Electrical Materials Compliance Sheet
Compliance Sheet for Electrical Materials
The following Technical data shall be furnished and filled by the bidders:
1-Distribution Transformer 11/0.416 kV 400 KVA
No
Description
1
2
3
Make/Brand/Model:
Name of manufacturer
Type:
4
5
Country of origin
Reference standard
6
Ambient temperature:
7
Air humidity:
8
9
10
11
12
13
14
Altitude:
Number of poles
Indoor or outdoor
Highest system voltage
Short circuit current on 11 kV side
Short circuit current on LV side
11 kV system earthing
1000M above MSL
3
Outdoor
12 kV
25 KA
15
Low voltage side earthing
Neutral solidly earthed
16
Voltage Ratio
11/0.416 KV
17
Type of cooling
ONAN
18
Rated power
- Continuous
400 kVA
19
20
21
22
Rated Frequency
Altitude:
Impedance voltage at 75 deg at
nominal tap
Nominal Voltage of winding
a) H.V.
b) L.V
UNDP required
specifications
Offered specification
Oil-immersed
hermetically sealed bolted type
IEC 60076-1, 2,3,5,8,
IEC 60214, IEC 60137
Maximum:55/C
Minimum: -10/C
92% maximum
kA
Neutral isolated / earthed
through a resistor
50Hz
1000M above MSL
4%
11 kV
0.416 kV
23
Insulation level 11 kV
a) Lightning Impulse
b) AC power frequency
24
Insulation level LV -phases/neutral
AC power frequency
75 kV
28 kV
3V
Short circuit withstand capacity of
transformer
Winding temperature rise at rated
power
…..KA for
…….seconds
50 C
27
Top oil temperature rise at rated
power
45 C
28
No load loss
……..KW
29
Load loss at full load at 75 deg
temperature
Guaranteed magnetizing current
……..KW
25
26
30
31
32
33
34
35
36
37
38
39
40
Maximum flux density in iron at
rated frequency and at rated voltage
ratio at nominal voltage
Maximum current density in
windings at
rated power
a) H.V. winding
b) L.V. winding
Zero sequence impedance
No load current at rated voltage
Material of windings
Type of winding
a) H.V.
b) L.V.
Type of insulation of winding
a) H.V.
b) L.V.
Type of insulation of
a) Core assembly
b) Core laminations
Thickness of transformer
a) tank
b) sides
c) bottom
Thickness of radiator plates and for
cooling tube
……….A
≤ 1.65 Tesla
…A
Copper
Minimum 3 mm
Minimum 3 mm
Minimum 3 mm
….. mm
41
Winding connection
a) H.V.
Delta
b) L.V.
Star (Neutral brought out)
42
Vector group symbol
Dyn11
43
Type of core
44
Core sheet materials
45
Tap changer
46
11 kV side terminal arrangement
47
Low voltage terminal arrangement
48
Test pressure of oil leak test of tank
49
Noise level at 0.3 m distance
50
Off-load tap changer with
5 positions in the HV
winding giving
± 2 x 2.5 %.
Clamp type for terminating
up to 150 mm2 copper
conductor
Suitable for terminating
copper cables of cross
section area 7x1x 150 mm2
copper (two holes per phase )
Transformer oil
1
Type of oil
2
Manufacturer
3
Place of manufacture
4
Manufactruer’s type designation
5
Applied IEC standard
6
Kinematic viscosity mm2/s
IEC60296 class 1
IEC 60296
At 40 deg
≤ 16.5
At -15 deg
≤ 800
7
Flash point
≥ 140 C
8
Pour point
≤ - 30 C
9
Density at 20 deg C – kg/dm3
≤ 0.895
10
Breakdown strength
kV
11
Dielectric dissipation factor
51
Dimensions of transformer –
maximum
L1400 ( mm) x W 1000
(mm) x H 1400(mm)
52
Weight of transformer
kg
53
Type of corrosion protection on steel
parts
a) Inside tank
Oil resistant paint
b) Outside tank
Metalized, aluminium
paint or equivalent
54
11 kV bushings
54-1
Name of manufacturer
54-2
Make/Brand/Model:
54-3
Reference standard
54-4
Type of bushing
54-5
Rated current
A
54-6
Rated voltage
KV
54-7
Material
Porcelain
54-8
Color
Brown
54-9
Creepage distance
55
L V bushings
55-1
Name of manufacturer
55-2
Make/Brand/Model:
55-3
Reference standard
55-4
Type of bushing
55-5
Rated current
A
55-6
Rated voltage
KV
55-7
Material
Porcelain
55-8
Color
Brown
55-9
Creepage distance
56
Warranty period
57
Submit Manufacturer
certification:
Submit type test certificates or
reports :
Submit Detail drawings, brochures
and catalogues:
58
59
IEC 60137
IEC 60137
One year
2-Distribution Transformer 11/0.416 kV 250 KVA
No
Description
1
2
3
Make/Brand/Model:
Name of manufacturer
Type:
4
5
6
UNDP required
specifications
Oil-immersed
hermetically sealed bolted type
Country of origin
Reference standard
Ambient temperature:
IEC 60076-1, 2,3,5,8,
IEC 60214, IEC 60137
Maximum:55/C
Minimum: -10/C
7
Air humidity:
92% maximum
8
Altitude:
1000M above MSL
9
10
11
12
13
14
Number of poles
Indoor or outdoor
Highest system voltage
Short circuit current on 11 kV side
Short circuit current on LV side
3
Outdoor
12 kV
25 KA
15
Low voltage side earthing
16
Voltage Ratio
11/0.416 KV
17
Type of cooling
ONAN
18
Rated power
- Continuous
Rated Frequency
Altitude:
Impedance voltage at 75 deg at
nominal tap
Nominal Voltage of winding
a) H.V.
b) L.V
19
20
21
22
23
Offered specification
11 kV system earthing
Insulation level 11 kV
a) Lightning Impulse
KA
Neutral isolated / earthed
through a resistor
Neutral solidly earthed
250 kVA
50Hz
1000M above MSL
4%
11 kV
0.416 kV
75 kV
b) AC power frequency
24
25
26
27
Insulation level LV -phases/neutral
AC power frequency
Short circuit withstand capacity of
transformer
Winding temperature rise at rated
power
28 kV
3V
…..KA for
…….seconds
50 C
Top oil temperature rise at rated
power
45 C
28
No load loss in
……..KW
29
Load loss at full load at 75 deg
temperature
……..KW
30
Guaranteed magnetizing current
……….A
31
Maximum flux density in iron at
rated frequency and at rated voltage
ratio at nominal voltage
Maximum current density in
windings at
rated power
a) H.V. winding
b) L.V. winding
32
33
Zero sequence impedance
34
35
36
No load current at rated voltage
Material of windings
Type of winding
a) H.V.
b) L.V.
Type of insulation of winding
a) H.V.
b) L.V.
Type of insulation of
a) Core assembly
b) Core laminations
Thickness of transformer
a) tank
37
38
39
≤ 1.65 Tesla
…A
Copper
Minimum 3 mm
b) sides
c) bottom
Thickness of radiator plates and for
cooling tube
Winding connection
a) H.V.
Minimum 3 mm
Minimum 3 mm
b) L.V.
Star (Neutral brought
out)
42
Vector group symbol
Dyn11
43
Type of core
44
Core sheet materials
40
41
45
Tap changer
46
11 kV side terminal arrangement
47
Low voltage terminal arrangement
48
….. mm
Delta
Off-load tap changer with
5 positions in the HV
winding giving ± 2 x 2.5
%.
Clamp type for
terminating up to 150
mm2 copper conductor
Suitable for terminating
copper cables of cross
section area
6x1x95+1x70 mm2( 1
hole per phase )
Test pressure of oil leak test of tank
Noise level at 0.3 m distance
49
50
Transformer oil
1
2
3
4
5
6
7
8
Type of oil
IEC60296 class 1
Manufacturer
Place of manufacture
Manufactruer’s type designation
Applied IEC standard
IEC 60296
Kinematic viscosity mm2/s
At 40 deg
≤ 16.5
At -15 deg
≤ 800
Flash point
≥ 140 C
Pour point
≤ - 30 C
9
Density at 20 deg C – kg/dm3
≤ 0.895
10
Breakdown strength
kV
11
Dielectric dissipation factor
51
Dimensions of transformer
L 1230 ( mm) x W
700.(mm) x H
1300.(mm)
52
Weight of transformer
kg
53
Type of corrosion protection on steel
parts
a) Inside tank
b) Outside tank
54
54-1
54-2
54-3
54-4
54-5
54-6
54-7
54-8
54-9
55
55-1
55-2
55-3
55-4
55-5
55-6
55-7
55-8
Oil resistant paint
Metalized, aluminium
paint or equivalent
11 kV bushings
Name of manufacturer
Make/Brand/Model:
Reference standard
IEC 60137
Type of bushing
Rated current
A
Rated voltage
KV
Material
Porcelain
Color
Brown
Creepage distance
L V bushings
Name of manufacturer
Make/Brand/Model:
Reference standard
IEC 60137
Type of bushing
Rated current
A
Rated voltage
KV
Material
Porcelain
Color
Brown
55-9
Creepage distance
56
Warranty period
57
58
Submit Manufacturer certification:
Submit type test certificates or
reports :
Submit Detail drawings, brochures
and catalogues:
59
One year
3-Tubular Steel Poles 11 m for 11 kV
#
Description
UNDP specifications
Make:
Original manufacturer
(locally assembled not
acceptable)
1
2
3
4
Name of manufacturer
Country of origin
Ambient temperature:
Maximum:55/C
Minimum: -10/C
5
Air humidity:
92% maximum
6
Altitude:
1000M above MSL
7
8
Nominal voltage:
11 KV
Reference standard
BS, JIS, DIN or equivalent
standard
9
Properties of steel
9-1
Type of steel used
9-2
Tensile strength -min
Kgf/mm2
Yield strength -min
Kgf/mm2
Design bending stress- min
Kgf/mm2
Effective length of pole
11m
9-3
9-4
10
Offered specification
11
12
12-1
12-2
12-3
13
13-1
Weight
Kg
Wall thickness
Bottom section
mm
Middle section
mm
Top section
mm
Lengths of sections
Bottom section
5500 mm
13-2
Middle section
3000 mm
13-3
Top section
2500 mm
14
Outside diameter of sections
14-1
Bottom section
165 mm
14-2
Middle section
139 mm
14-3
Top section
114 mm
15
Manufacturing method (swaged/welded)
16-1 Working load ( Ps)
Kgf 285
16-2 Deflection at (Pp )
16-3 Breaking load ( Pb)
kgf
16-4 Factor of safety
17
Type of corrosion prevention system used
18
Submit Manufacturer certification:
19
Submit type test certificates or
reports :
20
Submit Detail drawings, brochures
and catalogues:
Hot dip galvanized
4-Lattice Steel Poles 11 m for 11 kV
#
Description
UNDP specifications
Original manufacturer
(locally assembled not
acceptable)
1
Make:
2
Name of manufacturer
3
Country of origin
4
Ambient temperature:
Maximum:55/C
Minimum: -10/C
5
Air humidity:
92% maximum
6
Altitude:
1000M above MSL
7
Nominal voltage:
11 KV
8
Reference standard
BS, JIS, DIN or an
equivalent standard
9
Properties of steel
9-1
Type of steel used
9-2
Tensile strength -min
Kgf/mm2
9-3
Yield strength -min
Kgf/mm2
9-4
Design bending stress- min
Kgf/mm2
10
Effective length of pole
11m
11
Weight
Kg
12-1
Working load ( Ps)
Kgf 700
12-2
Deflection at (Pp )
12-3
Breaking load ( Pb)
12-4
Factor of safety
13
Type of corrosion prevention system used
kgf
Hot dip galvanized
Offered specification
14
Manufacturing
15
Submit Manufacturer certification:
16
Submit type test certificates or reports :
15
Submit Detail drawings, brochures and
catalogues:
Confirmation that the
lattice pole shall be
manufactured as per the
specification No. D 46
and the drawing attached
to the specification
Yes /No
5-Tubular Steel Poles 9 m for LV
#
Description
UNDP specifications
1
Make:
Original manufacturer
(locally assembled not
acceptable)
2
Name of manufacturer
3
Country of origin
4
Ambient temperature:
Maximum:55/C
Minimum: -10/C
5
Air humidity:
92% maximum
6
Altitude:
1000M above MSL
7
Nominal voltage:
400V
8
Reference standard
BS, JIS, DIN or
equivalent standard
9
Properties of steel
9-1
Type of steel used
9-2
Tensile strength -min
Kgf/mm2
9-3
Yield strength -min
Kgf/mm2
9-4
Design bending stress- min
Kgf/mm2
Offered specification
10
Effective length of pole
9m
11
Weight
Kg
12
Wall thickness
12-1
Bottom section
mm
12-2
Middle section
mm
12-3
Top section
mm
13
Lengths of sections
13-1
Bottom section
4700 mm
13-2
Middle section
2300 mm
13-3
Top section
2000 mm
14
Outside diameter of sections
14-1
Bottom section
139 mm
14-2
Middle section
114 mm
14-3
Top section
89 mm
15
Manufacturing method (swaged/welded)
16-1
Working load ( Ps)
16-2
Deflection at (Pp )
16-3
Breaking load ( Pb)
16-4
Factor of safety
17
Type of corrosion prevention system used
18
Submit Manufacturer certification:
19
Submit type test certificates or reports :
Kgf 210
kgf
Hot dip galvanized
20
Submit Detail drawings, brochures and
catalogues:
6-Lattice Steel Poles 9 m for LV
#
Description
UNDP specifications
Original manufacturer
(locally assembled not
acceptable)
1
Make:
2
Name of manufacturer
3
Country of origin
4
Ambient temperature:
Maximum:55/C
Minimum: -10/C
5
Air humidity:
92% maximum
6
Altitude:
1000M above MSL
7
Nominal voltage:
400 V
8
Reference standard
BS, JIS, DIN or an
equivalent standard
9
Properties of steel
9-1
Type of steel used
9-2
Tensile strength -min
Kgf/mm2
9-3
Yield strength -min
Kgf/mm2
9-4
Design bending stress- min
Kgf/mm2
10
Effective length of pole
9m
11
Weight
Kg
12-1
Working load ( Ps)
Kgf 700
12-2
Deflection at (Pp )
Offered specification
12-3
Breaking load ( Pb)
12-4
Factor of safety
13
kgf
Type of corrosion prevention system used
Hot dip galvanized
14
Manufacturing
Confirmation that the
lattice pole shall be
manufactured as per the
specification No. D 46
and the drawing attached
to the specification
15
Submit Manufacturer certification:
16
Submit type test certificates or reports :
17
Submit Detail drawings, brochures and
catalogues:
Yes /No
7—ACSR Conductor (120/20 mm2):
Description
UNDP specifications
Original manufacturer
(locally assembled not
acceptable)
1
Make:
2
Name of manufacturer
3
Country of origin
4
Reference standards
IEC/ BS/DIN (48204)
5
Ambient temperature:
Maximum:55/C
Minimum: -10/C
6
Air humidity:
92% maximum
7
Altitude:
1000M above MSL
8
Number and diameter of stranding
Aluminium/Steel
Aluminium
Steel
26/2.44mm
7/1.9mm
9
Over all diameter
mm
10
Cross section area
mm2
11
Rated / ultimate tensile strength ( UTS ) – kg
kg
12
Weight , kg/km
kg
Offered specification
13
DC resistance , ohms/km at 20 deg C
ohms
14
Modulus of Elasticity of stranded
conductor kg/mm2
15
Coefficient of linear expansion of stranded
conductor , per deg C
16
Maximum continuous load current at 55
deg outdoor temperature
A
17
Maximum length of conductor and mass
of conductor per drum
m
kg
18
Submit Manufacturer certification:
19
Submit type test certificates or reports :
20
Submit Detail drawings, brochures and
catalogues:
8- AAC Conductor (95 mm2):
Description
1
Make:
2
Name of manufacturer
3
Country of origin
4
Reference standards AAC
UNDP specifications
Original manufacturer
(locally assembled not
acceptable)
IEC 61089 / DIN
(48201)
Ambient temperature:
Maximum:55/C
Minimum: -10/C
Air humidity:
92% maximum
Altitude:
1000M above MSL
8
Number and diameter of stranding
Aluminium
19/2.5mm
9
Over all diameter
mm
10
Cross section area
mm2
11
Rated / ultimate tensile strength ( UTS ) – kg
kg
5
6
7
Offered specification
kg
12
Weight , kg/km
13
ohms
DC resistance , ohms/km at 20 deg C
Modulus of Elasticity of stranded
conductor kg/mm2
Coefficient of linear expansion of stranded
conductor , per deg C
Assumed maximum continuous load
A
current A
14
15
16
17
Maximum length of conductor and mass
of conductor per drum
18
Submit Manufacturer certification:
19
Submit type test certificates or reports :
20
Submit Detail drawings, brochures and
catalogues:
M
kg
9-Low Voltage Power Cables – 95mm2
No
Description
1
Make/Brand/Model:
2
Name of manufacturer
3
4
Type :
Country of origin
5
6
7
8
9
Reference standard
Ambient temperature:
Air humidity:
Altitude:
Nominal Voltage :
Construction data
1) Number of conductor
2) Cross sectional area
3) Shape of conductor
10
4) Material of conductor
5) Material of insulation
6) Thickness of insulation (Nominal)
7) Material of sheath
8) Thickness of sheath (Nominal)
Low Voltage cables
UNDP required
specifications
According to Vender
List in Iraq
CU/PVC/PVC –
IEC 60502, IEC 60183,
IEC 60228, IEC 60287, ,
IEC 60287, IEC 60811,
IEC 60853,
Maximum:55/C
Minimum: -10/C
92% maximum
1000M above MSL
400 V
1 Core
95 mm2
Circular stranded
compacted
Copper
PVC
mm
PVC - ST2
mm
Offered
specification
11
12
13
14
15
9) Color of sheath
Gray
10) Type of treatment against termite in
outer sheath
11) Overall diameter of cable (Approx.)
12) Marking of cable
As per the specification
13) Net weight (Approx.) (kg/km)
kg
Electrical data:
1) AC. withstand voltage for 5 minutes
3 KV
2) Max. DC. conductor resistance at
0.193 ohm/km
20_C
3) Rated Frequency
50 Hz
Insulating resistance between phase and
M ohm
earth
Submit Manufacturer certification :
Submit Detail drawings, brochures and catalogues:
Submit type test certificates or reports :
10 – Outdoor LV Switchgear Cabinets - Pole Mounted - 400 A
No
Description
UNDP required
specifications
Original manufacturer
(locally assembled not
acceptable)
1
Name of manufacturer:
2
Country of origin:
3
Reference standards
IEC 60439
4
Ambient
temperature:
Maximum:55/C
Minimum: -10/C
5
Relative Humidity:
92% maximum
6
Altitude:
1000M above MSL
7
Rated voltage
416/240 Volts
8
Frequency
9
Switchgear type:
50 Hz
Outdoor type, pole
mounted cabinet
10
Rated operating voltage
11
Rated insulation voltage
12
Rated impulse withstand voltage
13
Rated power frequency withstand voltage 2.5 kV
14
Rated current at the maximum operating
temperature
kV
400 A
Offered specification
16
17
Rated short circuit current
for 1 second
The cabinet type:
Thickness of sheets
18
Painting type
19
IP class
20
Dimensions of the LV switchgear cabinet L mm x W mm x H mm
21
Weight of the LV switchgear cabinet
kg
22
Circuit breaker
MCCB - shall be accommodated inside the panel
for outgoing feeder and shall comply with IEC
947-2 category B
15
22-1
Country of manufacture
22-2
Name of manufacturer
22-3
Model No-
22-4
Rated operating voltage
22-5
Rated insulating voltage
22-6
Rated impulse withstand voltage
22-7
Rated power frequency withstand voltage
22-8
Rated current at the maximum operating
temperature
22-9
22-10
22-11
Thermal overload and magnetic release
provided
Circuit breaker ultimate breaking
capacity
Circuit breaker service breaking
capacity
22-12
Short circuit making capacity
22-13
Fault clearing time
23
Submit Manufacturer certification for
switchgear cabinet
24
Submit type test certificates or reports
25
Submit Detail drawings, brochures
and catalogues of cabinet and MCCB
KA
Outdoor type
Minimum 2mm
Electro-static and
thermal painting.
IP 55
Yes
35 kA
35 kA
kA
Yes / No
11 – Outdoor LV Switchgear Cabinets, Pole Mounted – 250 A
No
Description
UNDP required
specifications
Offered specification
Original manufacturer
(locally assembled not
acceptable)
1
Name of manufacturer:
2
Country of origin:
3
Reference standards
IEC 60439
4
Ambient
temperature:
Maximum:55/C
Minimum: -10/C
5
6
Relative Humidity:
Altitude:
92% maximum
1000M above MSL
7
Rated voltage
416/240 Volts
8
Frequency
9
Switchgear type:
50 Hz
Outdoor type, pole
mounted cabinet.
10
Rated operating voltage
11
Rated insulation voltage
12
Rated impulse withstand voltage
13
Rated power frequency withstand voltage 2.5 kV
14
Rated current at the maximum operating
temperature
15
Rated short circuit current
for 1 second
16
17
The cabinet type:
Thickness of sheets
Outdoor type
Minimum 2mm
18
Painting type
Electro-static and
thermal painting.
19
IP class
IP 55
20
Dimensions of the LV switchgear cabinet
L mm x W mm x H mm
21
Weight of the LV switchgear cabinet
kg
Circuit breaker
MCCB - shall be accommodated inside the panel
for outgoing feeder and shall comply with IEC
947-2 category B
22
22-1
Country of manufacture
22-2
Name of manufacturer
250 A
kA
22-3
Model No-
22-4
Rated operating voltage
22-5
Rated insulating voltage
22-6
Rated impulse withstand voltage
22-7
Rated power frequency withstand voltage
22-8
Rated current at the maximum operating
temperature
22-9
22-10
22-11
Thermal overload and magnetic release
provided
Circuit breaker ultimate breaking
capacity
Circuit breaker service breaking
capacity
Yes
35 kA
35 kA
22-12
Short circuit making capacity
kA
22-13
Fault clearing time
ms
23
Submit Manufacturer certification for
cabinet
24
Submit type test certificates or reports
25
Submit Detail drawings, brochures
and catalogues of cabinet and MCCB
Yes / No
12- 33 KV Pole Mounted Load Break Switch
No
Description
1
2
3
Make/Brand/Model:
Name of manufacturer
Type:
4
5
Country of origin
Reference standard
UNDP required
specifications
33 kV Load break
switch – pole mounted ,
Air type
6
Ambient temperature:
7
Air humidity:
IEC 62271-102, IEC
62271-103
Maximum:55/C
Minimum: -10/C
92% maximum
8
Altitude:
Number of poles
1000M above MSL
3
9
Offered
specification
10
11
12
13
14
15
16
17
Indoor or outdoor
Nominal Voltage
Highest system voltage
Outdoor
33 kV
36 kV
Rated current
600 A
Maximum overload breaking capacity
800 A
Rated Frequency
Altitude:
Insulation level 33 kV
a) Lightning Impulse
Phase – earth
Phase-phase
50Hz
1000M above MSL
b) AC power frequency
Phase – earth
Phase-phase
170 kV
195 kV
70 kV
80 kV
18
Short circuit withstand capacity
25 KA for 1 second
19
Breaking current capacity
KA
20
Minimum clearance – phase to phase
mm
21
Minimum clearance – phase to Earth
mm
22
Main contact material
23
Main contact plating material
24
All current carrying parts copper or
copper alloy
Dimensions of operating rod/ pipe
(Vertical) ;
25
26
27
i)
Diameter
mm
ii)
Length
mm
iii)
Thickness (for pipe only)
mm
Whether the operating mechanism
provided with earthing terminal
Galvanizing
Yes
a) Thickness
mm
b) Weight per square meter
g/m²
28
29
30
Whether the holding part of the
operating handle is insulated
Mechanical ON/OFF indication
Available
33 kV bushings
Yes/No
Yes
30-1
Name of manufacturer
30-2
Make/Brand/Model:
30-3
Reference standard
30-4
Type of bushing
30-5
Rated current
A
30-6
Rated voltage
KV
30-7
Material
Porcelain
30-8
Color
Brown
30-9
Creepage distance
31
Warranty period
32
33
Submit Manufacturer certification:
Submit type test certificates or
reports :
Submit Detail drawings, brochures
and catalogues:
34
IEC 60137
One year
13- 11 KV Pole Mounted Load Break Switch
No
Description
1
2
3
Make/Brand/Model:
Name of manufacturer
Type:
4
5
Country of origin
Reference standard
6
Ambient temperature:
7
Air humidity:
8
Altitude:
Number of poles
9
UNDP required
specifications
11 kV Load break
switch – pole mounted ,
Air type
IEC 62271-102, IEC
62271-103
Maximum:55/C
Minimum: -10/C
92% maximum
1000M above MSL
3
Offered
specification
10
11
12
13
14
15
16
17
Indoor or outdoor
Nominal Voltage
Highest system voltage
Outdoor
11 kV
12 kV
Rated current
400 A
Maximum overload breaking capacity
800 A
Rated Frequency
Altitude:
Insulation level 11kV
c) Lightning Impulse
Phase – earth
Phase-phase
50Hz
1000M above MSL
d) AC power frequency
Phase – earth
Phase-phase
75 kV
85 kV
28 kV
32 kV
18
Short circuit withstand capacity
25 KA for 1 second
19
Breaking current capacity
KA
20
Minimum clearance – phase to phase
mm
21
Minimum clearance – phase to Earth
mm
22
Main contact material
23
Main contact plating material
24
All current carrying parts copper or
copper alloy
Dimensions of operating rod/ pipe
(Vertical) ;
25
26
27
i)
Diameter
mm
ii)
Length
mm
iii)
Thickness (for pipe only)
mm
Whether the operating mechanism
provided with earthing terminal
Yes
Galvanizing
a) Thickness
mm
b) Weight per square meter
g/m²
28
Whether the holding part of the
operating handle is insulated
29
Mechanical ON/OFF indication
Available
30
11 kV bushings
Yes/No
Yes
30-1
Name of manufacturer
30-2
Make/Brand/Model:
30-3
Reference standard
30-4
Type of bushing
30-5
Rated current
A
30-6
Rated voltage
KV
30-7
Material
Porcelain
30-8
Color
Brown
30-9
Creepage distance
31
Warranty period
32
33
Submit Manufacturer certification:
Submit type test certificates or
reports :
Submit Detail drawings, brochures
and catalogues:
34
IEC 60137
One year
14 -33 KV Porcelain Pin Insulators with Spindle
Description:
UNDP specifications
1
Make/brand / Model
Original manufacturer
(locally assembled not
acceptable)
2
Name of manufacturer
3
Country of origin
4
Reference standard
IEC 60383-1/
ANSI/BS/ASTM
5
Ambient temperature :
Maximum:55 deg C
Minimum:-10
deg C
6
Relative Humidity :
92% maximum
7
Altitude
1000 M above mean sea
level
#
Offered specification
8
Nominal voltage
33 kV
9
System highest voltage
36 kV
10
Impulse withstand voltage + ve
180-200 KV
11
Impulse withstand voltage - ve
190-220 kV
12
Power frequency withstand voltage- dry 100-110 KV
13
Power frequency withstand voltage – wet 80-90 KV
14
15
16
17
18
19
Puncture voltage
Mechanical failing load
Creepage distance
Material of insulator
Color of insulator
Zn sleeve provided
20
Radius of conductor groove
21
Total height
203-250 mm
22
Total diameter
≥ 280 mm
23
Cantilever strength
10-12 KN
24
Weight of insulator
7.5-7.9 Kg
25
Height of galvanized steel spindle- min
125 mm
26
Diameter of spindle - min
18.5 mm
27
Submit Manufacturer certification
28
Submit type test certificates or reports
29
Submit Detail drawings, brochures
and catalogues of insulator and
spindle
200-210 kV
580-685 mm
Ceramic
Brown
Yes
Suitable for a conductor
of 20.3 mm diameter
15 -11 KV Porcelain Pin Insulators with Spindle
#
Description:
1
Make/brand / Model
UNDP specifications
Original manufacturer
(locally assembled not
acceptable)
Offered specification
2
Name of manufacturer
3
Country of origin
4
Reference standard
5
Ambient temperature :
Maximum:55 deg C
Minimum:-10 deg C
6
Relative Humidity :
92% maximum
7
Altitude
1000 M above mean sea
level
8
Nominal voltage
11 kV
9
System highest voltage
15 kV
10
Impulse withstand voltage + ve
95-105 KV
11
Impulse withstand voltage - ve
105-120 kV
12
Power frequency withstand voltage- dry
65-75 KV
13
Power frequency withstand voltage – wet 35-50 KV
14
15
16
17
18
19
Puncture voltage
Mechanical failing load
Creepage distance
Material of insulator
Color of insulator
Zn sleeve provided
20
Radius of conductor groove
Suitable for a conductor
of 15.5 mm diameter
21
Total height
135-160 mm
22
Total diameter
140-175 mm
23
Cantilever strength
10-12 KN
24
Net Weight
1.8-2.5 Kg
25
Height of galvanized steel spindle - min
125 mm
26
Diameter of spindle - min
18.5 mm
27
Submit Manufacturer certification
28
Submit type test certificates or reports
29
Submit Detail drawings, brochures
and catalogues of insulator and
spindle
IEC 60383-1/
ANSI/BS/ASTM
105-120 kV
270-320 mm
Ceramic
Brown
Yes
16 -400 V Porcelain Shackle Insulators
#
Description:
UNDP specifications
1
Make/brand / Model
2
Name of manufacturer
3
4
Country of origin
Reference standard
5
Ambient temperature :
Maximum:55 deg C
Minimum:-10 deg C
6
Relative Humidity :
92% maximum
7
Altitude
1000 M above mean sea
level
8
Rated voltage
400 V
9
System highest voltage
600 V
10
Power frequency withstand voltage- dry
≥ 23 KV
11
Power frequency withstand voltage – wet ≥ 10 KV
12
Puncture voltage
1.3 x actual dry F.O.V
13
Electro mechanical strength
15-16 KN
14
15
Material of insulator
Color of insulator
Ceramic
Brown
16
Radius of conductor groove
15 mm
17
Total height
65-100 mm
18
Total diameter
75-115 mm
19
Net Weight
0.6-1 Kg
20
Submit Manufacturer certification
21
Submit type test certificates or reports
22
Submit Detail drawings, brochures
and catalogues of insulator and
spindle
BS or equivalent standard
Offered specification
17 – L V line taps (Al-Cu)
#
Description:
UNDP specifications
1
Make/brand / Model
2
Name of manufacturer
3
4
Country of origin
Reference standard
5
Ambient temperature :
Maximum:55 deg C
Minimum:-10 deg C
6
Relative Humidity :
92% maximum
7
Altitude
1000 M above mean sea
level
8
Rated voltage
400 V
9
System highest voltage
600 V
10
Applicable main conductor Size
35 mm2- 120 mm2
11
12
13
14
15
16
17
18
Applicable tap conductor
size
Length of the
Clamp
Temperature
rise
Whether the applicable conductor sizes
are marked on the
clamp
Bolt
a) Size & Length of the bolt
b) Thread length
c) Tensile strength of the bolt
d)
Property
Yes/No
Class
Submit
Manufacturer certification
Submit type test certificates or reports
b)
are marked on the
clamp
Submit brochures and catalogues
Thread
length
Yes/No
mm
25 mm2- 95 mm2
deg C
Yes/No
mm / mm
mm
N/mm²
Offered specification
18 – L V line taps (Al-Al)
#
Description:
UNDP specifications
1
Make/brand / Model
2
Name of manufacturer
3
4
Country of origin
Reference standard
5
Ambient temperature :
Maximum:55 deg C
Minimum:-10 deg C
6
Relative Humidity :
92% maximum
7
Altitude
1000 M above mean sea
level
8
Rated voltage
400 V
9
System highest voltage
600 V
10
Applicable main conductor Size
35 mm2- 120 mm2
11
12
13
14
15
16
17
18
Applicable tap conductor
size
Length of the
Clamp
Temperature
rise
Whether the applicable conductor sizes
are marked on the
clamp
Bolt
a) Size & Length of the bolt
b) Thread length
c) Tensile strength of the bolt
d)
Property
Yes/No
Class
Submit
Manufacturer certification
Submit type test certificates or reports
b)
are marked on the
clamp
Submit brochures and catalogues
Thread
length
Yes/No
mm
-
35 mm2- 120 mm2
deg C
Yes/No
mm / mm
mm
N/mm²
Offered specification
19 – Cable Lugs- 150 mm2 Cu cable
#
Description:
UNDP specifications
1
Make/brand / Model
2
Name of manufacturer
3
4
Country of origin
Reference standard
5
Current carrying capacity
A
6
Temperature rise at rated current
Deg C
7
Marking details- Cable size and No. of
crimps
8
Submit Manufacturer certification
9
Submit type test certificates or reports
10
Submit brochures and catalogues
150 mm2 /…
Offered specification
20 – Cable Lugs- 120 mm2 Cu cable
#
Description:
UNDP specifications
1
Make/brand / Model
2
Name of manufacturer
3
4
Country of origin
Reference standard
5
Current carrying capacity
A
6
Temperature rise at rated current
Deg C
7
Marking details- Cable size and No. of
crimps
8
Submit Manufacturer certification
9
Submit type test certificates or reports
10
Submit brochures and catalogues
120 mm2 /…
Offered specification
21 – Cable Lugs- 50 mm2 Cu cable
#
Description:
UNDP specifications
1
Make/brand / Model
2
Name of manufacturer
3
4
Country of origin
Reference standard
5
Current carrying capacity
A
6
Temperature rise at rated current
Deg C
7
Marking details- Cable size and No. of
crimps
8
Submit Manufacturer certification
9
Submit type test certificates or reports
10
Submit brochures and catalogues
50 mm2 /…
Offered specification
22-& 23– 11 kV Expulsion Fuse Cutouts
No
Description
123-
Make/Brand/Model:
Name of manufacturer
Type :
4-
Country of origin
5-
Reference standard
6-
Ambient temperature :
7-
Relative Humidity :
8-
Altitude
9101112
1314
Rated Voltage :
Rated frequency
Short circuit current
Rated continuous current
Mounting Angle to the vertical
Rated insulation level –to earth
a) Impulse withstand voltage (peak)
b) One minute 50Hz withstand
voltage (r.m.s.)
Rated insulation level – across isolating
distance
a) Impulse withstand voltage (peak)
15
16
IEC 60282, IEC 60071,
IEC 60071, IEC 60273
Maximum:55 deg C
Minimum:-10 deg C
92% maximum
1000 M above mean sea
level
11 KV
50 Hz
25 kA
100 A
15-20 Deg
75 kV
28 kV
85 kV
32 kV
Conductor terminals tin plated
Required
18
Contracts silver clad
19
Temperature rise tests
1
11 kV Expulsion Fuse
Cutouts
b) One minute 50Hz withstand voltage
(r.m.s.)
Size and Material of
i)
Upper Terminal Clamps
ii)
Lower Terminal Clamps
iii)
Moving Contacts
iv)
Fixed Contacts
17
11 KV
UNDP required
specifications
Ambient temperature during
temperature rise
Size/ Copper, copper alloy
Size/ Copper, copper alloy
Size/ Copper, copper alloy
Size/ Copper, copper alloy
Required
Offered
specification
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
2
Temperature rise for Contacts
1) Upper ºC
2) Lower ºC
3
Temperature rise for terminals ºC
1) Upper ºC
2) Lower ºC
Symmetrical / Asymmetrical (rms)
8 KA /…. KA
interrupting rating
Material of insulator
Porcelain
Color of insulator
Glazed brown or grey
Creepage distance
mm
Type of Mounting Bracket
Fuse cut-out with single or stand-off
Required
insulator NEMA brackets
Cut out suitable for removable button
Required
head fuse link
All assemblies potted into the porcelain
Required
Shed to be incorporated into upper
Required
contract assembly
Load break hook fitting
Required
Arc interrupting assisted by a spring
Required
operated flipper
The protection of fuse link from
mechanical shock by latching of toggle
Required
mechanism
Non expandable type fuse cap
Required
Galvanizing thickness of all ferrous
components
Submit Manufacturer certification :
Submit Detail drawings, brochures and catalogues:
Submit certification or report of type tests
22 & 23- Expulsion Fuse links for 11 kV
No
Description
123-
Make/Brand/Model:
Name of manufacturer
Type :
4-
Country of origin
5-
Reference standard
11 KV
UNDP required
specifications
Expulsion Fuse links
for 11 kV
IEC60 282-2
Offered specification
678-
Ambient temperature :
Maximum:55 deg C
Minimum:-10 deg C
Relative Humidity :
92% maximum
Altitude
9101112
13-
Rated Voltage :
Rated frequency
Rated continuous current
Diameter of Button Head Cap
Material of Button head cap
14
Diameter of removable washer
15
Material of button head cap
16
Material of current responsive element
17
Does the current responsive fuse element
enclosed with an insulating sleeve having
arc extinguishing properties
1819
20
21
Material of insulating sleeve enclosure
Diameter of flexible conductor
Material of flexible conductor
Whether the flexible conductor is tinned
type
Overall length of the fuse link
Tensile withstand strength
Whether the following information
indelibly marked on the fuse link
22
23
24
25
1000 M above mean
sea level
11 KV
50 Hz
20 A, 40 A
mm
Yes/No
mm
Yes/No
mm
kg
Rated continuous current
Yes/No
Type (Fast “K” – Slow “T”)
Yes/No
Manufacturers identification code
Yes/No
Whether the following information
indelibly marked on the sealed polythene
cover of the fuse link.
Rated Voltage
Yes/No
Rated continuous current
Yes/No
Type (Fast ‘K’ / Slow ‘T’)
Yes/No
Manufacturer’s identification code
Yes/No
26
27
28
29
Melting Time/Current characteristics
a)
For fuses of all current rating
b)
At what ambient temperature
Yes/No
Submit Manufacturer certification :
Submit Detail drawings, brochures and catalogues:
Submit certification or report of type tests