Download Voltage Distribution Along Surge Arresters Under

Survey
yes no Was this document useful for you?
   Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Document related concepts

Capacitor wikipedia , lookup

Ground loop (electricity) wikipedia , lookup

Decibel wikipedia , lookup

Pulse-width modulation wikipedia , lookup

Stepper motor wikipedia , lookup

Power inverter wikipedia , lookup

Power engineering wikipedia , lookup

Ground (electricity) wikipedia , lookup

Variable-frequency drive wikipedia , lookup

Electrical ballast wikipedia , lookup

Islanding wikipedia , lookup

Integrating ADC wikipedia , lookup

Three-phase electric power wikipedia , lookup

Pโ€“n diode wikipedia , lookup

Metadyne wikipedia , lookup

Ignition system wikipedia , lookup

Rectifier wikipedia , lookup

History of electric power transmission wikipedia , lookup

Power electronics wikipedia , lookup

Current source wikipedia , lookup

Ohm's law wikipedia , lookup

Schmitt trigger wikipedia , lookup

Resistive opto-isolator wikipedia , lookup

Triode wikipedia , lookup

Electrical substation wikipedia , lookup

Switched-mode power supply wikipedia , lookup

Buck converter wikipedia , lookup

Distribution management system wikipedia , lookup

Opto-isolator wikipedia , lookup

Voltage regulator wikipedia , lookup

Alternating current wikipedia , lookup

Voltage optimisation wikipedia , lookup

Stray voltage wikipedia , lookup

Spark-gap transmitter wikipedia , lookup

Surge protector wikipedia , lookup

Mains electricity wikipedia , lookup

Transcript
Voltage Distribution Along Surge
Arresters Under Influence of
Temperature
CHRISTOPH HIPPLER
KARSTEN LAUE
Voltage distribution along surge arresters under
influence of temperature
Christoph Hippler1
Karsten Laue2
1
Technische Universität Ilmenau, Inter-departmental Center for Energy Technologies, Research Unit HighVoltage Technologies, Germany
2
TRIDELTA Meidensha GmbH, Head of Development, Germany
Abstract
The design of high voltage surge arresters is a challenging assignment, due to
the fact, that, in praxis the voltage and temperature over a metal-oxide varistor
block (MO-block) of a surge arrester may be stressed differently from MO-block
to MO-block. This voltage and temperature stress depends on the installation
place, distribution of MO-blocks inside the arrester or the operation voltage.
Therefore, it is favourable to measure both the voltage distribution and the
temperature distribution. The selection of an appropriate measurement method is
limited, in order to the fact, that the chosen method shall minimal influence the
voltage or temperature distribution. Thus, the aim of this contribution is to present
one possibility to measure the non-linear voltage distribution by using one sphere
spark gap. Simultaneously the temperature distribution is recorded during all
measurements. Preliminary measurements as well as simulations are realised in
order to show the feasibility of using a spark gaps in the kind of application. After
all, the designed spark gap is used to show the various voltage stress over each
MO-block at two different surge arrester configurations as well as different
temperatures. All FEM simulations and analytical calculations are verified by
voltage measurements.
1
Introduction
MO-surge arrester are established as an efficient, economical and reliable form for the
overvoltage protection against slow- and fast front surges in electrical transmission systems.
This objective can only be achieved when the high voltage surge arrester will not be
overstressed due to a large non-linear voltage- and temperature distribution. The emergence
of such higher voltage or temperature stresses is different and generally upper MO-blocks
are more affected. The cause of higher voltage stress are the stray capacitances to ground
and to high voltage potential which determine the axial voltage distribution along the surge
arrester by applying a continuously rated alternating voltage. Additionally, the particular
temperature of each MO-block has also to consider as an important factor for the voltage
distribution. In order to ensure a reliable operation of surge arresters, large safety factors are
settled by manufactures in order to prevent the risk of overstressing. In recent years an
increasing demand and by the wide application range of arresters have shown the need for a
combined determination of the voltage- and temperature distribution along the MO-column.
There are different possibilities available to measure the voltage distribution, but the chosen
measurement method shall minimal interact with the test object. Hence, air sphere spark
gaps are precise, easy to implement devices, used to measure reliable the peak voltage
1/15
above 3 kV with frequencies up to 500 Hz and the influence of the potential field distribution
is low due to the small size.
This work addresses the usage of one spark gap in parallel to one MO-block as a sensitive
measurement method for the determination of the voltage distribution. The spark gap
spacing set is permanently constant to a specific gap which keeps constant during all
measurements. Then the spark is mounted to the MO-block. When the spark gap ignites, the
peak voltage at the terminal of the arrester is repetitive detected and reporting. Afterwards,
the spheres are cleaned up and the contemporary position of spark gap is chanced to the
next MO-block. This procedure is repeated for all MO-blocks. The determination of the
percentage portion of each MO-block is calculated and shows the voltage distribution along
the surge arrester.
The measurement results are used to indicate possible weaknesses during the design of
surge arrester and utilised to verify or improve surge arrester models. These models are
deployed to calculate the potential- and temperature distribution in advance (before type
tests begin).
The aim of this paper is to show the voltage and temperature distribution at two different
surge arrester configurations under ambient and increased temperature. Both voltage
distributions are calculated and measured by an applied alternating 50 Hz voltage. Further,
both surge arrester configurations are built without ceramic housing to simplify the
measurements. The axial temperature distribution is measured by using fibre optical
temperature sensors between each MO-block.
2
Preliminary considerations - Measurement by Spark gap
It is expected that the operation and the performance of the spark gap is slightly different by
connecting a MO-block in parallel to the spark gap, due to the chanced surrounding and
inner electrical field distribution. Hence, several preliminary measurements and calculations
with and without MO-block parallel to the spark gap are realised to verify this measurement
method.
2.1
Test circuit
The used test circuit arrangement is shown in Figure 1. The operating voltage form is
configured as a variable voltage by an AC source which it connected to the high voltage
transformer and in serial to the test object. Between both, source and test object, a high
voltage resistor (330 kOhm) is connected in serial to limit the short circuit current.
The voltage measurement is achieved by using a conventional high voltage probe with a
voltage ratio of 1000:1 and a sufficient bandwidth of 100 MHz. The current measurement in
the spark-gap/MOV branch is achieved by using a current transformer with a sensitivity of
0.1Volt/Ampere and a high 3 dB cut-off frequency of 20 MHz.
2/15
Figure 1: Measurement circuit; VT: variable voltage source; HVT: high voltage
transformer; R1: high voltage resistor; CSG: spark-gap; MO-block: Metal-OxideVaristor block; CT: current transformer; VD: voltage probe.
2.2
Comparison of breakdown voltage characteristic of spark gap โ€“ with and without
MO-block in parallel
The diameter, the gap spacing, the atmospheric conditions, the material and the surface
condition of a spark gap are decisive factors for the measurement of the breakdown voltage.
Furthermore, the electrical strength of gases is also a function of the duration of voltage
stress, the applied voltage form as well as the velocity of voltage rise. After several attempts,
it has been found, that the standard deviation is smallest when the velocity voltage rise is
constant increased with 1 kV per second in each 50 Hz period, during the tests.
In Figure 2 is the preliminary measurement circuit shown. The distance (d) between the
spark gap and the parallel MO-block is studied to clarify the influence of this parallel circuit. It
is known, that any extraneous objects, such as walls or supporting frameworks influence the
breakdown characteristic as well as the homogeneity of the electrical field of the spark gap.
Hence, measurements are realised to consider if any deviation of the breakdown voltage
characteristic occurs. Tests on various spark gap spacing distances (s), with and without
MO-block in parallel, have been carried out to determine the breakdown voltage
characteristic. Figure 2A depicts the spark gap with the insulating support (1) which is used
to adjust the spacing between the spark gap for the measurements without MO-block. In
Figure 2B the MO-block and spark gap are mounted between two rounded brass electrodes
(2, 3) and the parameter (d and s) are varied during the test procedure. The diameter of the
brass spheres are 12 mm and the surface of the spheres are polished and free from any
trace of varnish or grease before every test starts. The breakdown-voltage tests are realised
with at least 15 alternating voltage ignitions for each distance (parameter d and s).
All measurements are made during a period when the atmospheric conditions (temperature,
pressure, and humidity) in the high voltage laboratory are not constant. Hence, the
corrections factors for temperature, pressure and humidity are applied. Two quantities are
used to characterise the non-uniform electrical field between the spark gap. First, the
geometry factor (p) of the spark gap which results from the ratio: ๐‘ = (๐‘Ÿ + ๐‘ )/๐‘Ÿ, whereby ๐‘Ÿ is
radius of the sphere, ๐‘  the spark gap spacing. It results that p is in the range from 1.06 to
1.16 for a spacing (s) from 0.6 mm to 1.6 mm. The second quantity is the utilisation factor ๐œ‚
(Schwaiger factor) which requires the geometry factor to readout ๐œ‚ from diagrams. The
utilisation factor is in the range from 0.90, for the largest spacing, to 0.95 for the smallest
spacing.
3/15
Figure 2: Schematic representation of spark-gap, A: spark gap between insulating
support (1), B: spark-gap between two brass electrodes (2, 3) in parallel to MO-block.
The results of the breakdown voltage characteristic of the air spark gap for configuration B
(shown in Figure 2B) by variation distance parameter d and constant spacing s = 1 mm is
shown in Figure 3. For this measurement, the gap (s) between the spark gap is held
constant at 1 mm and the parameter (d) between the shell surface of MO-block and the
vertical axis of the spark gap is varied between 13 mm to 52 mm. As can be seen form
Figure 3, that the breakdown voltage characteristic is approximately constant for all four
distances with around 5.3 kV. The standard deviation is further illustrated in Figure 3 - shows
that the smallest standard deviation can be reached by 13 mm and increases slightly with the
distance (d). Nevertheless, the parameter (d) with a value of 39 mm is laid down for the next
measurements due to the small difference between the breakdown voltages and can be
easily implemented in a construction. The sphere gap spacing is adjustable but the brass
electrodes (2, 3) permanent fixed through the insulating support. The designed and mounted
spark gap is shown in Figure 5.
Figure 3: Breakdown voltage as function of distance
between spark gap axis and MO-block, constant spark
gap spacing s = 1 mm, number standard deviation above
curve, mean value below curve.
4/15
Figure 4 shows the results of the measured breakdown voltage characteristic of the spark
gap as a function of the gap spacing with and without MO-block as well as the calculated
curve. For the calculation of the breakdown voltage curve, Ub is given in equation 1 where A,
B = experimentally determined gas constant, p = pressure, s = gap spacing and ฮณ = material
and gas type coefficient [1].
๐‘ˆ๐‘ =
๐ตโˆ™๐‘โˆ™๐‘ 
๐ดโˆ™๐‘โˆ™๐‘ 
ln (
)
ln(1 + 1/๐›พ)
(1)
In this contribution, the parameters are chosen as follows: A = 1130 [1/(mm*bar)],
B = 27.4 [kV/(mm*bar)] and ๐›พ for copper with 0.025. Further, the calculated breakdown
voltages are converted to the case normal conditions for a better comparability.
As expected, the measured breakdown voltage values are proportional to the gap spacing for
both configurations (with and without MO-block in parallel). Furthermore, Figure 4 illustrates
also, that the breakdown voltages of spark gap in parallel with the MO-block is higher for
small gap spacing distances (< 1.2 mm) and the curves get closer for higher gap spacing
distances (> 1.4 mm). The standard deviation is also illustrated in Figure 4 and shows that
the standard deviation for the spark gap with MO-block is slightly higher than without the MOblock in parallel. Both, the variation between the breakdown curves and the standard
deviations can be attributed to the change in the electrical field distribution and by
measurement uncertainties.
Figure 4: Breakdown voltage characteristic of spark gap
(SG) โ€“ with (red curve) and without (blue curve) MO-block
in parallel and calculated breakdown voltage curve (black)
for d = 39 mm.
2.3
Calculation electrical field distribution of Spark gap with and without in parallel
to MO-blocks
A column of five MO-blocks with and without mounted spark gap is numerically designed and
the electrical field is calculated by using COMSOL finite element package for the time
depending analysing. The permittivity is provided as a constant value and the conductivity of
the metal-oxide is assumed to be non-linear curve. The material parameters are known from
5/15
measurements. The illustration of the named MO-column with spark gap is illustrated in
Figure 5. Moreover, the figure shows the geometry of the MO-block with a height of 45 mm
and diameter of 64 mm, also the varied parameter d and s are shown. The spark gap is
mounted at MO-block Nr. 3 (middle) and spark gap position is not modified for all calculation.
The only variable that is changed during the FEM calculation is the parameter d. The
operation high voltage is selected by a peak voltage of 25 kV with a frequency of 50 Hz,
which was adopted that the maximum voltage between both spheres is roughly 5 kVpeak
before the ignition starts. This is chosen, because to be become assured, that, the electric
field stress is under the self-breakdown voltage of the spark gap.
Figure 5: Left side: MO-block column with mounted spark gap, HV: high voltage potential, GND: ground potential;
right side: selected area show electrical field distribution (normalized to 0.5 kV/mm).
The distribution of the electric potential in and surrounding the MO-column can be found from
Maxwell´s equations based on the non-linear material parameter โ€“ conductivity and the
assumed constant permittivity. In all calculations, the non-linear voltage depending
conductivity is stored as a lock-up table in COMSOL. The ambient medium is air with open
boundaries, set as Neumann criterion.
6/15
To get an exact description how the potential or rather the electrical field strength is changed
through the MO-column by variation of spark gap arrangement, the following distinctions are
made:
๏‚ท
๏‚ท
๏‚ท
without spark gap (referred as line 1)
with spark gap and parameter d set by 13 mm (referred as line 2)
with spark gap and parameter d set by 39 mm (referred as line 3)
The results are shown in Figure 6 for all three lines which represent the electrical field
strength along the vertical axis of the MO-column, see also the yellow line in Figure 5 left
side. As expected, it was found that the difference of the electrical field strength through the
MO-column is negligible small for all three lines, as it shown in the magnified Figure 6. The
figure shows small negligible variations between each line. However, the electrical field
distribution is more homogeneous by mounting a spark gap. One of the observations derived
from the computational results is that the electrical field distribution inside the MO-column is,
overall, not effected by the spark gap as well as distance between the MO-block and the
spark gap. The result of the field distribution by using a 2D cut-surface for the case with
mounted spark gap is shown in Figure 5, right side. The maximum electrical field strength is
normalized to 0.5 kV/mm.
Figure 6: Electrical field strength inside the MOcolumn, peak voltage 25 kV.
As an intermediate result, the measurements and FEM-calculations show that it is possible to
use a sphere spark gap for the measurement of the voltage distribution under consideration
of the correction factors. The measurement errors by using a spark gap are very small and
the chosen distance between the MO-block and the spark gap has no further impact of the
breakdown voltage characteristic or the electrical field distribution inside the MO-block.
7/15
3
3.1
Measurement of the voltage and temperature distribution
Experimental arrangement
The experimental arrangement of the surge arrester configuration I and II is shown in Figure
7 and Figure 8. Both surge arresters are built up of 22 MO-block, without porcelain insulator,
between each block an aluminium sheet is inserted and the arrester is installed on a pedestal
of 0.5 m height. The blue arrows indicate the temperature measuring points which are
positioned in holes into the aluminium sheet or - spacer.
Configuration I
Configuration II
Figure 7: Surge arrester configuration I, black
numbers are MO-block, blue indicates temperature
sensor.
Figure 8: Surge arrester configuration II, black
numbers are MO-block, blue indicates temperature
sensor.
3.2
Test procedure
The measurement circuit is shown in Figure 9. The single phase alternating voltage source
contains of an isolated transformer, a variable voltage and frequency source to set the
voltage and frequency at the high voltage transformer. The measurement coil at the high
voltage transformer is used to measure the high voltage potential at the surge arrester
terminal (VHS). The current measurement in the surge arrester branch for the detection of the
8/15
impulse is achieved by using a current transformer (same CT as above mentioned). The
connection of a high voltage resistor in serial to limit the short circuit current is not necessary,
due to the high resistance of the remaining MO-blocks.
In this test procedure, the spark gap spacing is always set to 1 mm to fulfil the breakdown
voltage of around 5 kVpeak which is a bit lower than the continuous operating voltage of the
used MO-block. This implies that the measurement is performed in the range of leakage
current when the resistive current component is very small compared to the capacitive
current (dissipation factor < 0.1).
Figure 9: Measurement circuit; VT: variable voltage source; HVT: high
voltage transformer; MC: measurement coil; SG: spark-gap; MO-block:
Metal-Oxide-Varistor block; A: current transformer; DSO: digital stored
oscilloscope.
Measurement process, first, the spark gap including the provided isolated support is mounted
in the above presented measurement circuit (Figure 1 and Figure 2B) to determine the
contemporary voltage breakdown of the spark gap. Then, the spark gap is connected to the
surge arrester at the first position, compare with Figure 9 - SG1. Then, the voltage is
continuously increased until the spark gap ignites, the voltage is decreased until the sparks
extinguish, after 10 seconds the voltage is again increased until the spark ignites between
the gaps. This process is repeated with at least 15 ignitions. The voltage at the surge
arrester terminal (VHS), the contemporary determined breakdown voltage and the current is
reported for all measurements, independently from the polarity of the terminal voltage. These
measurements are summarized to a series. Afterwards, the average voltage value is
calculated and multiplied with the correction factor (due to different atmospheric conditions).
Simultaneously to the measurement of the voltage distribution, the temperature distribution is
reported. There are four optical temperature sensors in use to measure the temperature
between the MO-blocks with a measurement error of 0.5 K. The ambition is to record all
temperatures, thereby one sensor is permanent mounted at the warmest position, the
temperature is maintained constant, whereas the other sensors are located near the spark
gap.
9/15
3.3
Test results
When an air spark gap is connected in parallel with one MO-block from the column of the
surge arrester, the voltage distribution can be measured at different temperatures. The
results of the test measurements are shown in Figure 10 and Figure 11 for configuration I
and II at a temperature of 20°C and 60°C. The number of MO-blocks is specified, by which
the y-axis starts referencing the bottom MO-block. The voltage stress is expressed at a ratio
of measured voltage drop to mean voltage stress and is hold onto the x-axis. Both figures
show that bottom MO-blocks are exposed to a lower voltage than the head MO-blocks and
the voltage stress increases almost uniformly. There is a small measureable change in the
voltage distribution between 20°C and 60°C for both configurations. However, the biggest
variations are shown for the head, from MO-block number 14 of both configurations. For
case the surge arrester is warmed, the voltage distribution intends to a uniform distribution
which can be explained by an increase of the leakage current whereas the capacitive
currents (based on the stray capacitances) remains constant.
Figure 10: Measurement results of voltage distribution
by 20°C and 60°C for surge arrester configuration I
Figure 11: Measurement results of voltage distribution
by 20°C and 60°C for surge arrester configuration II
Completely in contrast is the temperature distribution of both configurations which is depicted
in Figure 12. As expected, it was found that the temperature hot spots are located in the
upper third section of both configurations and temperature of the top MO-block is lower due
to the cooling of the metal flange contact. The biggest deviation between both temperature
curves is, that, configuration II consist of long metal tube in the middle of the surge arrester
which leads to active cooling of the adjacent MO-blocks. It is likewise become clear that two
smaller metal tubes (as provided in configuration I) lead not to the same effect as a long
metal tube. Additionally, the temperature along configuration I is almost evenly distributed
only the first six and upper three MO-blocks are cooler. It must be mentioned that the
10/15
porcelain housing of the surge arrester did not exist and thus the head radiation as well as
the head conduction are changed.
Figure 12: Results of temperature measurement for
configuration I (green curve) and configuration II (orange
curve)
4
Calculation of the voltage distribution
The alternating voltage distribution of high voltage surge arrester at a voltage level under the
continuous voltage is not equal because of the capacitive characteristic of the MO-blocks
and the stray capacitances effect in the direction to the ground as well as to the high voltage
potential. This means, the non-uniform voltage distribution depends on height of the arrester
and also on the supply of the grading ring. However, this non-uniform voltage distribution of
the arrester can be calculated by using analytical approaches as well as numerical tools like
the finite element method (FEM). The analytical approaches are suitable as an easy and
initial calculation of the voltage distribution, provided that the arrangement of surge arrester
is two dimensional and has a cylindrical symmetry shape. Thereby, to calculate the voltage
drop ux analytical equations (2) can be used [3, 4]:
๏‚ฎ
by only taken stray capacitances to ground into account:
๐‘ข๐‘ฅ =
๏‚ฎ
๐‘ ๐‘–๐‘›โ„Ž(๐›พ๐‘’ โˆ™๐‘›)
๐‘ ๐‘–๐‘›โ„Ž(๐›พ๐‘’ โˆ™๐‘ง)
(2)
by taken stray capacitances to ground and to HV potential into account:
1
๐บ๐‘๐ท +๐ถ๐ป๐‘‰
๐‘ข๐‘ฅ = ๐ถ
๐‘ ๐‘–๐‘›โ„Ž(๐›พ โˆ™๐‘›)
โˆ™ (๐ถ๐บ๐‘๐ท โˆ™ ๐‘ ๐‘–๐‘›โ„Ž(๐›พ๐‘‘ โˆ™๐‘ง) + ๐ถ๐ป๐‘‰ โˆ™ (1 โˆ’
๐‘‘
๐‘ ๐‘–๐‘›โ„Ž(๐›พ๐‘‘ โˆ™(๐‘งโˆ’๐‘›))
๐‘ ๐‘–๐‘›โ„Ž(๐›พ๐‘‘ โˆ™๐‘ง)
))
(3)
11/15
๐‘˜ = 0โ€ฆ๐‘› + 1
Nodes
๐‘›
Number of MO-blocks
๐‘ˆ
๐‘ข๐‘ฅ = ๐‘ˆ ๐‘›
Ratio voltage drop of applied high voltage
๐ป๐‘‰
1
๐ถ
๐›พ๐‘’ = 2 โˆ™ ๐‘Ž๐‘Ÿ๐‘๐‘ ๐‘–๐‘›โ„Ž (2 โˆ™ โˆš๐ถ๐บ๐‘๐ท )
๐‘€๐‘‚๐‘‰
๐ถ๐บ๐‘๐ท +๐ถ๐ป๐‘‰
๐ถ๐‘€๐‘‚๐‘‰
Capacitance ratio of simple linkage calculation
๐›พ๐‘‘ = โˆš
Capacitance ratio of double linkage calculation
๐ถ๐บ๐‘๐ท
Capacitance to ground
๐ถ๐ป๐‘‰
Capacitance to high voltage potential
๐ถ๐‘€๐‘‚๐‘‰
Capacitance MO-block
๐‘ˆ๐ป๐‘‰
Applied high voltage
The voltage distribution of surge arresters by using the mentioned equations is deeply
depending on the stray capacitances. The first step is the determination of the stray
capacitance to ground and the following assumptions are made:
Coaxial cylinders (source [5]):
(4)
Surge arrester configuration I
Surge arrester configuration II
CGND
1.8 pF
6.4 pF
CHV
0.18 pF
0.64 pF
Table 1: Calculated stray capacitances.
In general, the analytical determination of the stray capacitances assumes that the electrical
field between two different potentials is homogenously which can be made, as first
approximation, for stray capacitances to ground. But, for the calculation of the stray
capacitances in the direction to high voltage potential it is advisable to divide the volume in
several smaller parts, due to the numerousness of calculation a numerical calculation is
recommended. In real applications, the stray capacitances to ground are generally bigger
than stray capacitances to high voltage potential [3]. It is assumed, that the stray
capacitances to ground are 10 times larger than the capacitances in direction of high voltage
potential. The results of the all non-uniform capacitive calculated voltage distribution are
shown in Figure 13.
Additionally, the axial voltage distribution of both configurations is numerically solved by
using a time depending solver for the 2D model which reflects the non-linear current-voltage
12/15
curve of the MO-block. The curves are illustrated in Figure 13-A and -B as a green trace and
compared in Figure 13-C.
A)
B)
C)
Figure 13: A) calculated axial voltage distribution for configuration I; B) calculated axial voltage distribution for
configuration II; C) FEM capacitive-resistive calculation of axial voltage distribution for configuration I and II; FEM:
Finite Element Method; DLC: double linkage capacitance; SLC: single linkage capacitance ;
As expected, the voltage drop at higher MO-blocks is greater than the voltage drop for the
lower position MO-blocks and consequently higher MO-blocks are more stressed than the
other MO-blocks. The configuration of the active part of the surge arrester has a significant
influence of the voltage distribution, due to the changed stray capacitances. Both calculations
by taking the non-linear resistive effect of the MO-block into account provides a clearly
information about the distribution, as can be shown in Figure 13-C. As a result, it is evident
that the effect of a long metal tube in the middle of the active part of the surge arrester leads
to a significant higher stress for the MO-blocks at the head, compare FEM I and FEM II.
13/15
5
Comparison between measurement and calculation
Figure 14 and Figure 15 show the calculated and the measured voltage distribution for
surge arrester configuration I and II at a temperature of 20°C. Both calculated curves are the
result of the numerical calculation (FEM). The variation between the measurement and
calculation is within the inaccuracy of the standard deviation of the spark gap, the adopted
boundary conditions in the simulation as well as the small deviation of each voltage current
curve of the MO-block. As can be seen, that the non-linear resistive capacitive simulation
give a good approximation about the voltage distribution. In Figure 14, U/Umean is smaller
than one over a wide range until MO-block 14/15 for the measurements as well as for the
calculations. In comparison to configuration I, configuration II leads overall to a higher
voltage stress from MO-block number 12/13 upwards. Nevertheless, the highest voltage
stress occurs, verified by simulation and measurements, at MO-block 22 for the surge
arrester configuration I.
Figure 14: Measured and calculated voltage distribution
for surge arrester configuration I at 20°C
6
Figure 15: Measured and calculated voltage
distribution for surge arrester configuration II at 20°C
Conclusion
In this contribution, a sphere spark gap is used as one possibility to determine the nonuniform voltage distribution along two surge arrester configurations. Preliminary experimental
tests and simulations have shown that the breakdown voltage characteristic of the spark gap
that is arranged in parallel with a MO-block is almost identical to an arrangement with only
one spark gap. Hence, it can be concluded, that the spark gap is a suitable method for the
measurement of the voltage distribution as it has a minimum influence on the electrical field
strength between the MO-block and the sphere gaps. The voltage and temperature
distribution measurements have shown that the voltage and temperature stress for each MO-
14/15
block is different. For both configurations, the voltage drop over the upper MO-blocks is
always higher than the rest of the MO-column, even though, the upper MO-blocks show not
the highest temperature. The temperature distribution shows a strong dependence of the
position and the size of the metal tubes. The greatest cooling could be achieved with
configuration II which also shows a lower average temperature than configuration I. It should
be pointed out, that during all measurements the porcelain housing was not assembled.
Further, the voltage distribution is numerical calculated with the help of 2D surge arrester
models. Several 2D numerical FEM models have been created to simulate the voltage
distribution by taking into account the permittivity and the non-linear conductivity. The
simulation results show a good agreement with the measurements and verify the assumed
parameters of the surge arrester model. The measurements have shown that the voltage
distribution depends, next to the stray capacitances, also on the temperature distribution of
the surge arrester column. As a future prospect, the realised simulation models will be
supplemented by a coupled electrical-thermal calculation in order to calculate the voltage
distribution and temperature distribution in advance (before type tests begin).
7
Acknowledgments
This work was mainly supported by TRIDELTA Meidensha GmbH. Further, I am grateful for
the support of the graduating school PhotoGrad.
8
References
[1] A. Küchler, โ€œHochspannungstechnik: Grundlagen - Technologie - Anwendungenโ€,
2nd edition, Berlin, 2005.
[2] E. Kuffel, W. Zaengl, J.Kuffel, โ€œHigh Voltage Engineering: Fundamentalsโ€, 2nd edition,
Oxford, Newnes, 2000.
[3] M. Beyer, W. Boeck, K. Möller, W. Zaengl, โ€œHochspannungstechnik: Theoretische und
praktische Grundlagen für die Anwendungโ€, Berlin, Springer, 1992.
[4] A. Schwab, โ€œHochspannungsmesstechnik: Messgeräte und Messverfahrenโ€, 3rd edition,
Berlin, Springer, 2011.
[5] L. Baxter, โ€œCapacitive Sensor: Design and Applicationsโ€, New York, IEEE Press, 1997.
15/15