Compliance sheets for indoor LV switchgear cabinet and LV circuit breakers
No
UNDP required
specifications
Description
Original manufacturer
(Locally assembled not
acceptable)
1
Name of manufacturer:
2
Country of origin:
3
Reference standards
IEC 60439
4
Ambient temperature:
Maximum:55/C
Minimum: -10/C
5
Relative Humidity:
92% maximum
6
Altitude:
1000M above MSL
7
Rated voltage
416/240 Volts
8
Frequency
50 Hz
9
Switchgear type:
Indoor type
10
Rated operating voltage
400 V
11
Rated impulse withstand voltage
KV
12
Rated power frequency withstand voltage
2.5 kV
13
Rated current at the maximum operating
Minimum 630 A,
temperature
14
15
Rated short circuit current
Offered specification
KA
1
LV switchgear cabinet
Thickness of sheets
2
Painting type
3
IP class
4
Dimensions of the LV switchgear cabinet L mm x W mm x H mm
5
Weight of the LV switchgear cabinet
kg
Circuit breaker
MCCB - shall be accommodated inside the
cabinet and shall comply with IEC
947-2 category B
16
Minimum 2mm
Electro-static and
Thermal painting.
IP 42
16-1
Name of manufacturer
16-2
Country of origin
16-3
Model Nos-
16-4
Rated operating voltage
16-5
Rated impulse withstand voltage
16-6
Rated power frequency withstand voltage 2.5 kV
16-7
Rated currents at the maximum operating
temperature
16-8
16-9
16-10
Thermal overload and magnetic release
provided
Circuit breaker ultimate breaking
capacity
Circuit breaker service breaking
capacity
Yes
Main breaker 50 kA
Other breakers 35 kA
Main breaker 50 kA
Other breakers 35 kA
16-11
Short circuit making capacity
kA
16-12
Fault clearing time
ms
18
Submit Detail drawings, brochures
and catalogues of cabinet and MCCBs
Yes / No