Download Inrush Current in a Transformer

Survey
yes no Was this document useful for you?
   Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project

Document related concepts
no text concepts found
Transcript
1
REDUCTION OF THE INRUSH CURRENT IN ELECTRICAL
2
TRANSFORMER USING VOLTAGE DOWN-CHIRP
3
TECHNIQUE
4
Somkid Suttisak* and Teerapong Chimphet
5
6
7
Department of Electrical Engineering, Faculty of Engineering,
8
Rajamangala University of Technology Srivijaya, Muang Songkhla, 90000, Thailand
9
* Corresponding author, e-mail: [email protected]
10
11
Abstract
12
This study aims to examine the reduction of the inrush current on a single phase
13
transformer when there is no power transmission by using a voltage Down-Chirp
14
technique. The transformer is initially pressured with a frequency higher than the
15
frequency range. Then, such frequencies are downgraded in an equal to the frequency
16
range of the transformer in a short span of time, resulting in the reduced size of the
17
magnetic flux on the magnetic axis and line of the transformer. The design of the
18
process and simulation are relying on MATLB SIMULINK software. The results of
19
stimulation of the 1 2 0 0 VA transformer showed that the inrush current reduced when
20
the default frequency of the voltage is equal to 90Hz.
21
22
Keywords: inrush current, transformer, Down-chirp techniques.
2
23
Introduction
24
Inrush current in a transformer has a higher rated electrical currents, and the voltage is
25
asymmetric, resulting from the instantaneous electricity distribution to the transformer which
26
cause a momentary electric current with the increased amplitude values up to 10 times of the
27
current primary coil of the transformer with no power transmission. [1] An occurrence of the
28
inrush current of a transformer in transmission lines, distribution systems, or coordinate low
29
voltage transformer is an important concern for a protective device as a protective equipment
30
may view the exceeded as the short circuit current and may cause the circuit breaker of
31
transformer.
32
transformer coils as well.
33
Reviewing such existing issues, the researcher conducted this study to provide ways to reduce
34
the amount of inrush current occurring on the transformer by employing the Down-Chirp
35
method with the voltage of the supply to reduce the amount of excess flow. The results of the
36
study provide guidelines for further development of the inrush current reduction.
The frequent occurrence of the inrush current may directly damage the
37
38
Notations
39
v (t ) : Transformer supplied voltage
40
Vmax : Maximum voltage of supply
41
max : Maximum magnetic flux
42
N P : Turns of wiring
43
 : Angular frequency
44
f: Ordinary frequency
45
3
46
Inrush Current in a Transformer [2]
47
The connection between the transformer and the supply result in a momentary overload
48
currents or inrush current in the primary circuit that is higher than the rated current because of
49
the change of the magnetic flux on transformer cores. The current quantity depends on the
50
form of the coil, transformer size, the structure of the axis, the residual magnetic flux on
51
transformer cores, and the phase sequence of the supply. The characteristic pattern of the
52
inrush current of the transformer is presented in Figure 1.
53
The change of the magnetic flux on transformers according to the phaser of supply affecting
54
the amount of the inrush current can be explained in Figure 2, which shows the direction of
55
the magnetic flux occurring on the axis of the transformer when the transformer has the
56
maximum voltage. It was determined from the following equations
57
v(t )  Vm sin( t   ) V
58
The maximum flux height reached on the first half-cycle of the applied voltage depends on
59
the phase of the voltage at the time the voltage is applied. If the initial voltage is
60
v(t )  VM sin( t  90 )  VM cos  t V
61
and if the initial flux in the core is zero, then the maximum flux during the first half-cycle
62
will just equal the maximum flux at steady state, that is
max 
63
Vmax
N p
(1)
(2)
(3)
64
This flux level is just the steady-state flux, so it causes no special problem. However, if the
65
applied voltage happens to be
66
v(t )  VM sin  t V
(4)
4
67
the maximum flux during the first half-cycle is given by
 /
68
1
NP
69
Integrating gives
 (t ) 
max 
70

0
VM sin  t dt
2Vmax
 NP
(5)
71
This maximum flux is twice as high as the normal steady-state flux in the core and results in
72
an enormous magnetization current that look like a short circuit, and a very large current
73
flows, that shown in Figure 1.
74
Equation (1) to (5) represent the factors that affect the magnetic flux values occurring on the
75
transformer while receiving voltage. The phaser position of the supply is significant and
76
directly affect the quantity of magnetic flux. The changes of flux values result in the
77
relationship between the magnetic flux with the magnetomotive force (mmf) by considering
78
from the transformer magnetization curve. If the magnetization curve of the transformer
79
increased, the inrush current will increase correspondingly. Therefore, if the quantity of
80
magnetic flux is controlled and reduced, the amount of the inrush current on the transformer
81
can be controlled and reduced as well.
82
83
The Reduction of the Inrush Current in Electrical Transformer
84
An effective way to reduce or limit the inrush current in electrical transformer while it is
85
running with power is to control the quantity of magnetic flux on the transformer axis so that
86
the value has decreased. The equation 4 presents a variable that defines the quantity of
87
magnetic flux such as the maximum voltage of the supply (Vmax ) number of the cycle of the
88
transformer’s coils ( N P ) , and the angular frequencies  . This research, therefore, focuses
5
89
and places an attention on the way to reduce or limit the inrush current from the supply
90
frequency   2 f to change the performance of the angular frequency and the values of the
91
magnetic flux.
92
Changing the frequency of the supply to a value higher than the frequency range while there
93
is the electrical power in the transformer causes the magnetic flux values to decrease due to
94
the increase of the angular frequency  . As a result, the magnetization curve of the
95
transformer gets smaller. The values of inrush current are a direct variable in the change of
96
magnetization curve. Characteristics of the changes of magnetization curve and the
97
magnetization current according to the frequency of the supply are presented in Figure 3.
98
99
Figure 3(a) demonstrates the change of the magnetic flux in the transformer when
100
transformer’s coils receive the voltage with different frequency values. It can be noted that if
101
the frequency of the supply has a higher value, the quantity of magnetic flux is reduced,
102
resulting in the changes of the magnetization curve of the transformer. In addition, the
103
saturation of the transformer core occurs quickly as shown in Figure 3(b). The performance
104
of the magnetization current of a normal frequency is different from the sine signal. However,
105
when the transformers get a higher frequency value, the magnetization current changes its
106
shape and becomes similar to a sine signal as shown in Figure 3(c). From this process, it can
107
be explained that to increase the frequency of the voltage until it is higher than the frequency
108
range of a transformer is a method that can be used to reduce the amount of the inrush current
109
in the transformer.
110
111
Down-Chirp Technique [3]
112
The Down-Chirp of the supply voltage to reduce the inrush current in a transformer refers
113
to the change in the frequency of the voltage supplied to the transformer from high frequency
6
114
to a frequency range. That is, a transformer starts working with the high-frequency value
115
voltage for a while before turning back to operate with a frequency range. The pattern of
116
voltage supply with the adaptive Down-Chirp model is shown in Figure 4, which presents the
117
voltage supplied to the transformer. The frequency of a signal is changed in form of a linear
118
equation as shown in the equation
119
f f 
f (t )  f 0   1 0  t
 f1 
(6)
120
When the default frequency is f 0 , f1 is the last frequency. It was observed that the frequency
121
of the voltage supplied to the transformer had a high value at the beginning, resulted in the
122
saturation of the magnetic flux and reduction of the inrush current in the transformer.
123
124
Operational Testing
125
In testing the inrush current, this research study simulated the operation using MATLB
126
software. The coordinated information and important characteristics of the transformer used
127
in the test are presented in Table 1 , the performance of the inrush current in the 1200VA
128
50Hz can be tested and simulated as shown in Figure 5, which shows the comparison of the
129
simulation results obtained from the MATLB SIMULINK software with inrush current
130
values which were actually measured from oscilloscopes. It was found that the values of
131
inrush current were approximately ten times greater than the normal currents in the
132
transformer. Afterwards, the circuit was designed to reduce the values of inrush current by
133
Down-Chirp the supply voltage. The simulation of the circuit is shown in Figure 6.
134
135
Results
136
In the simulation of the initial configuration, the default frequency and the transformer’s
137
value of the frequency range of the Chirp Signal are controlled by comparing results from the
7
138
default frequency value of four samples: 60Hz, 70Hz, 80 Hz, and 90Hz respectively. The
139
results of the experiment determine the performance of the inrush current in the transformer
140
as presented in Figure 7, its shows that the supply’s default frequency of 60 Hz, 70Hz, 80Hz,
141
and 90Hz can reduce excess flow down to 3.25A, 2.7A, 2.4A, and 1.85A respectively. This
142
research study suggests that the amount of excess currents can be reduced up to 50 percent of
143
the actual inrush current which were measured.
144
145
8. Conclusion
146
Down-Chirp the frequency of the supply is a method that can be effectively used to reduce
147
the inrush current of the transformer. The quantity of the inrush current depends on the
148
default frequency of the voltage supplied to the transformer. Practically, in using such
149
technique, the operation of an equipment which has the capability to control the frequency of
150
voltage and the ability to modify the default frequency value with the transformer.
151
152
References
153
Taylor D. I., Law J. D., Johnson B. K. and Fischer N. "Single-phase transformer inrush
154
current reduction using prefluxing," IEEE Transactions on Power Delivery, Vol. 27,
155
No. 1, January 2012, pp. 245-252.
156
157
158
159
S. J.Chapman, Electric Machinery Fundamentals, 4th
ed., New York:McGraw-Hill,
2004,pp.65-151.
Weisstein, Eric W. "Sweep Signal." From MathWorld-A Wolfram Web Resource.
http://mathworld.wolfram.com/SweepSignal.html, Jan.6,2015[Jan.10,2015].
160
S. G. Abdulsalam, Wilson Xu, W. L. A. Neves, and X. Liu, "Estimation of Transformer
161
saturation characteristics from inrush currents waveforms," IEEE Trans. On Power
162
Delivery, Vol. 21, No.1, pp. 170-177, Jan. 2006.
8
163
V.Molcrette, J.-L. Kotny , J.-P. Swan and J.-F. Brudny "Reduction of inrush current in single-
164
phase transformer using virtual air gap technique", IEEE Trans. Magn., vol. 34, no.
165
4, pp.1192 -1194 1998.
166
Yu-Hsing Chen and Po-Tai Cheng, "An inrush current mitigation technique for the line-
167
interactive uninterruptible power supply systems," IEEE Trans. on Industrial
168
Applications, vol. 46, no.4, July/August 2010.
169
170
R. A. Turner and K. S. Smith "Transformer inrush currents", IEEE Ind. Appl. Mag., vol.
16, no. 5, pp.14 -19 2010.
171
N. Chiesa and H. K. Hoidalen "Novel approach for reducing transformer inrush currents:
172
Laboratory measurements, analytical interpretation and simulation studies", IEEE
173
Trans. Power Del., vol. 25, no. 4, pp.2609 -2616 2010.
174
175
176
177
178
179
180
181
182
183
9
184
185
186
187
188
189
190
191
192
193
194
195
196
197
198
199
200
201
202
203
204
205
206
[1]
Figure 1: The inrush current in the transformer.
10
v (t)  (t)
t
207
208
209
210
211
212
213
214
215
216
217
218
219
220
221
222
223
224
225
226
Figure 2: The phaser voltage and magnetic flux of the transformer.
11
 ,Wb
 ,Wb
f1 =50Hz
f2 =60Hz
f3 =70Hz
f1
f2
mmf
A.turns
f3
im
(a)
(b)
f2
f1
f3
t
227
(c)
228
Figure 3 (a) Magnetic flux on transformer cores. (b) magnetization curve.
229
(c) magnetization Current.
230
231
232
233
234
235
236
237
238
239
240
241
242
243
244
Voltage
12
245
Time
246
Figure 4: The voltage resulted from the adjustable frequency value with
247
the Down-Chirp method.
248
249
250
251
252
253
254
255
256
257
258
259
260
261
262
263
264
265
13
266
267
268
269
270
271
272
273
274
275
276
277
278
279
280
281
282
283
284
285
286
287
Table 1. Parameters of the 1200VA 50Hz transformer.
Parameter
Voltage(V)
Normal
Current (A)
R(ohm)
L(H)
LV winding
115
0.35
8.27
0.148
HV winding
230
0.17
14.9
0.41
14
4
Current (A)
3
2
1
0
-1
0
0.05
0.1
0.15
0.2
0.25
0.3
0.35
0.4
0.45
0.5
Time (s)
(a)
3.76A
288
(b)
289
Figure 5: Inrush Current: (a) results of the MATLAB simulation
290
(b) results from the actual measurement.
291
292
293
294
295
296
297
298
299
300
301
302
303
15
304
305
306
307
308
309
Figure 6: Circuit simulation of reducing inrush current by Down-Chirp supply voltage.
16
Initial frequency = 60 Hz
4
3.5
3
2.5
Current (A)
2
1.5
1
0.5
0
-0.5
-1
0
0.05
0.1
0.15
0.2
0.25
0.3
0.35
0.4
0.45
0.5
0.3
0.35
0.4
0.45
0.5
0.3
0.35
0.4
0.45
0.5
0.3
0.35
0.4
0.45
0.5
Time (s)
Initial frequency = 70 Hz
4
3.5
3
2.5
Current (A)
2
1.5
1
0.5
0
-0.5
-1
0
0.05
0.1
0.15
0.2
0.25
Time (s)
Initial frequency = 80 Hz
4
3.5
3
Current (A)
2.5
2
1.5
1
0.5
0
-0.5
-1
0
0.05
0.1
0.15
0.2
0.25
Time (s)
Initial frequency= 90 Hz
4
3.5
3
Current (A)
2.5
2
1.5
1
0.5
0
-0.5
-1
310
0
0.05
0.1
0.15
0.2
0.25
Time (s)
311
Figure 7: The result of inrush current reduction in the power transformer using voltage
312
Down-Chirp technique.
313
Related documents