Download Datasheet - Pump Centre

Survey
yes no Was this document useful for you?
   Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Document related concepts

Ohm's law wikipedia , lookup

Electric power system wikipedia , lookup

Mercury-arc valve wikipedia , lookup

Current source wikipedia , lookup

Power inverter wikipedia , lookup

Electromagnetic compatibility wikipedia , lookup

Resistive opto-isolator wikipedia , lookup

Electrical ballast wikipedia , lookup

Power engineering wikipedia , lookup

Pulse-width modulation wikipedia , lookup

Rectifier wikipedia , lookup

Electrification wikipedia , lookup

Induction motor wikipedia , lookup

Amtrak's 25 Hz traction power system wikipedia , lookup

History of electric power transmission wikipedia , lookup

Islanding wikipedia , lookup

Buck converter wikipedia , lookup

Ground (electricity) wikipedia , lookup

Electrical substation wikipedia , lookup

Brushed DC electric motor wikipedia , lookup

Opto-isolator wikipedia , lookup

Distribution management system wikipedia , lookup

Power electronics wikipedia , lookup

Stray voltage wikipedia , lookup

Switched-mode power supply wikipedia , lookup

Stepper motor wikipedia , lookup

Surge protector wikipedia , lookup

Portable appliance testing wikipedia , lookup

Voltage optimisation wikipedia , lookup

Mains electricity wikipedia , lookup

Alternating current wikipedia , lookup

Variable-frequency drive wikipedia , lookup

Earthing system wikipedia , lookup

Three-phase electric power wikipedia , lookup

Electrical wiring in the United Kingdom wikipedia , lookup

Transcript
WIMES 3.04
Page 59
APPENDIX C1 - DATA SHEETS
PACKAGE PLANT (ELECTRICAL)
PROJECT TITLE (P)
PROJECT NUMBER (P)
PROJECT LOCATION (P)
PACKAGE
PLANT
SUPPLIER (P/S)
* - indicates Purchaser’s default requirement
3.0 OPERATING ENVIRONMENT AND SERVICE
CONDITIONS
1
3
Operating Environment (P)
Site Location ()
Inland
Coastal
Package Plant Location ()
Indoors
Outdoors
Other (specify)
Hazardous Area Classification ()
Non hazardous
Zone 1
Zone 2
EMC Environment ()
1st environment – C1
1st environment – C2
2nd environment – C3
Special Service Conditions (P)
DOCUMENT REFERENCE (P)
REVISION (P)
DATE (P)
REFERENCE
DRAWINGS
INCLUDED (Y/N) (P)
4.0 ELECTRICAL SYSTEM CHARACTERITICS
(CONTD.)
c
d
e
f
4.0 ELECTRICAL SYSTEM CHARACTERITICS
1
a
b
Electrical System Characteristics (P)
Supply Arrangement ()
Single source
Multiple source (specify
sources and operating
arrangement elsewhere)
Supply Voltage, Frequency and Number of
Phases ()
400 V, 3 phase, 50 Hz
3 wire
4 wire
Other (specify)
ISSUE 5
g
Prospective Fault Current (kA) (max)
Phase to phase
Phase to neutral
Phase to earth
Type of Earthing System ()
TN-S
TN-C-S (PME)
TT
Other (specify)
Earth Fault Loop Impedance (Ohms)
Ze
Type and Rating of the Upstream
Protective Device ()
None
Circuit breaker
Fuse
Number of poles
BS
Type
Overcurrent rating (A)
Earth fault rating (A)
Earth fault time delay
(secs)
Other
arrangement
(specify)
Supply Cable Characteristics
BS
Type
Copper conductors
Rating (A)
Phase CSA (mm2)
Neutral CSA (mm2)
Earth CSA (mm2)
MARCH 2014
WIMES 3.04
2
3
4
6
Page 60
6.2.4 Construction
Overvoltage
Category
(III*) (P)
Assumed Voltage Drop
for Package Plant (V) (P)
Supply Restrictions (P)
Lightning
and
Requirements (P)
6.2.4.1 General
Surge
Protection
5.0 PERFORMANCE SPECIFICATION
3
Minimum Design
(20 years*) (P)
3
Material(s) of Construction (Including
Details of Any Protective Coatings) (P/S)
4
a
b
6
Type of Assembly Construction () (P/S)
Cubicle/multi-cubicle
Box/multi-box
Degree
of
Ingress
Protection (IP Code) (P/S)
Size/Weight Restrictions (P)
7
Life
6.0 DESIGN SPECIFICATION
6.2.4.5 Mounting Arrangements
6.1 General
1
6.1.1 General and Safety Requirements
3
Method of Fault Protection
(ADS*) (P/S)
Mounting Arrangements () (P/S)
Skid/frame mounted
Wall mounted
Other (specify)
6.2.5 Earthing and Bonding
6.1.6 O & M Manuals
4
1
Reference for O & M Manual Specification
([P)
Separate Earth Bars/
Studs Required (Y/N) (P)
6.2.6 Cabling and Wiring
6.2.6.1 General
6.2 The Assembly
3
6.2.1 General
2
5
7
Form of Internal Separation (P/S)
Form 2 assemblies (2a or
2b)
Form 4 assemblies (4a or
4b)
Control Circuit Test Facilities () (S)
Internal push-button
Test position on switching
and isolation device
Diversity factor (S)
Ratio of CSAs of Neutral
and
Line
Conductors
(100 %*) (P)
6.2.2 Electrical Components
4
Component (P)
ISSUE 5
Details (S)
MARCH 2014
WIMES 3.04
Page 61
6.2.7 Requirements for Specific Components
6.2.8.2 Motor Starters
6.2.7.1 Indicating Lamps
Refer to APPENDIX C2
2
Lamp Colours/Meanings (P)
Available/auto-available
Supply on
Running
Stopped
Emergency stop
Dangerous condition
Normal condition
Alarm
Tripped/fault
6.2.8.3 Control Circuit Supplies
white
CCS Voltage (P/S)
6.2.8.4 ICA Equipment
General
red
yellow/
amber
yellow/
amber
On
Off
Process indicators
6.2.7.2 Push-Button and Control Switches
1
3
Push Button Switch Colours/Meanings (P)
Start
Stop
Reset
Emergency stop
red
Inch
Lamp test
Closed
Open
On
Off
10
Type of HMI Required/Provided (P/S)
11
Method of Connecting Package Plant to
Site Control System () (P)
Hardwired
Remote I/O unit
Fieldbus connection
Reference for Purchaser’s Particular
Specification
11
Low Voltage and Extra Low Voltage Systems
1
Type and Configuration of LV and ELV
Systems (P/S)
Lighting and Socket Outlets
1
Lighting
Facilities
Required (Y/N) (P)
PLC
1
PLC Provided (Y/N) (S)
6.2.8.5 Uninterruptible Power Supply (UPS)
6.2.8 Functional Units
1
1
Method of Functional Unit
Connection (P)
6.2.8.1 Incomer
1
Fuse Switch Rating & Configuration (S)
Rating (A)
3 pole
3 pole + bolted neutral link
4 pole
Short circuit capacity (kA)
ISSUE 5
3
4
UPS Requirements () (P)
None required
Provided within Assembly
Provided
within
a
separate assembly
Details of Loads to be Supported by the
UPS (P)
UPS Rating and Autonomy Time (110%
and 15 minutes (min)) (P)
MARCH 2014
WIMES 3.04
Page 62
6.2.8.6 Supervisory Control and Monitoring
2
7.2 Inspection and Testing of the Assembly
Local & Remote Supervisory Control
Signals Required/ Provided (P/S)
Signal Description
Signal Type1
7.2.1 General
1
a
b
Additional Tests Required () (P)
Witness FATs
Site commissioning tests
7.2.2 Factory Acceptance Tests (FATs)
1
3
a
1 – Volt-free (VF), Digital (D), Analogue (A)
3
Local & Remote Supervisory Monitoring
Signals Required/Provided (P/S)
Signal Description
Type1
I/C2
b
c
d
Samples of Supplier’s test
schedules to be submitted
before testing (Y/N) (P)
Additional FATs Required () (P)
Injection
testing
of
incomer protection circuits
Injection testing of motor
starter protection circuits
Response
testing
to
simulated voltage dips
Serial
communication
network testing
7.2.3 Witness
Required)
2
a
1 – Volt-free (VF), Communications link (CL),
Analogue (A)
2 – Individual (I), common (C)
6.2.10 Additional
Assemblies
Requirements
for
Form
b
2
6.2.10.1 Construction
3
a
i
General
ii
3
Distribution Board Location (P)
iii
7.0 INSPECTION AND TESTING
iv
7.1 General
v
4
4
Package Plant to Include
/be Included in a Fieldbus
Network (Y/N) (P)
Reference for Purchaser’s
Specification (P)
ISSUE 5
vi
Particular
vii
Factory
Acceptance
Tests
(If
Availability/Distribution of Supplier’s Test
Schedules (P)
Schedules to be made
available to the Purchaser
at witness FATs
Schedules to be sent to
the Purchaser before
witness FATs
Witness FATs to Include () (P)
Routine Tests to BS EN 61349
Constructional:
Degree of protection of
enclosures
Clearance and creepage
distances
Protection against electric
shock and integrity of
protective circuits
Incorporation of built in
components
Internal electric circuits
and connections
Terminals for external
conductors
Mechanical operation
MARCH 2014
WIMES 3.04
i
ii
3
i
ii
iii
iv
4
5
Page 63
Performance:
Dielectric properties
Wiring,
operational
performance and function
Additional Tests
Injection
testing
of
incomer protection circuits
Injection testing of motor
starter protection circuits
Response
testing
to
simulated voltage dips
Serial
communication
network testing
Details of Any Further Witness FATs
Required (P)
DOC (to BS EN 61439-2)
to be Available at Witness
FATs (Y/N) (P)
7.2.5 Site Commissioning Tests (If Required)
1
3
Tests to be Witnessed by
the Purchaser (Y/N) (P)
Details of Any Further Testing or
Commissioning Activities Required (P)
7.3 Inspection and Testing of the Installation
7.3.1 General
3
Additional Inspection &
Testing Reqd. (as Part of
Process Commissioning)
(Y/N) (P)
ISSUE 5
MARCH 2014
WIMES 3.04
Page 64
APPENDIX C2 - MOTOR STARTER DATA SHEET
PACKAGE PLANT (ELECTRICAL)
DRIVE DESIGNATION ____________________
1
Motor Starter Details (S)
Type
Direct-on-line
Star delta
Reversing
Two speed
Soft start/stop
Variable speed
Voltage
400 V 3 phase
230 V 1 phase
Other (specify)
Rating
Output (kW)
Full load current (A)
Starting current (xFLC)
Number of starts per hour
Power Factor
Uncorrected motor power factor
DRIVE DESIGNATION ____________________
1
Motor Starter Details (S)
Type
Direct-on-line
Star delta
Reversing
Two speed
Soft start/stop
Variable speed
Voltage
400 V 3 phase
230 V 1 phase
Other (specify)
Rating
Output (kW)
Full load current (A)
Starting current (xFLC)
Number of starts per hour
Power Factor
Uncorrected motor power factor
ISSUE 5
DRIVE DESIGNATION ____________________
1
Motor Starter Details (S)
Type
Direct-on-line
Star delta
Reversing
Two speed
Soft start/stop
Variable speed
Voltage
400 V 3 phase
230 V 1 phase
Other (specify)
Rating
Output (kW)
Full load current (A)
Starting current (xFLC)
Number of starts per hour
Power Factor
Uncorrected motor power factor
DRIVE DESIGNATION ____________________
1
Motor Starter Details (S)
Type
Direct-on-line
Star delta
Reversing
Two speed
Soft start/stop
Variable speed
Voltage
400 V 3 phase
230 V 1 phase
Other (specify)
Rating
Output (kW)
Full load current (A)
Starting current (xFLC)
Number of starts per hour
Power Factor
Uncorrected motor power factor
MARCH 2014
WIMES 3.04
Page 65
APPENDIX D – SUPPLIER’S SUPPLEMENTARY DATA SHEET INFORMATION
Clause
ISSUE 5
Supplementary Information
MARCH 2014