Download I56-3326 MIX-M502MAPA

Survey
yes no Was this document useful for you?
   Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Document related concepts

Rectifier wikipedia , lookup

Audio power wikipedia , lookup

Ground (electricity) wikipedia , lookup

Stray voltage wikipedia , lookup

Pulse-width modulation wikipedia , lookup

Electrification wikipedia , lookup

Immunity-aware programming wikipedia , lookup

Electric power system wikipedia , lookup

Buck converter wikipedia , lookup

History of electric power transmission wikipedia , lookup

Islanding wikipedia , lookup

Power over Ethernet wikipedia , lookup

Electrical substation wikipedia , lookup

Power engineering wikipedia , lookup

Voltage optimisation wikipedia , lookup

Distribution management system wikipedia , lookup

Alternating current wikipedia , lookup

Switched-mode power supply wikipedia , lookup

Earthing system wikipedia , lookup

Rectiverter wikipedia , lookup

AC adapter wikipedia , lookup

Mains electricity wikipedia , lookup

Solar micro-inverter wikipedia , lookup

Electrical wiring in the United Kingdom wikipedia , lookup

Transcript
INSTALLATION AND MAINTENANCE INSTRUCTIONS
25 Interchange Way, Vaughan Ontario, L4K 5W3
Phone: 905.660.4655; Fax: 905.660.4113
MIX-M502MAPA Interface Module
Specifications
Normal Operating Voltage:
15 to 32 VDC
Maximum Alarm Current:
5.1mA (LED on)
Average Operating Current:
400µA, 1 communication and 1 LED flash every 5 seconds, 3.9k eol
EOL Resistance:
3.9K Ohms
Maximum IDC wiring resistance:
25 Ohms
IDC Supply Voltage (between Terminals T3 and T4)
Regulated DC Voltage:
24 VDC power limited
Ripple Voltage:
0.1 Volts RMS maximum
Current:
90mA per module
Temperature Range:
32˚F to 120˚F (0˚C to 49˚C)
Humidity:
10% to 93% Non-condensing
Dimensions:
41⁄2˝ H x 4˝ W x 11⁄4˝ D (Mounts to a 4˝ square by 21⁄8˝ deep box.)
Accessories:
SMB500 Electrical Box
Before Installing
Wiring
This information is included as a quick reference installation
guide. Refer to the control panel installation manual for detailed
system information. If the modules will be installed in an existing
operational system, inform the operator and local authority that
the system will be temporarily out of service. Disconnect power to
the control panel before installing the modules.
NOTE: All wiring must conform to applicable local codes, ordinances, and regulations. This module is intended for power-limited wiring only.
1. Install module wiring in accordance with the job drawings and
appropriate wiring diagrams.
2. Set the address on the module per job drawings.
3. Secure module to electrical box (supplied by installer), as
shown in Figure 2A.
Figure 1. Controls and indicators:
NOTICE: This manual should be left with the owner/user of this
equipment.
General Description
The MIX-M502MAPA Interface Module is intended for use in intelligent, two-wire systems, where the individual address of each
module is selected using the built-in rotary decade switches. This
module allows intelligent panels to interface and monitor two-wire
conventional smoke detectors. It transmits the status (normal,
open, or alarm) of one full zone of conventional detectors back
to the control panel. All two-wire detectors being monitored must
be ULC compatible with this module. The MIX-M502MAPA has a
panel controlled LED indicator.
Figure 2A. Module mounting
with barrier:
C0218-06
Figure 2B:
Compatibility Requirements
To ensure proper operation, these modules shall be connected to
listed compatible system control panels only.
Mounting
The MIX-M502MAPA mounts directly to 4˝ square electrical boxes
(see Figure 2A). The box must have a minimum depth of 21⁄8˝. Surface mounted electrical boxes (SMB500) are available from Mircom.
C0449-02
C0450-03
Compatible Two-wire System Sensor Smoke Detectors for Use with MIX-M502MAPA with Zone Identifier A:
Detector
Model
1451A
2451A
2451THA
1400A
2400A
2400THA
1151A
2151A
MC-460-012
Compatibility
ID
A
A
A
A
A
A
A
A
Detector
Type
Ionization
Photoelectric
Photoelectric with Thermal
Ionization
Photoelectric
Photoelectric with Thermal
Ionization
Photoelectric
1
Base
Model
B401/BA
B401/BA
B401/BA
N/A
N/A
N/A
B110LPA/B401A
B110LPA/B401A
Base
Identifier
A
A
A
—
—
—
A
A
Max
Detectors
20
20
20
20
20
20
20
20
I56-3326-000
Figure 3. Interface two-wire conventional detectors, NFPA Style B:
POWER TO THE INTERFACE MODULE MUST
BE EXTERNALLY SWITCED TO RESET THE
DETECTORS. AN MIX-M500RAPA RELAY
CONTROL MODULE CAN BE USED TO SWITCH
POWER FROM A STANDARD POWER SUPPLY SEE FIGURE 5.
LISTED BATTERY-BACKUP SWITCHED
REGUALTED DC POWER SUPPLY
3.9K EOL
RESISTOR
(INCLUDED)
A2143-10
OPTIONAL BRANCH CIRCUIT
TO NEXT INTERFACE MODULE.
TO NEXT
MODULE SUPERVISES SUPPLY
DEVICE
VOLTAGE AND DETECTOR LOOP.
)–(
)–(
)+(
)+(
INTERFACE
MODULE
FROM PANEL OR
PREVIOUS DEVICE
SIGNAL LINE CIRCUIT (SLC)
32 VDC MAX.
TWISTED PAIR
IS RECOMMENDED
(–)
)–(
)+(
(+)
CONNECT MODULES TO LISTED
COMPATIBLE CONTROL PANELS ONLY.
+
+
–
–
TERMINAL WIRING MUST BE POWER LIMITED.
DO NOT MIX FIRE ALARM INITIATING, SUPERVISORY,
OR SECURITY DEVICES ON THE SAME MODULE.
DO NOT LOOP WIRE UNDER TERMINALS. BREAK ALL WIRE
RUN TO PROVIDE SUPERVISION OF CONNECTIONS.
DETECTORS MUST BE ULC LISTED COMPATIBLE WITH
MODULE. INSTALL DETECTORS PER MANUFACTURER’S
INSTALLATION INSTRUCTIONS
*NOTE: ANY FAULT IN THE POWER SUPPLY IS LIMITED TO THAT ZONE AND DOES NOT RESULT IN A FAULT IN A SEPARATE ZONE.
C0921-10
Figure 4. Interface two-wire conventional detectors, NFPA Style D:
POWER TO THE INTERFACE MODULE MUST
BE EXTERNALLY SWITCED TO RESET THE
DETECTORS. AN MIX-M500RAPA RELAY
CONTROL MODULE CAN BE USED TO
SWITCH POWER FROM A STANDARD POWER
SUPPLY - SEE FIGURE 5.
OPTIONAL BRANCH CIRCUIT
TO NEXT INTERFACE MODULE.
MODULE SUPERVISES SUPPLY
VOLTAGE AND DETECTOR LOOP.
LISTED BATTERY-BACKUP
SWITCHED REGUALTED
DC POWER SUPPLY
TO NEXT
DEVICE
)–(
)–(
)+(
)+(
FROM PANEL OR
PREVIOUS DEVICE
INTERFACE
MODULE
(–)
)–(
)+(
(+)
3.9K EOL RESISTOR
REQUIRED AT TERMINALS
8 & 9 (INCLUDED) A2143-10
SIGNAL LINE CIRCUIT (SLC)
32 VDC MAX.
TWISTED PAIR
IS RECOMMENDED
CONNECT MODULES TO LISTED
COMPATIBLE CONTROL PANELS ONLY.
+
+
–
–
TERMINAL WIRING MUST BE POWER LIMITED.
DO NOT MIX FIRE ALARM INITIATING, SUPERVISORY,
OR SECURITY DEVICES ON THE SAME MODULE.
DO NOT LOOP WIRE UNDER TERMINALS. BREAK ALL WIRE
RUN TO PROVIDE SUPERVISION OF CONNECTIONS.
DETECTORS MUST BE ULC LISTED COMPATIBLE WITH
MODULE. INSTALL DETECTORS PER MANUFACTURER’S
INSTALLATION INSTRUCTIONS
C0922-09
*NOTE: ANY FAULT IN THE POWER SUPPLY IS LIMITED TO THAT ZONE AND DOES NOT RESULT IN A FAULT IN A SEPARATE ZONE.
Figure 5. Relay control module used to disconnect a power supply:
TO NEXT
DEVICE
)–(
)–(
)+(
)+(
RELAY CONTROL
MODULE
POWER LIMITED DC
POWER SUPPLY,
LISTED FOR FIRE
PROTECTION WITH
BATTERY BACKUP
FROM PANEL OR
PREVIOUS DEVICE
SIGNAL LINE CIRCUIT (SLC)
32 VDC MAX.
TWISTED PAIR
IS RECOMMENDED
)+(
)–(
)–(
)+(
CONNECT MODULES TO LISTED
COMPATIBLE CONTROL PANELS ONLY.
*NOTE: ANY FAULT IN THE POWER SUPPLY IS LIMITED TO THAT
ZONE AND DOES NOT RESULT IN A FAULT IN A SEPARATE ZONE.
)–(
)+(
C0923-04
MC-460-012
2
I56-3326-000
© 2008 Mircom