LEVEL MONITOR
WITH LINEARIZATION, ANALOG AND
DATASHEET F173 - LEVEL MONITOR
HIGH / LOW ALARM OUTPUTS
Advantages
Signal output
• Robust IP67 (NEMA Type4X) field enclosure.
It is so rugged, you can even stand on it!
• Intrinsically Safe available - ATEX and IECEx
approval for gas and dust applications.
• Programming can be done by your own crew, with
the sensible menu-driven structure, saving cost
and irritation. Know one, know them all!
• Very diverse mounting possibilities: walls, pipes,
panels or directly onto outdoor sensors!
• Up to 4 free configurable alarm outputs.
• (0)4 - 20mA / 0 - 10V DC according to the
linearized level.
Features
• The F-Series is your first and safest choice for field
mount indicators in safe and hazardous area
applications. Especially in harsh weather
conditions like rain, snow, salty atmosphers and
temperatures between -40°C up to +80°C
(-40°F up to 176°F).
• Level measurement where linearization and
continuous level monitoring is important. Also
re-transmission of the level or serial
communication is required. Alternative basic
model: F070 - F073 - F077 and F170 or the D-Series
DIN panel mount indicators.
Signal input
Level
• (0)4 - 20mA.
• 0 - 10V DC.
Applications
• Displays level and percentage filled.
• 15 point linearization of the tank shape - with
interpolation.
• Four alarm values can be entered: low-low, low,
high and high-high level alarm.
• Large 17mm (0.67") digits.
• Selectable on-screen engineering units; volumetric
or mass.
• Explosion/flame proof available.
• Full Modbus communication RS232/485/TTL.
• Loop or battery powered, 8 - 24V AC/DC or
115 - 230V AC power supply.
• Sensor supply 3 / 8.2 / 12 / 24V DC.
1
General information
The output signals can be a passive NPN, active
PNP or an isolated electro-mechanical relay.
Introduction
The F173 is a versatile level indicator with
linearization and continuous level monitoring
feature. It offers the facility to set two low level and
two high level alarm values. If desired, an ignore
function can be set up to allow for an incorrect
level for a certain period of time. Up to four outputs
are available to transmit the alarm condition. A
wide selection of options further enhances the
capabilities, including Intrinsic Safety and full
Modbus communication.
Signal input
The F173 does accept (0)4 - 20mA and 0 - 10V
input signals from any type of level measurement
device. Also a 4 - 20mA input loop powered model
is available.
Communication
All process data and settings can be read and
modified manually or through the Modbus
communication link (RS232 / RS485).
Full Modbus functionality remains available for the
Intrinsically Safe version (TTL).
Display
The display has large 17mm (0.67”) and 8mm
(0.31”) digits which can be set to show level,
percentage and alarm values. The alarm values
can be password protected. On-screen engineering
units are easily configured from a comprehensive
menu.
Hazardous areas
This model has been ATEX and IECEx certified
Intrinsically Safe for gas and dust applications,
with an allowed ambient temperature of
-40°C to +70°C (-40°F to +158°F). A flame proof
Ex d enclosure with ATEX certification is also
available.
Configuration
All configuration settings are accessed via a
simple operator menu which can be password
protected. Each setting is clearly indicated with an
alphanumerical description, which avoids
confusing abbreviations. All settings are safely
stored in EEPROM memory in the event of sudden
power failure.
Enclosures
Various types of enclosures can be selected, all
ATEX and IECEx approved. As standard the F173 is
supplied in an GRP panel mount enclosure, which
can be converted to an IP67 / NEMA Type4X GRP
field mount enclosure by the addition of a back
case. Most popular is our rugged aluminum field
mount enclosure with IP67 / NEMA Type4X rating.
Both European or U.S. cable gland entry threads
are available.
Analog output signal
The actual level is re-transmitted with the
(0)4 - 20mA or 0 - 10V DC output signal. The
output signal is updated eight times per second
with a filter function being available to smoothen
out the signal if desired.
The output value is user defined in relation to the
level, e.g. 4mA equals to 5m3 and 20mA equals to
20.000 m3. The output signal can be passive,
active or isolated where the passive output type
will loop power the F173 as well.
Overview application F173
alarm
output R1
alarm
output R2
alarm
output R3
alarm
output R4
Analog
output
Communication
link
Alarm outputs
Level input
Up to four configurable outputs are available to
transmit the alarm condition. You can have e.g.
two the same low alarm outputs, one high alarm
output and one "all alarms" output.
Type OS offers four mechanical relay outputs.
However, only two outputs are available in
Intrinsically Safe aplications. Three outputs are
available in all other configurations.
high - high
high
low
low - low
2
Linearization
F173
0.9"
14mm
1 2
/ "NPT
15mm
38mm
24mm 24mm
36mm
36mm
1 2
/ "NPT
15mm
HP
1 2
/ "NPT
HT
6 x M12
HJ
Ø22 ( 7/8") Ø22 ( 7/8") Ø22 ( 7/8")
HK
1.18" 1.18"
Flat bottom, no holes available.
1
/2"NPT
HU
4 x M20 x 1.5
HV
HZ
3
+
Display example - 90 x 40mm (3.5” x 1.6”)
+
+
+
PL: input loop powered
(terminals GND - 1 - 2 are not available)
=
=
=
=
OR: mech. relay
+
OT: passive trans.
07
08
I
I+
I+
I+
I+
I+
U
U+
AU: 0 - 10V
I
AP: 4 - 20mA
I-
AI: 4 - 20mA
I-
AF: 4 - 20mA
I
AB: 0 - 20mA
09
10
I+
I+
A - PL: 4 - 20mA
U+
U: 0 - 10V
A: (0)4 - 20mA
+
+
11
13
14
15
16
OA: active 24V DC
+
OT: passive trans.
17
18
19
60 mm (2.36")
Please note:
Terminal connections for the F173 with four alarm
outputs (type OS) is shown on one of the next pages.
12
30mm 30mm
PB / PC: battery powered
Internal long life Lithium battery
AP: 8 - 30V DC
Output loop powered
-
ZB: Backlight: 12 - 24V DC
-
PX: 8 - 30V DC
PM: 115 - 230V AC
-
PF: 24V DC
+
30mm (1.18") 30mm (1.18")
+
Ø12
PF: 24V AC
24mm 24mm
36mm
36mm
OR: mech. relay
HH
-
M20 x 1,5
Ø20
+
12mm 12mm
-
Ø20
PD - XI: 16 - 30V DC
M20 x 1,5
OT: passive trans.
HG
AA: 4 - 20mA
Ø22 ( 7/8")
06
25mm 25mm
05
HF
OA: active 24V DC
M16 x 1,5
Ø20
04
Ø16
ALARM OUTPUT 3
HD
03
M20 x 1,5 PG9
OA: active 24V DC
HO
HE
LEVEL SENSOR INPUT
GRP
PD: 8 - 24V DC
12mm 12mm
HN
112 mm (4.40")
02
M20 x 1,5
HM
20
21
Ø 7mm (0.27")
01
25mm
22
23
24
panel cut-out
00
25mm
25
26
27
A
A
DTR
+12V
RXD
CT: TTL Intrinsically Safe
CI: RS485 - 4 wire
28
RXD
CH: RS485 - 2 wire
DTR
+12V
CB: RS232
TXD
B
B
TXD
29
COMMUNICATION
98 (3.86")
115 (4.53")
PD: 8 - 24V AC
M20 x 1,5
HL
ANALOG OUTPUT
/2"NPT
ALARM OUTPUT 1
1
ALARM OUTPUT 2
M16 x 1,5
1.18"
22,50mm
Aluminum
POWER REQUIREMENTS
30mm 30mm
HA
22,50mm (0.9")
30mm 30mm
22,50mm
75 mm (2.95")
22,50mm
/ "NPT
Ø 7mm (0.27")
17mm
0.9"
130 mm (5.12")
14mm
1 2
22,50mm
HB & HC enclosures
22,50mm (0.9")
22,50mm
1.18"
22,50mm
PG9
17mm
130 mm (5.12")
+
F173
29 mm
(1.14")
+
0.9"
31 mm
(1.22")
15mm
120 mm (4.72")
Y
30
Z
31
Aluminum & GRP panel mount enclosure
+
16mm
120 mm (4.72")
Dimensions enclosures
Terminal connections
Aluminum & GRP field / wall mount enclosures
Ø16
Typical wiring diagram F173-A-AP-CH-OT-PX
Typical wiring diagram F173-A-AA-CB-OA-PD
OUTPUT LOOP POWERED
24V AC / DC POWER SUPPLY
TERMINAL CONNECTORS
F100 - series
Modbus communication type CB: RS232
29
28
27
Common ground
26
29
28
DTR
12V
26
Common ground
RXD
6
Supply *
11
Level sensor input type A:
(0)4 - 20mA
Signal
09
10
Common ground
e.g. indicator
06
Common ground
04
01
Power supply type PX:
8 - 30V DC
(not used in this example)
Common ground
*Supply voltage: 3.2V DC to sensor
8 - 24V AC
Power supply type PD:
8 - 24V AC / DC
00
01
00
03
Common ground
Switch output type OA:
active 24V DC signal
02
Switch output type OT:
passive transistor
-
04
+
03
alarm output 2
Main supply
Common ground
Switch output type OA:
active 24V DC signal
05
-
05
Switch output type OT:
passive transistor
alarm output 2
Common ground
Analog output type AA:
active 4 - 20mA
alarm output 1
+
06
alarm output 1
Common ground
Level sensor input type A:
(0)4 - 20mA
08
09
08
07
-
Common ground
8 - 30V DC
-
e.g. indicator
Common ground
+
Analog output type AP:
passive 4 - 20mA (loop powered)
+
Common ground
5
Common ground
10
Signal
Switch output type OA:
active 24V DC signal
07
15
11
Supply *
Switch output type OT:
passive transistor
-
Common ground
alarm output 3
+
16
alarm output 3
8 - 24V DC
-
A
TXD
27
Modbus communication type CH: RS485 - 2 wire
B
+
TERMINAL CONNECTORS
F100 - series
*Supply voltage: 3.2 / 8.2 / 12 / 24V DC to sensor
4
F173
Typical wiring diagram F173-A-AI-CI-OR-PM
Typical wiring diagram F173-A-AP-CB-OS-PD
115 - 230V AC POWER SUPPLY
Z
31
Y
30
B
29
TXD
A
RXD
Modbus communication type CI: RS485 - 4 wire
28
27
26
14
alarm output 3
Switch output type OS:
mechanic relay
alarm output 2
Signal
10
09
09
Analog output type AI: 8 - 30V DC
passive isolated 4 - 20mA
05
Switch output type OR:
mechanic relay
Main supply
Common ground
24V AC
Power supply type PD:
24V AC / DC
00
01
L1
02
N
06
00
01
02
03
Common ground
03
04
Signal
alarm output 2
Power supply type PM:
115 - 230V AC
Level sensor input type A:
(0)4 - 20mA
*Supply voltage: 3.2 / 8.2 / 12 / 24V DC to sensor
5
24V DC
-
07
Supply *
+
05
alarm output 1
*Supply voltage: 3.2 / 8.2 / 12 / 24V DC to sensor
F173
8 - 30V DC
-
04
e.g. indicator
Common ground
08
08
+
Common ground
N
Analog output type AP:
passive 4 - 20mA (loop powered)
e.g. indicator
Main supply
0 - 230V AC / DC
+
Common ground
L1
alarm output 1
10
11
Level sensor input type A:
(0)4 - 20mA
-
Supply *
11
12
13
15
-
Common ground
15
16
8 - 24V DC
alarm output 3
alarm output 4
+
Switch output type OT:
passive transistor
16
17
26
Common ground
29
Modbus communication type CB: RS232
DTR
12V
Common ground
24V AC / DC POWER SUPPLY
TERMINAL CONNECTORS
F100 - series
28
TERMINAL CONNECTORS
F100 - series
Hazardous area applications
Certificate of conformity KEMA 03ATEX1074 X
• IECEx DEK 11.0042X
The F173-XI has been certified according ATEX
and IECEx by DEKRA for use in Intrinsically Safe
applications with an ambient temperature of
-40°C to +70°C (-40°F to +158°F).
• The ATEX markings for gas and dust
applications are:
II 1 G Ex ia IIB/IIC T4 Ga
II 1 D Ex ia IIIC T100 °C Da.
• The IECEx markings for gas and dust
applications are: Ex ia IIC/IIB T4 Ga and
Ex ia IIIC T100 °C Da.
Besides the I.S. power supplies for the two
alarm outputs, it is allowed to connect up to
three I.S. power supplies in IIB/IIIC applications
or one in IIC applications. Consult the certificate
for the maximum input and output values of the
circuits. Full functionality of the F173 remains
available, including two alarm outputs and
4 - 20mA output and Modbus communication
(type CT). Power supply type PD-XI offers a
sensor supply according to the connected power
supply voltage at terminal 1.
An ATEX approved flame proof Ex d enclosure is
available as well. Please contact your supplier
for further details.
Configuration example IIB / IIIC - F173-A-AF-CT-OT-PC-XI - Battery powered
HAZARDOUS AREA
SAFE AREA
RXD
Uo=max 30V
28
TXD
29
Modbus communication type CT: TTL
26
e.g. indicator
Ci = 17nF
Analog output type AF:
passive floating 4 - 20mA
10
07
06
05
03
04
Po=max 750mW
Uo=max 30V
Po=max 750mW
Io=max 100mA
Alarm output 2
6
Uo=max 30V
Io=max 100mA
Alarm output 1
-
Switch output type OT:
passive transistor
Po=max 750mW
+
Ci is negligibly
small
Uo=max 30V
-
Common ground
Switch output type OT:
passive transistor
Po=max 750mW
Io=max 100mA
+
Common ground
Ci is negligibly
small
Uo=max 30V
Io=max 100mA
-
08
09
Level sensor input
type A: 4 - 20mA
+
Ci is negligibly
small
-
Circuit depends on
type of signal
+
Signal
Common ground
Po=max 850mW
e.g. PC
For example: MTL5051
-
Common ground
27
+
DTR
+12V
Io=max 250mA
ISOLATOR:
I.S. Certified Isolator
TTL to
RS232 / RS422 / TTL
REPEATER
For example
MTL 5541
POWER SUPPLY
e.g. MTL 5525
and / or
REPEATER
e.g. MTL 5541
e.g. indicator
POWER SUPPLY
e.g. MTL 5525
or
SWITCH INTERFACE
e.g. MTL 5511
e.g. sounder
POWER SUPPLY
e.g. MTL 5525
or
SWITCH INTERFACE
e.g. MTL 5511
e.g. sounder
Note: above values are safety values.
Consult the technical specification for operational values.
F173
Configuration example IIB / IIIC - F173-A-AP-CT-OT-(PX)-XI - Output loop powered
HAZARDOUS AREA
TERMINAL CONNECTORS
F100 - series
SAFE AREA
RXD
Uo=max 30V
28
TXD
29
Modbus communication type CT: TTL
26
11
+
09
Analog output type AP:
passive 4 - 20mA (output loop powered)
07
06
Switch output type OT:
passive transistor
Po=max 750mW
Uo=max 30V
Po=max 750mW
Io=max 100mA
Alarm output 1
Switch output type OT:
passive transistor
03
01
PX: Not used in this example
00
Common ground
* Note sensor supply voltage: 3.2V DC - not suitable to power analog sensors.
7
Uo=max 30V
Io=max 100mA
Alarm output 2
-
04
+
Common ground
Ci is negligibly
small
Uo=max 30V
Io=max 100mA
05
Ci is negligibly
small
Po=max 750mW
-
08
e.g. indicator
Ci = 17nF
Uo=max 30V
Io=max 100mA
+
Common ground
Level sensor input type: A
(0)4 - 20mA
-
Common ground
Ci is negligibly
small
+
10
Signal
-
Circuit depends on
type of signal
For example: MTL5051
Supply *
Common ground
F173
Po=max 850mW
e.g. PC
-
Common ground
27
+
DTR
+12V
Io=max 250mA
ISOLATOR:
I.S. Certified Isolator
TTL to
RS232 / RS422 / TTL
REPEATER
For example
MTL 5541
POWER SUPPLY
e.g. MTL 5525
and / or
REPEATER
e.g. MTL 5541
e.g. indicator
POWER SUPPLY
e.g. MTL 5525
or
SWITCH INTERFACE
e.g. MTL 5511
e.g. sounder
POWER SUPPLY
e.g. MTL 5525
or
SWITCH INTERFACE
e.g. MTL 5511
Po=max 750mW
e.g. sounder
Note: above values are safety values.
Consult the technical specification for operational values.
Configuration example IIB / IIIC and IIC - F173-A-AP-(CT)-OT-PD-XI - Power requirement 16 - 30V DC
HAZARDOUS AREA
TERMINAL CONNECTORS
F100 - series
SAFE AREA
RXD
Uo=max 30V
28
TXD
29
Modbus communication type CT: TTL
Please note: communciation type CT is not allowed in IIC applications.
Po=max 850mW
e.g. PC
For example: MTL5051
26
-
Common ground
27
+
DTR
+12V
Io=max 250mA
ISOLATOR:
I.S. Certified Isolator
TTL to
RS232 / RS422 / TTL
* Note: Communication only allowed when configured as IIB / IIIC.
11
Supply *
Level sensor input type: A
(0)4 - 20mA
Common ground
Ci is negligibly
small
e.g. indicator
Ci = 17nF
Analog output type AP:
passive 4 - 20mA
07
08
Common ground
10
Signal
09
Circuit depends on
type of signal
TOTAL Co OF ALL CONNECTED
ANALOG APPARATUS IN IIC
APPLICATIONS MAY NOT
EXCEED 66nF MINUS 17nF
(17nF IS USED BY THE ANALOG
OUTPUT SIGNAL TERMINAL 7 + 8).
Switch output type OT:
passive transistor
05
03
01
e.g. sounder
Po=max 750mW
POWER SUPPLY
e.g. MTL 5525
or
SWITCH INTERFACE
e.g. MTL 5511
e.g. sounder
Uo=max 30V
POWER SUPPLY
Po=max 750mW
Uo=max 30V
Io=max 100mA
Alarm output 2
02
Main supply
Switch output type OT:
passive transistor
-
04
+
Common ground
Ci is negligibly
small
POWER SUPPLY
e.g. MTL 5525
or
SWITCH INTERFACE
e.g. MTL 5511
Uo=max 30V
Io=max 100mA
Alarm output 1
-
06
+
Common ground
Ci is negligibly
small
+
Io=max 100mA
00
-
Common ground
Power supply type PD: 16 - 30V DC
(please note: PD and battery supply (type PC) is NOT allowed in IIC applications).
Po=max 750mW
For example
MTL 5525
Note: above values are safety values.
Consult the technical specification for operational values.
* Note power supply type PD: the supply voltage to the analog sensor is as connected to terminal 1 (internally linked).
8
F173
Configuration example IIB / IIIC - F173-A-AF-CT-OT-(PC)-(PD)-XI - Power requirement 16 - 30V DC or battery powered
HAZARDOUS AREA
TERMINAL CONNECTORS
F100 - series
SAFE AREA
RXD
Uo=max 30V
28
TXD
29
Modbus communication type CT: TTL
For example: MTL5051
26
11
Supply *
+
e.g. indicator
Analog output type AF:
passive floating 4 - 20mA
07
06
Switch output type OT:
passive transistor
04
03
02
Due to analog output type AF, the unit has to be powered with
battery type PC or with external power supply type PD.
Uo=max 30V
POWER SUPPLY
Power supply type PD: 16 - 30V DC
00
Uo=max 30V
Io=max 100mA
Alarm output 2
Io=max 100mA
-
01
e.g. sounder
Io=max 100mA
+
Common ground
Po=max 750mW
Po=max 750mW
-
Main supply
Switch output type OT:
passive transistor
e.g. sounder
POWER SUPPLY
e.g. MTL 5525
or
SWITCH INTERFACE
e.g. MTL 5511
Uo=max 30V
+
Common ground
Ci is negligibly
small
e.g. indicator
POWER SUPPLY
e.g. MTL 5525
or
SWITCH INTERFACE
e.g. MTL 5511
Po=max 750mW
Alarm output 1
REPEATER
For example
MTL 5541
POWER SUPPLY
e.g. MTL 5525
and / or
REPEATER
e.g. MTL 5541
Uo=max 30V
Io=max 100mA
05
Common ground
Ci is negligibly
small
Po=max 750mW
-
Ci = 17nF
Uo=max 30V
Io=max 100mA
+
08
09
Level sensor input type: A
(0)4 - 20mA
-
Ci is negligibly
small
+
Common ground
10
Signal
-
Circuit depends on
type of signal
Po=max 850mW
e.g. PC
-
Common ground
27
+
DTR
+12V
Io=max 250mA
ISOLATOR:
I.S. Certified Isolator
TTL to
RS232 / RS422 / TTL
Po=max 750mW
For example
MTL 5525
Note: above values are safety values.
Consult the technical specification for operational values.
* Note power supply type PD: the supply voltage to the analog sensor is as connected to terminal 1 (internally linked).
F173
9
Directives & Standards
Technical specification
EMC
Low voltage
RoHS
ATEX / IECEx
IP & NEMA
General
Display
Type
Dimensions
Digits
Refresh rate
Option ZB
Note ZB
High intensity reflective numeric and
alphanumeric LCD, UV-resistant.
90 x 40mm (3.5” x 1.6”).
Seven 17mm (0.67") and eleven 8mm (0.31") digits.
Various symbols and measuring units.
User definable: fast, 1sec , 3sec, 15sec, 30sec, off.
Transflective LCD with white LED-backlight.
Good readings in full sunlight and darkness.
Only available for safe area applications.
Directive 2014/30/EU, FCC 47 CFR part 15.
Directive 2014/35/EU
Directive 2011/65/EU
Directive 2014/34/EU, IEC 600079-0, IEC 60079-11.
EN 60529 & NEMA 250
Enclosure
General
Window
Sealing
Control keys
Polycarbonate window.
Silicone.
Three industrial micro-switch keys. UV-resistant
silicone keypad.
Ambient temperature
Safe areas
-40°C to +80°C (-40°F to +176°F).
Intrinsically Safe -40°C to +70°C (-40°F to +158°F).
Aluminum wall / field mount enclosures
General
Power requirements
Dimensions
Weight
Type AP
Analog output loop powerd, 8 - 30V DC.
Power consumption max 0.5 Watt.
Type PB
Long life Lithium battery - life-time depends upon
settings and configuration - up to 5 years.
(requires PD, PL or PX)
Type PC
Intrinsically Safe long life lithium battery - life-time
depends upon settings and configuration - up to 5
years. (requires XI and PD or PX)
Type PD
8 - 24V AC / DC ± 10%. Power consumption max. 10
Watt. Intrinsically Safe: 16 - 30V DC; power
consumption max. 0.75 Watt.
Type PF
24V AC / DC ± 10%. Power consumption max. 15 Watt.
Type PL
Input loop powered from sensor signal 4 - 20mA
(type “A”) - requires types AI and OT (not Xi).
Type PM
115 - 230V AC ± 10%. Power consumption max. 15 Watt.
Type PX
8 - 30V DC. Power consumption max. 0.5 Watt.
Type ZB
12 - 24V DC ± 10%. Power consumption max. 1 Watt.
Note PB/PF/PM Not available Intrinsically Safe.
Note PF/PM
The total consumption of the sensors and outputs
may not exceed 400mA @ 24V.
Note
For Intrinsically Safe applications, consult the safety
values in the certificate.
Type HA
Type HL
Type HM
Type HN
Type HO
Type HP
Type HT
Type HU
Type HV
Type HZ
GRP wall / field mount enclosures
General
Dimensions
Weight
Type HD
Type HE
Type HF
G
Type H
Type HH
Type HJ
Type HK
Sensor excitation
Type PB/PC/PX
Note
Type PD
Type PD-XI
Type PF / PM
3V DC.
This is not a real sensor supply. Only suitable for
sensors with a very low power consumption.
3 / 8.2 / 12 / 24V DC - max. 50mA @ 24V DC.
The sensor supply volage is according to power
supply as connected to terminal 1 (internally linked).
3 / 8.2 / 12 / 24V DC - max. 400mA @ 24V DC.
GRP wall/field mount enclosure IP67 / NEMA Type4X,
UV-resistant and flame retardant.
130 x 120 x 75mm (5.12" x 4.72" x 2.95") - W x H x D.
600 gr.
Cable entry: no holes.
Cable entry: 2 x Ø 16mm and 1 x Ø 20mm.
Cable entry: 1 x Ø 22mm (7/8").
Cable entry: 2 x Ø 20mm.
Cable entry: 6 x Ø 12mm.
Cable entry: 3 x Ø 22mm (7/8").
Flat bottom, cable entry: no holes.
Panel mount enclosures
Dimensions
Panel cut-out
Type HB
Weight
Type HC
Terminal connections
Type
Die-cast aluminum wall/field mount enclosure IP67 /
NEMA Type4X with 2-component UV-resistant coating.
130 x 120 x 75mm (5.12" x 4.72" x 2.95") - W x H x D.
1100 gr.
Cable entry: 2 x PG9 and 1 x M20.
Cable entry: 3 x 1/2" NPT.
Cable entry: 2 x M16 and 1 x M20.
Cable entry: 1 x M20.
Cable entry: 2 x M20.
Cable entry: 6 x M12.
Cable entry: 1 x 1/2" NPT.
Cable entry: 3 x 1/2" NPT.
Cable entry: 4 x M20.
Cable entry: no holes.
Removable plug-in terminal strip.
Wire max. 1.5mm2 and 2.5mm2.
Weight
130 x 120 x 60mm (5.12" x 4.72" x 2.36") - W x H x D.
115 x 98mm (4.53" x 3.86") L x H.
Die-cast aluminum panel mount enclosure IP65 /
NEMA Type4X.
600 gr.
GRP panel mount enclosure IP65 / NEMA Type4X,
UV-resistant and flame retardant.
450 gr.
Data protection
Type
Password
EEPROM backup of all settings. Data retention at
least 10 years.
Configuration settings can be password protected.
10
F173
Digital outputs
Hazardous area
Intrinsically Safe (Type XI)
ATEX
certification
IECEx
certification
Ambient Ta
Function
II 1 G Ex ia IIB/IIC T4 Ga.
II 1 D Ex ia IIIC T100 °C Da.
Ex ia IIC/IIB T4 Ga.
Ex ia IIIC T100 °C Da.
-40°C to +70°C (-40°F to +158°F).
Type OA
Type OR
Type OS
Explosion proof (Type XF)
ATEX certification
Type XF
Weight
Note
II 2 G / Ex d IIB T5 Gb.
II 2 D / Ex t IIIB T100 °C Db.
Dimensions of enclosure: 300 x 250 x 200mm
(11.8" x 9.9" x 7.9") L x H x D.
Appr. 15kg.
IECEx available on request.
Type OT
Note
Operational
Operator functions
Signal inputs
Level sensor
Displayed
functions
Type A
(0)4 - 20mA. Analog input signal can be scaled to any
desired range within 0 - 20mA.
Type U
0 - 10V DC. Analog input signal can be scaled to any
desired range within 0 - 10V DC.
Accuracy
Resolution: 14 bit. Error < 0.025mA / ± 0.125% FS.
Low level cut-off programmable.
Span
0.000010 - 9,999,999 with variable decimal position.
Offset
-999,999 - +999,999 units.
Update time
Four times per second.
Voltage drop
Type A: 2.5V @ 20mA.
Load impedance Type U: 3kOhm.
Relationship
Linear calculation.
Note
For signal type A and U: external power to sensor is
required; e.g. type PD.
Update time
Type AA
Type AB
Type AF
Type AI
Type AP
Type AU
• Level and percentage.
• Low-low alarm value.
• Low alarm value.
• High alarm value.
• High-high alarm value.
• Alarm values can be set (or only displayed).
Level
Digits
Units
Decimals
Offset
7 digits.
L, m3, GAL, USGAL, kg, lb, bbl, no unit.
0 - 1 - 2 or 3.
User defined quantity.
Height
Digits
Units
Signal outputs
Analog output
Function
Accuracy
User defined: low, low-low, high, high-high or all
alarms output.
Three active 24V DC transistor outputs (PNP);
max. 50mA per output (requires PD, PF, PM or PX).
Two electro-mechanical relay outputs isolated (N.O.) max. switch power 230V AC - 0.5A (requires PF
or PM) and one transistor output OT or OA.
Four electro-mechanical relay outputs - isolated;
max. switch power 230V AC - 0.5A per relay
(requires AP and PD with 24V AC / DC).
Three passive transistor outputs (NPN) - not isolated.
Max. 50V DC - 300mA per output.
Intrinsically Safe applications: only two transistor
outputs type OT available.
Decimals
Transmitting linearized level.
10 bit. Error < 0.05%. Analog output signal can be
scaled to any desired range.
Eight times per second.
Active 4 - 20mA output (requires PD, PF, PM or PX).
Active 0 - 20mA output (requires PD, PF, PM or PX).
Passive floating 4 - 20mA output for Intrinsically
Safe applications (requires XI + PD or PX).
Passive galvanically isolated 4 - 20mA output - also
available for battery powered models.
Passive 4 - 20mA output - not isolated. Unit will be
loop powered.
Active 0 - 10V DC output (requires PD, PF, PM or PX).
6 digits.
mm, cm, m, mtr, inch, ft, mmwk, mmwc, cmwk, cmwc,
mwk, mwc, inwc, ftwc, mbar, bar, psi, no unit.
0 - 1 or 2.
Percentage
Digits
Decimals
4 digits.
1.
Alarm values
Function
Digits
Units
Decimals
Type of alarm
Protection
Four user defined alarm values to monitor the level.
7 digits.
According to the settings for level.
According to the settings for level.
Low, high, low-low or high-high level alarm.
Includes alarm ignore time and configurable alarm
outputs.
The alarm values can be password protected.
Communication option
Function
Protocol
Speed
Addressing
Type CB
Type CH
Type CI
Type CT
F173
Reading display information, reading / writing all
configuration settings.
Modbus RTU.
1200 - 2400 - 4800 - 9600 baud.
Maximum 255 addresses.
RS232
RS485 2-wire
RS485 4-wire
TTL Intrinsically Safe.
Accessories
Mounting accessories
ACF02
ACF05
ACF06
ACF07
ACF08
ACF09
ACF11
11
Stainless steel wall mounting kit.
Stainless steel pipe mounting kit (worm gear clamps
not included).
Two stainless steel worm gear clamps Ø 44 - 56mm.
Two stainless steel worm gear clamps Ø 58 - 75mm.
Two stainless steel worm gear clamps Ø 77 - 95mm.
Two stainless steel worm gear clamps Ø 106 - 138mm.
Swivel with 25° movement from center axis for direct
flowmeter mounting: 1” NPT to 1/2” NPT
Ordering information
Standard configuration: F173-A-AP-CX-HC-OT-PX-XX-ZX.
Ordering information:
Level input signal
A
U
(0)4 - 20mA input.
0 - 10V DC input.
AA
AB
AF
AI
AP
AU
Active 4 - 20mA output - requires PD, PF, PM or PX.
Active 0 - 20mA output - requires PD, PF, PM or PX.
I.S. floating 4 - 20mA output - requires XI + PD or PX.
Isolated 4 - 20mA output.
Passive 4 - 20mA output, loop powered unit.
Active 0 - 10V DC output - requires PD, PF, PM or PX.
CB
CH
CI
CT
CX
Communication RS232 - Modbus RTU.
Communication RS485 - 2wire - Modbus RTU.
Communication RS485 - 4 wire - Modbus RTU.
Intrinsically Safe TTL - Modbus RTU.
No communication.
HB
HC
Aluminum enclosure.
GRP enclosure.
F173
-_
-A _
-C _
-H _
-O _
-P _
-X _
-Z _
Analog output signal
Communication
Panel mount enclosures - IP65 / NEMA Type4X
GRP field / wall mount enclosures - IP67 / NEMA Type4X
HD
HE
HF
G
H
HH
HJ
HK
Cable entry: no holes.
Cable entry: 2 x Ø 16mm & 1 x Ø 20mm.
Cable entry: 1 x Ø 22mm (7/8”).
Cable entry: 2 x Ø 20mm.
Cable entry: 6 x Ø 12mm.
Cable entry: 3 x Ø 22mm (7/8”).
Flat bottom, cable entry: no holes.
Aluminum field / wall mount enclosures - IP67 / NEMA Type4X
HA
HL
HM
HN
HO
HP
HT
HU
HV
HZ
Cable entry: 2 x PG9 + 1 x M20.
Cable entry: 2 x 1/2”NPT.
Cable entry: 2 x M16 + 1 x M20.
Cable entry: 1 x M20.
Cable entry: 2 x M20.
Cable entry: 6 x M12.
Cable entry: 1 x 1/2”NPT.
Cable entry: 3 x 1/2”NPT.
Cable entry: 4 x M20.
Cable entry: no holes.
OA
OR
OS
OT
Three active transistor outputs - requires PD, PF, PM or PX.
Two mechanical relay outputs + one OT or OA - requires PF or PM.
Four mechanical relay outputs - requires AP and PD.
Three passive transistor outputs - standard configuration.
PD
PF
PL
PM
PX
8 - 24V AC/DC + sensor supply - with XI: 16 - 30V DC.
24V AC/DC + sensor supply.
Input loop powered from sensor signal type “A” - requires AI and OT (not XI).
115 - 230V AC + sensor supply.
Basic power supply 8 - 30V DC (no real sensor supply).
PB
PC
Lithium battery powered - requires PD, PL or PX.
Lithium battery powered - Intrinsically Safe - requires XI, and PD or PX.
XI
XF
XX
Intrinsically Safe, according ATEX and IECEx.
Ex d enclosure - 3 keys according ATEX.
Safe area only.
ZB
ZX
Backlight.
No options.
Digital output signals
Power requirements
Additional battery supply (optional)
Hazardous area
The bold marked text contains the standard configuration.
Available Intrinsically Safe.
Specifications are subject to change without notice.
Fluidwell bv
P.O. Box 6
5460 AA - Veghel - The Netherlands
Telephone: +31 (0)413 343 786
Telefax: +31 (0)413 363 443
email: [email protected]
Internet: www.fluidwell.com
12
Copyright: Fluidwell bv - 2017 - F173-DATA-EN-V1704
Other options