current change is effectively suppressed at the moment of sudden voltage change. namely the amplitude difference. From Formula (9) and Formula (10), the following can be obtained: V. RESEARCH ON ACTIVE POWER OUTPUT AND REACTIVE POWER COMPENSATION CONTROL 2 A. Analysis of active power output and reactive power compensation control If PV grid-connected system is equivalent to a voltage source, there will be the equivalent circuit of PV grid-connected system as shown in Fig. 6, in which L is the joint inductance between PV grid-connected inverter and the grid, R is the equivalent internal resistance of PV grid-connected system, Uo∠ δ is the output voltage of PV grid-connected inverter, and Ug∠ 0° is the grid voltage. L U U gU o P 2 g Q X X 2 2 U U gU o P 2 g X X 2 (11) As shown in Formula (11), when P=0, the output or absorbed reactive power reaches maximum, and it is related to inverter output voltage, voltage at PCC, filter inductor and the active power output then. It is restricted by the rated capacity limits of PV grid-connected inverter. And the steady state vector correlation on the AC side of grid-connected inverter is shown in Fig. 7 Uo∠δ Ug∠0° uo uL io R Fig. 6 The equivalent circuit of PV grid-connected system Q U oU g X U oU g X uo uL ug (b) ug uo io ug s i n cos uL (a) The formula of output power from the PV grid-connected inverter to the grid can be obtained from Fig. 6 as follows: P ug io (9) U g2 io X uL (c) (d) Fig. 7 AC steady state vector of inverter (10) in there X=jωL (ignoring R). As shown in Formula (9) and Formula (10), the active power output can be controlled by adjusting the phase difference between the output voltage and the grid voltage, i.e. the power angle δ; once the power angle δ is determined, directional control of the reactive power output can be achieved by adjusting between Uo and Ug , uo As shown in Fig. 7, the ratio between the active and reactive power of the inverter output can be controlled by controlling the phase difference between the grid-connected current and grid voltage, i.e. the power factor angle θ. In summary, combining Fig. 4, there is the control block diagram of this strategy, as shown in Fig. 8. Kg G1(s) G3(s) + Kvp + Kvi /s - - + Iref1 Kip + + + + Ks 1/L1s 1/Cs uo + io G2(s) Grid + - ug - φ + - δg Fig. 8 The control block diagram of PV grid-connected inverter For detection of the grid voltage phase signal, this strategy applies hardware phase zero-crossing detection circuits. Because delays in the phase zero-crossing detection of grid-connected current and grid voltage both have the same length of time, the detection delay does not affect the detection accuracy of the power factor angle. B. Analysis of Crowbar circuit control As shown in Fig. 2, no matter how the voltage drops, the PV array output voltage cannot exceed the open circuit voltage, which means dominant advantages of protection. Based on this principle, Crowbar circuit is not generally adopted in the current design of PV grid-connected system. However, during the voltage drop, depth of drop may change. Once the depth changes from deep to shallow, the PV cells do not have the reverse features, i.e. the output voltage is automatically lowered to ensure that the output power increases, and therefore, in order to meet the requirements of State Grid, this paper chooses to keep the Crowbar circuit to guarantee the adjustment capacity of reactive power during grid voltage drop. By detecting the output DC voltage of the PV array, this strategy determines whether the DC voltage exceeds a preset maximum volume, issue a command about whether to start Crowbar circuit and get PWM output [7] by PI control. The control block diagram is shown in Fig. 9. Upv - Upv* 光伏阵列输出电压 波动判断 PI PWM Crowbar电路 Tab.2 Component parameters Three-phase voltage regulator Three-phase rectifier 75A/1600V IGBT 100A/1200V Filter capacitor 3300μF/450VDC In order to better verify the control effect of this strategy, this experiment has designed inverter load connection circuit as shown in Fig. 11, wherein L1 is filter inductor 10.7mH (measured), L2 is connection inductance 1.0mH (measured), C is the filter capacitor 2.2μF, R1 and R2 are the voltage dividing resistors, and K is the switch. Short-circuiting operation R1 is performed. Y Ug是否正常 L1 Fig. 9 Control block diagram of Crowbar In summary, Formula (5) is taken as operation criteria for the state of grid. Then, when the grid operates normally, the PV grid-connected inverter runs in inverter operation mode with unity power factor; when the grid encounters temporary fault, the PV grid-connected inverter controls the output power control according to needs in order to help restore the grid voltage; based on detection of the DC bus voltage, Crowbar circuit is controlled to ensure that the PV array works in the vicinity of the actual output power of the grid-connected inverter. The flow chart of control program is shown in Fig. 10. 380VAC/0~430VAC/4A/50Hz/3KVA uo L2 R1 io C R2 K GRID 本实验电网 电压采样点 Fig. 11 Load connection circuit In this experiment, the voltage loaded on R2 is used as the grid voltage sample values. Sudden change of grid voltage is simulated by switching K. Take basic control parameters as shown in Tab. 3. The experimental results are as follows: Tab.3 Control parameters 跟踪Ug,单位功率因数 逆变运行 carrier wave ratio N=256; carrier cycle Tc=78.125μs 返回 N PI Control parameters Kvp=10, Kvi=0.1(1/s, Kip=1 Y 低电压穿越? N Crowbar工作? N 按预设发出无功 返回 tracking control feedback factor Kg=1.02 Y PWM控制 uo ug Y 高电压穿越? 按预设吸收无功 返回 u(140V/格) N 过流保护 N 返回 t(10ms/格) (a) Fig. 10 Program flow chart ug uo ug u(140V/格) TMS320F28XXX is applied as the control core and single-phase bridge voltage source inverter is taken as example. The experiment is carried out by short-circuiting the resistive load to simulate the sudden and non-directional change of grid voltage. The main power electronic devices and their parameters chosen in the experiment are shown in Tab. 2. uo u(140V/格) V. EXPERIMENT t(25ms/格) (b) t(10ms/格) (c) uo ug u(140V/格) ug u(140V/格) uo t(25ms/格) (d) the premise of ensuring the active power output, reactive power is sending to the grid system or absorbed according to power system instructions for purpose of making full use of the inverter capacity. REFERENCES t(10ms/格) (e) Fig. 12 Experiment results As shown in Fig. 12(a), the simulation grid has normal power supply and runs in inverter operation mode which is close to unity power factor. As shown in Fig. 12(b) and (c), voltage of simulation grid drops, and PV grid-connected inverter is riding through with low voltage. Low-voltage ride-through of grid voltage amplitude is achieved within two frequency cycles. Switch from inverter operation mode with unity power factor to pure capacitance operation mode is achieved within four frequency cycles. As shown in Fig. 12(d) and (e), voltage of simulation grid rises, and PV grid-connected inverter is riding through with high voltage. High-voltage ride-through of grid voltage amplitude is achieved within two frequency cycles. Switch from inverter operation mode with unity power factor to pure capacitance operation mode is achieved within four frequency cycles. [1] State Grid. Q/GDW617 2011Technical Requirements for PV Power Plants Connection to the Grid[S]. Beijing: State Grid, 2011. [2] Jesus Lopez, Eugenio Gubia, Eneko Olea, Josu Ruiz, et al. Ride Through of Wind Turbines With Doubly Fed Induction Generator Under Symmetrical Voltage Dips[J]. IEEE transactions on industrial electronics, Vol. 56, No. 10, 2009. [3] Yin B, Oruganti R, Panda S K. An output-power-control strategy for a three-phase PWM rectifier under unbalanced supply conditions[J]. IEEE Transactions on Industrial Electronics, 2008, 55(5): 2140-2150. [4] State Grid. Q/GDW480 2010 Technical Regulations of Distributed Power Connection to the Grid[S]. Beijing: State Grid, 2010. [5] MA Zhao-biao, HUI Jing, PAN Jian. Study on Photovoltaic Grid-connected Inverter based on Repetitive-PI Control[J]. POWER ELECTRONICS, 2008, 43(3): 25-27. [6] ZHOU Bin. LVRT of Photovoltaic Inverter Based on Feedforward Control[J]. POWER ELECTRONICS, 2013, 47(8): 49-51. [7] AN Zhi-long. Research on Photovoltaic grid-connected control strategy and low voltage ride-through control[D]. NCEPU, master's thesis, 2012. VI. CONCLUSIONS Based on analyzing the necessity of research on high and low voltage ride-through technology, this paper proposes a non-directional ride-though control strategy of household PV grid-connected inverter based on voltage feed-forward control: (1) An instantaneous prediction algorithm is adopted for tracking the grid voltage amplitude signal, which, to some extent, compensates PI closed loop control delay; voltage feed-forward control is applied to effectively suppress sudden change of grid-connected current caused by sudden change of grid voltage. (2) The direction of reactive power is controlled by controlling the inverter output voltage amplitude. The ration between active and reactive output is controlled by controlling the phase difference between the grid-connected current and grid voltage, i.e. the power factor angle. (3) Necessity of Crowbar circuit application in this strategy is explained based on the PV curve of PV cells. The experiment is carried out by simulating the sudden and non-directional change of grid voltage. Experimental results have verified the feasibility and effectiveness of the strategy as a practical control method. In actual situations, the grid-connected inverter is generally not working in full capacity, so when the grid voltage is normal, this strategy can also be adopted. On CHEN Kun was born in the city of Wuhan, Hubei Province, China in 1986. He earned the Ph. D in Power Electronics in Wuhan University in 2014. His major field of study is inverter control, PV grid-connected control, DC transmission control and protection. E-mail:[email protected]