Survey
* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project
* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project
Measurement and Control Design Standards I. Background and Overview A. The City’s Program Standards and Procedures (PSP) are intended to be used in conjunction with the data contained in related standards and procedures. They are not intended to be used as stand alone documents. It is the responsibility of the Designer to become familiar with all the PSP documents and comply with the criteria set forth as a whole. B. Designer shall adhere to the design standards without exception unless permission is granted by the City’s Project Manager to deviate from these standards. The City Project Manager shall be notified in writing of the need to deviate from any standard and approval issued by the Owner in writing before the design deviation is made. Approval will be authorized by the City Project Manager in writing before the design deviation is made. Should a design be made that deviates from these standards without approval from the City Project Manager, the Designer shall bear the cost of modifying the design to conform. This standard is divided into the following sections: II. III. IV. V. VI. VII. VIII. IX X. XI. XII. XIII. XIV. XV. XVI.. XVII. XVIII. XIX. General Requirements Nameplates and Labels for Control Enclosures Boxes, Control Panels, and Control Centers Low Voltage Motor Controls Uninterruptible Power Supply for Control Equipment Noise and Electrical Magnetic Interference (EMI) Suppression Control I/O Database Distributed Control System Fire Alarm and Life Safety Systems I/O Fusing Control Circuit Sourcing in General Motor Control Circuit Configuration General Control Circuit Configuration Analog Circuits Emergency Stop Circuits Data Collection Alarms Alarm Indication Measurement and Control Design Standards Page 1 of 20 January 31, 2005 II. General Requirements A. Apply the more restrictive requirements of the applicable codes and these design standards. Reference the Life Safety and Maintenance Access Design Standard for additional requirements. B. Provide National Electrical Code (NEC) working clearance requirements as a minimum to provide access to accommodate assembly, disassembly, and routine maintenance of equipment. C. Design shall ensure compliance with Seismic Zone 4. D. Floor mounted electrical equipment shall be installed on a concrete housekeeping pad 3.5 inches high. The concrete pad shall extend two inches in all directions beyond the foot print of all equipment. Refer to Drawing Requirements for example. E. Electrical equipment shall be placed to allow maintenance activities to be performed in areas protected from rain and wind. F. All electrical equipment and materials including, but not limited to, panels, instruments, transformers, conduits, and etc. shall be labeled as required by the State of Oregon Building Codes Division. G. Control circuits shall be shown in the de-energized (power off) position. H. Equipment shall be designed to not allow starting in the power off condition. I. Scaled plan views shall be provided for all electrical and measurement and control equipment and components. J. Scaled elevation drawings shall be provided for all areas containing electrical and measurement and control equipment or components, except for general purpose light switches and receptacles. K. All products referenced in this design standard (e.g., UPS, MCC, VFD, relays, selector switches, instrument transmitters, etc.) shall be those as specified in the Willow Lake Master Guide Specifications and the design documents shall be based on these products. The Designer must be familiar with the products specified so that all unique characteristics of each product are accurately reflected and reproduced in the design. L. The Drawing Library contains samples of the standard control circuits configuration to be used at the Willow Lake Water Pollution Control Facility (WLWPCF). Measurement and Control Design Standards Page 2 of 20 January 31, 2005 III. Nameplates and Labels for Control Enclosures All nameplates and labels for control enclosures shall be pursuant to Section VI of the Process Identification, Finishes and Labeling Design Standards. IV. Boxes, Control Panels, and Control Centers Control Panel Design: A. Enclosures located in dedicated electrical or control rooms shall be rated NEMA 12. All other locations shall be stainless steel enclosures rated NEMA 4X. Reference Master Guide Specification, Section 13430 - Boxes, Control Panels, and Control Centers, for specific product data. B. No devices, component, or instrument shall be mounted higher than 72 inches or lower than 24 inches above the finished floor. C. The design shall provide adequate space above components requiring natural convection for heat removal. This area shall be that as recommended by the manufacturer of the control component. If the manufacturer does not have a recommendation, the minimum distance shall be three inches. D. Terminal strips shall be mounted on back-panels. Relays and other like control devices are to be mounted around the center and top portions of the enclosure backpanel. E. Electrical enclosures supplied with 480-volt and above shall be provided with a main disconnect. F. Enclosures with power supplied from more than one source shall have a warning label affixed to the cover stating equipment is fed from more than one source. G. Scaled elevation drawings shall be provided for all exterior control panels and backpanel layouts with all the control devices mounted on the door and back-panel shown. H. The Designer shall ensure that all control enclosures are large enough to accommodate the required components and meet all design criteria including the spare space requirements stated in these standards. I. Control enclosures shall be designed with an additional 20 percent usable spare space available on the back-panel for future additions. This additional space does not need to be in one specific area, but can occupy up to three different areas that total the 20 percent requirement. The area shall be measured by using X and Y coordinates in a two-dimensional layout. J. Control enclosures, excluding MCC sections, shall contain primarily voltages equal to or less than 120 VAC and DC. Measurement and Control Design Standards Page 3 of 20 January 31, 2005 K. All back-panel layouts shall be designed to NEC Class 1 and Class 2 wiring requirements. The two classes shall be separated from each other by a distance of six inches: 1. When Class 1 and Class 2 circuits must cross, they shall do so at right angles or as close to right angles as possible. 2. Class 1 and Class 2 may be ran parallel when connecting to the same control device. This shall occur only for the minimum distance required to make the connection to the device. 3. Control enclosure design layouts shall clearly show and label Class 1 and Class 2 areas, terminal strips and wireways. 4. The Designer shall design control enclosures that will accommodate the construction of control systems using the above listed Class 1 and 2 standards. L. Back-panel layout design showing wire ducts running parallel with terminal strips, shall show a minimum of three inches distance between the wire duct and terminal strip. Terminal strips shown next to the edge of the back-panel without an adjacent wire way shall be shown to have a minimum of three inches distance between the terminal strip and the edge of the back-panel. M. All control panels larger than 36 inches high and 24 inches wide shall have a panel light fixture mounted on the ceiling of the control panel, near the front, with a door activated switch. N. During the design process, all control equipment enclosures shall have internal temperature analysis performed. This analysis shall be performed by charts, formulas or software provided by the enclosure manufacturer. The data from this analysis shall be provided to the City Project Manager at design reviews. This data shall be utilized by the Designer to ensure adequate temperature control is designed into the system to meet the requirements of all components located within the enclosure. O. Panels located in outdoor areas and unheated areas shall have heaters and ventilation fans or air conditioning installed. Indoor enclosures in climate controlled areas shall be only be required to have supplemental ventilation fans. All fans and intake ventilation louvers shall have filters that can be removed and cleaned. Heaters, ventilation fans, or air-conditioning units shall be operated from a thermostat mounted within the enclosure unless the temperature control is integral to the heater, fan, or air conditioner. Internal enclosure temperatures shall not exceed the temperature rating of any control components installed within the enclosure. P. Enclosures shall not be used as pull boxes. Q. Push button switches shall have button construction pursuant to Section 13430 Boxes, Control Panels, and Control Centers. Measurement and Control Design Standards Page 4 of 20 January 31, 2005 R. V. The standard selector switch operator shall be without level, cylinder locks, etc. and maintained in all positions. Should a clear advantage exist to deviate from this standard, approval shall be obtained from the City Project Manager. Low Voltage Motor Control Circuits Control Circuit Sourcing for Motor Control Circuits (MCC). A. Typical motor control circuits for 480 volt, three-phase motors shall be derived from individual Control Potential Transformers (CPT). These CPTs shall be connected to the load side of the motor branch circuit protection device for the motor. Both legs of the high voltage winding shall be fused. The ungrounded leg of the low voltage winding shall be fused with the other low voltage leg grounded at the point of installation for the CPT. All fuses shall have blown fuse indication. B. Typical motor control circuits for 240 and 208 single phase motors shall be derived either from CPTs that are connected to the load side of the motor branch circuit protection device for the motor or preferably by connecting to one leg of the 240 or 208 conductor and grounded neutral for the system. The CPTs shall be fused on the ungrounded leg of the low voltage winding with the other low voltage leg grounded at the point of installation for the CPT. If no CPT is used, the ungrounded conductor shall be separately fused. C. For packaged, Original Equipment Manufacturer (OEM) provided equipment, all motor starters that are not located in a MCC and are an integral component of the OEM provided system shall be permitted to operate from one single 120 VAC (nominal) control power source provided by the manufacturer. VI. Uninterruptible Power Supply for Control Equipment Control Circuit Power Sources: A. The 120 VAC control power for DCS I/O shall be from an Uninterruptible Power Supply (UPS). The 120 VAC supplying power to the UPS from a lighting panel or dedicated CPT shall be used as an alternate source of power by the use of a threeposition selector switch with Line/Off/UPS positions. B. All UPS shall be pursuant to Master Guide Specification, Section 13455 Uninterruptible Power Supplies for Control Equipment. C. A UPS under 700 VA shall be installed within a dedicated enclosure. A UPS over 700 VA shall be installed on a shelf for visibility and ease of access and properly secured for the Seismic Zone 4. D. The UPS shall be monitored for failure alarms by the Foxboro DCS. The UPS shall generate a discrete 120 VAC input to the DCS that indicates a general UPS failure or fault alarm. If this contact is not rated for 120 VAC, an alternate power supply and Measurement and Control Design Standards Page 5 of 20 January 31, 2005 slave relay shall be installed to accommodate the required alarm input to the DCS. Reference Drawing Library for typical installation detail. E. The UPS shall be configured to prevent shutdown from external devices. VII. Noise and Electrical Magnetic Interference Suppression A. For systems that are supplied power from UPS units, protection for electrical noise transmission from power sources shall be provided through the UPS unit itself. No additional noise suppression shall be necessary. B. For non-UPS power, noise suppression for electrical noise transmission from power sources shall be provided by a dedicated Transient Voltage Surge Suppression (TVSS) device. C. The TVSS shall be inserted in the control circuit to protect the loads sensitive to electrical noise transmissions such as controller processors and instrument power supplies. Equipment such as panel lights, enclosure temperature control equipment, relay control circuits, etc. are not required to be protected by TVSS devices. D. Electrical noise from non-power sources are primarily large inductive devices such as size three and greater motor starters, solenoid valves drawing 300 mA and greater, and small, fractional horsepower motors (1/8 Hp and less). If these devices are powered directly from the controller outputs, individual noise suppression devices shall be installed and connected to the coil of each device. These devices shall be Metal Oxide Varistors (MOV). E. Protection from other sources, such as Variable Frequency Drives (VFD), shall be considered provided by the design requirements for electrical construction. Components such as conductors installed in rigid conduit, control enclosures constructed of metal, and instrument cable shields/ drain wires are to be properly grounded. This does not rule out the possibility that additional measures may be required. The Designer shall determine the need of additional noise suppression and recommend such measures to the City Project Manager during the design process. An example may be the use of EMI resistant control enclosures in areas containing VFDs. Measurement and Control Design Standards Page 6 of 20 January 31, 2005 VIII. Control I/O Database A. A Control I/O Database will be developed for all projects at WLWPCF. The database will be created during the Schematic Design Phase of a project by the Design Team and continue to be expanded through all phases of the project. The database shall be managed by one-individual selected by the City Project Manager. Any and all modifications to the project database shall be submitted to the Database Manager. The database shall be utilized for control development, construction, startup, and commissioning activities. B. At the completion of the Schematic Design Phase of a project the database shall be provided as a deliverable to the Owner. C. During each phase of the project various members of the Project Team will be providing information that will be added to the database. Specific database information required to be provided by team members is detailed below. The required information listed is the minimum database information requirements. Any additional information that Project Team members identify as information that will contribute to the success of the project should be submitted to the Owner for approval to be included in the database. The Owner may request additional information be provided. D. The Control I/O Database shall be developed utilizing Microsoft Access. E. Following lists the minimum database information that will be provided by Project Team members: 1. The Design Team shall provide (at minimum) the information detailed in Table 1 for every I/O point developed. Each item listed in Table 1 represents a separate field for each database record. Table 1 Design Team—Database Requirements Database Field Description of database field REF_NO (Reference Number) The Reference Number is the principal method of uniquely identifying records in a database. EQUIP_TAG (Equipment Tag) Lists the Equipment Tag assigned to the I/O point. DESCRP (Description) A description of the I/O point Facility Code The plant facility code that the I/O point is associated with. Process The plant process that the I/O point is associated with. P&ID_DWG Number(s)) (P&ID Drawing Measurement and Control Design Standards Lists the P&ID drawings that the I/O point is detailed on. Page 7 of 20 January 31, 2005 ELEC_DWG (Electrical Drawing Lists the Electrical drawings that the I/O point is detailed Number(s)) on. SIG_TYPE (Signal Type) Defines the type of signal used by each I/O point. This field normally contains one of five values: AI - analog input AO - analog output DI - discrete input DO - discrete output PI - pulse input SIG_RANGE (Signal Range) Defines the type and level of field signal used by each I/O point. (e.g. 4-20 ma for analog, 24VDC for discrete) PSOURCE (Power Source) Defines source power for instrumentation (Internal or External). CAL_REL (Calibration Relationship) This field is used for analog inputs. It should be left blank unless the input signal should be square-rooted., in which case the field should contain the value “SQRT”, or another appropriate indication that the calibration is other than linear. INST_TYPE (Instrument Type) Defines type of Instrument (e.g. Pressure Transmitter). EO1 (Engineering Units) Defines the Engineering Units that the analog input, analog output, or pulse input point is measuring. HSCO1 (High Scale) This field is used for analog-input, analog-output, and pulse-input points. It defines the maximum permissible value of the point, in engineering units. For 4-20mA analog inputs and outputs, this is typically the engineering unit value at 20 milliamps. LSC01 (Low Scale) This field is used for analog-input, analog-output, and pulse-input points. It defines the minimum permissible value of the point, in engineering units. If not supplied, the default value is 0. For 4-20mA analog inputs and outputs, this is typically the engineering unit value at 4 milliamps. Failsafe If applicable defines the Failsafe state (Energized, Deenergized). ALM (Alarm) This field should contain a “Yes” or “No” indicating whether or not the I/O point will generate alarms. Measurement and Control Design Standards Page 8 of 20 January 31, 2005 ALM_STATE (Alarm State) This field is used for discrete inputs. It normally contains “TRUE” or “FALSE,” indicating whether the point generates an alarm in the closed state (closed field contact) or the open state (open field contact). This information is extremely important to define the action or polarity of Discrete inputs used for logic functions. If this information is not supplied, the default value is alarm on closed state (“TRUE”). HALIM (High Alarm Limit) This field is used for analog inputs. It defines the value, in engineering units, at which point the I/O point will go into a high alarm condition. If not provided by the Design Team this information will be provided by the owner. HHALIM (High High Alarm Limit) This field is used for analog inputs. It defines the value, in engineering units, at which point the I/O point will go into a high high alarm condition. If not provided by the Design Team this information will be provided by the owner. LAL (Low Alarm Limit) This field is used for analog inputs. It defines the value, in engineering units, at which point the I/O point will go into a low alarm condition. If not provided by the Design Team this information will be provided by the owner. LLALIM (Low Low Alarm Limit) This field is used for analog inputs. It defines the value, in engineering units, at which point the I/O point will go into a low low alarm condition. If not provided by the Design Team this information will be provided by the owner. Design Comments Utilized for any Design Team comments relating to the control point. 2. The Owner shall provide (at minimum) the DCS information detailed in Table 2 for every DCS I/O point developed. Each item listed in Table 2 represents a separate field for each database record. Table 2 Owners—Database Requirements Database Field Description of database field Block Name Contains the control block name Compound Contains the name of the control compound that the control block resides in IOM_ID Contains the 6-character letterbug address of the FBM that the I/O point is connected to. Measurement and Control Design Standards Page 9 of 20 January 31, 2005 PNT_NO (Point Number) Contains the 2-digit point address within the FBM that the I/O point is connected to. Block Type Contains the type of control block utilized to connect the I/O point in the DCS (e.g. AIN, AOUT, CIN, COUT. Card Type Contains the type of FBM that the I/O point is connected to. ENCL_NAME (Enclosure Name) Contains the name of the enclosure in which the I/O point’s module resides. ALM (Alarm) This field should contain a “Yes” or “No” indicating whether or not the I/O point will generate alarms. This field is generated by the Design Team but should be reviewed by the Owner and changed if required. ALM_STATE (Alarm State) This field is used for discrete inputs. It normally contains “TRUE” or “FALSE,” indicating whether the point generates an alarm in the closed state (closed field contact) or the open state (open field contact). This information is extremely important to define the action or polarity of Discrete inputs used for logic functions. If this information is not supplied, the default value is alarm on closed state (“TRUE”). This field is generated by the Design Team but should be reviewed by the Owner and changed if required. HAL (High Alarm Limit) This field is used for analog inputs. It defines the value, in engineering units, at which point the I/O point will go into a high alarm condition. If not provided by the Design Team this information will be provided by the owner. If this information is not provided by the Design Team it shall be provided by the Owner. HHALIM (High High Alarm Limit) This field is used for analog inputs. It defines the value, in engineering units, at which point the I/O point will go into a high high alarm condition. If not provided by the Design Team this information will be provided by the owner. LAL (Low Alarm Limit) This field is used for analog inputs. It defines the value, in engineering units, at which point the I/O point will go into a low alarm condition. If not provided by the Design Team this information will be provided by the owner. Measurement and Control Design Standards Page 10 of 20 January 31, 2005 LLALIM (Low Low Alarm Limit) This field is used for analog inputs. It defines the value, in engineering units, at which point the I/O point will go into a low low alarm condition. If not provided by the Design Team this information will be provided by the Owner. HAT (High Alarm Text) The HAT (High Alarm Text) field is used for analog inputs. It contains the text that the DCS will display in the alarm summary when the block goes into high alarm. HHATXT (High High Alarm Text) The HHAXT (High High Alarm Text) field is used for analog inputs. It contains the text that the DCS will display in the alarm summary when the block goes into high high alarm. LAT (Low Alarm Text) The LAT (Low Alarm Text) field is used for analog inputs. It contains the text that the DCS will display in the alarm summary when the block goes into low alarm. LLATXT (Low Low Alarm Text) The LLATXT (Low Low Alarm Text) field is used for analog inputs. It contains the text that the DCS will display in the alarm summary when the block goes into low low alarm. HLPR (High/Low Alarm Priority This field is used for analog inputs. It sets the alarm priority if the I/O point goes into alarm. NM0 (Name for Zero State) The NM0 field is used for Discrete-input fields. It contains the text that I/A will display when the point changes to the 0 state (open contact). Typical values are ON, OFF, RUN, STOP, E-STOP, etc. NM1 (Name for One State) The NM1 field is used for Discrete-input fields. It contains the text that I/A will display when the point changes to the 1 state (closed contact). Typical values are ON, OFF, RUN, STOP, E-STOP, etc. SAT (State Alarm Text) The SAT field is used for discrete inputs. It contains the text that the DCS will display in the alarm summary when the block goes into a state alarm. SAP (State Alarm Priority) This field is used for discrete inputs. It sets the alarm priority if the I/O point goes into a state alarm. Verified This field is used for commissioning. It will remain blank until the I/O point (and all I/O point info.) has been verified. When The I/O point has been verified this field will contain the verification date. Measurement and Control Design Standards Page 11 of 20 January 31, 2005 Verified By This field is used for commissioning. When the I/O point has been verified this field shall contain the initials of the person who verified the I/O point. Rev_Date (Revision Date) Shall contain the date on which the Database Manager last revised the I/O point. Owner Comments Utilized for any Owner comments relating to the control point. IX. Control Drawings A. B. The Designer shall provide the following detailed drawings for all new and modified processes: 1. Piping and Instrumentation Drawings (P&IDs). 2. Control system discrete input diagrams 3. Control system discrete output diagrams. 4. Control system analog input loop diagrams. 5. Control system analog output loop diagrams. 6. Control system architecture drawings. All drawings shall be pursuant to the Willow Lake WPCF Drawing Requirements Standard.. X. Process Control Narratives/Control Strategies A. The designer shall provide a process control narrative/strategy for all new or modified processes and equipment control. Process control narrative/strategy shall be submitted in the following format: 1. Introduction The introduction shall provide an overview of the process and equipment that is to be controlled. This section will include an overview of the process and the associated equipment that will be utilized to control the process. Measurement and Control Design Standards Page 12 of 20 January 31, 2005 2. Control Description Shall be a detailed step by step narrative of the control strategy required to control the process or equipment. Control for every piece of equipment in the process shall be detailed in this section. 3. Common Monitoring Shall detail all locations that equipment is being monitored and controlled from. Each individual control variable being monitored from the common locations shall be listed in this section. 4. Field/Local Control Shall detail the control functionality that will be available locally at the equipment that is to be controlled. 5. DCS Manual Control Shall detail the manual control functionality that will be available from the DCS. 6. DCS Automatic Control Shall detail the automatic control and functionality that will be provided by the DCS. 7. Monitoring and Alarms Shall detail indications and alarms that will be available at the DCS in addition to the common monitoring. XI. Distributed Control System Distributed Control System Design General Requirements: A. Refer to the Distributed Control System (DCS) Design Standards for detailed data. B. The DCS for the WLWPCF is Foxboro I/A. The existing facility operates with the Foxboro I/A Series control processors and compatible I/O modules. The new facility shall use Foxboro I/A Series control processors and I/O modules to control and monitor new process equipment. The Designer shall note that certain areas of the existing facility will be upgraded during the design process. Equipment removed from operation shall be salvaged and given to the Owner. C. It is imperative to have one control system that is common to all unit processes. There should be one common method of operator interface, information sharing, reporting, data collection, database maintenance, trending and alarming. All control design shall Measurement and Control Design Standards Page 13 of 20 January 31, 2005 be performed with these criteria in mind. The control system of choice for the WLWPCF is the Foxboro I/A system. D. Original Equipment Manufacturer (OEM) may routinely provide a process purchased as a packaged unit that is provided with a control system. These processes are frequently controlled by Programmable Logic Controllers (PLCs). Regardless of the method of control selected, the process will be integrated into the Foxboro I/A DCS. E. The OEM system controller shall be hardwired to provide necessary I/O to the DCS for basic control and alarm status. F. Heat, Ventilation, and Air Conditioning (HVAC) systems typically have their own control systems requiring little or no intervention by the plant operator. The DCS will monitor the HVAC system and alarm status through the use of hardwired inputs to the DCS. G. Communication busses and data highways for all control systems shall be redundant. H. Control of primary process, control equipment (pumps, blowers, etc.) within a process area shall be distributed between separate I/) modules. This is to ensure that loss of single I/O module will not result in complete failure of a critical process or result in plant upset. XII. Fire Alarm and Life Safety Systems A. Fire Alarm and Life Safety systems shall have their own control and monitoring systems. Supervisory, trouble and alarm conditions shall be interfaced with the DCS. B. The Designer shall provide designs using standard industrial control enclosures based on control panel design as given in this guideline to house the DCS I/A systems components unless otherwise specified by the City Project Manager. C. The Designer shall provide for program backup of non-DCS controller processor programs. The preferred method is to use Electrically Erasable Programmable ReadOnly Memory (EEPROMS) if available. If not, the design shall specify other available means such as battery backup. D. Control program software and hard copies of the program shall be provided to the City Project Manager for controllers of non-DCS systems. E. The designer shall recommend control redundancy for Fire Alarm and Life Safety Systems. Measurement and Control Design Standards Page 14 of 20 January 31, 2005 XIII. AC and DC conductors A. AC and DC conductors shall be routed in separate conduits B. All conductor terminations shall be pursuant to Section 13420-2.06.AA Hollow Shaft Terminations. XIV. I/O Fusing Fuse discrete inputs to the Foxboro DCS system when power originates from the DCS. XV. Control Circuit Sourcing in General Typical control voltage for all discrete control circuits shall be 120-VAC powered from a source with a grounded neutral: A. Lower voltage exceptions must be approved by City Project Manager. B. Devices installed in areas classified as hazardous by the NEC shall use intrinsically safe devices as required by code. Intrinsically safe devices installed in areas containing substantial moisture or other conducting mediums that could provide and electrical shock hazard shall be powered by 24 volts DC or 24 volts AC. XVI. Motor Control Circuit Configuration A. Motor control circuits using hand only control functions shall use “Start” and “Stop” pushbuttons in a three-wire control configuration such that after the motor starter is energized by the Start pushbutton, the motor starter will remain energized until either the Stop pushbutton is pushed, an overload contact opens, electrical power is lost, or a safety interlock turns the motor starter off. Once off, the motor starter will remain deenergized until the Start pushbutton is once again pressed. B. Motor control circuits using a combination of hand and auto control functions shall be designed with a three-position, Hand-Off-Auto (HOA) switch to provide hand (local) control through the Start/Stop pushbuttons and auto control (or remote) mode of operation. The selector switch shall electrically disable all operation of the controlled motor when placed in the “Off” position. C. All motor control circuits shall provide indication of motor status through the use of indicating lights. D. Motor running status shall be provided by a “red”, push-to-test, Light-Emitting Diode (LED) indicating light. The light shall be labeled as directed in the Process Identification, Finishes and Labeling Design Standards. Measurement and Control Design Standards Page 15 of 20 January 31, 2005 E. Motor stopped status shall be provided by a “green,” push-to-test, LED indicating light that is connected directly to the “hot” side of the motor control through a normally closed motor starter auxiliary contact. This light shall be labeled as directed in the Process Identification, Finishes and Labeling Design Standards. F. For pump motors with check valves installed on the pump discharge, the preferred method of validation that the connected pump is pumping shall be through the use of limit switches mounted on the check valve arm. This switch shall detect if the valve is open by sensing the position of the check valve arm when in the open position. For this application, the preferred limit switch shall be a magnetic proximity switch. G. For pump motors controlled by the Foxboro DCS, the limit switch shall provide an input directly to the DCS. The DCS shall generate a “Pump Failed” alarm if the check valve does not open within a short time delay after the motor is energized or if the valve is not closed when the motor is de-energized. H. All motor circuit designs shall require hand resettable overload contacts. I. All motor overload devices shall provide a minimum of two contact closures, the required normally closed contact to de-energize the hardwired motor controls on motor overload conditions and a second contact to provide a discrete input to the Foxboro DCS should a motor overload condition exist. XVII. General Control Circuit Configuration A. The HOA designation shall be used when Auto refers to control by the Foxboro DCS. The Hand-Off-Remote (HOR) designation shall be used when remote refers to hand only or a combination of hand and auto control provided at a control station located remotely from the HOR switch. B. Standard design will be that the Auto position will refer to DCS control. If Auto does not refer to DCS, the phenolic nameplate mounted above the switch will reference the name of the auto device (source of control other than DCS). C. For HOA selector switches used in control circuits that provide two modes, or sources, of Auto control, one HOA selector switch will select the mode, the second selector switch shall select the sources of Auto control. XVIII. Analog Circuits A. Loop powered instruments connected to Foxboro Field Bus Modules (FBM) will be connected to the 24 VDC loop power provided by the FBM. B. Loop powered instruments connected to analog input modules other than Foxboro shall be connected to a common 24 VDC, DIN rail mounted power supply within the same enclosure. Typically, power supplies providing instrument loop power shall consist of a single power supply per each application. For critical systems, the use of Measurement and Control Design Standards Page 16 of 20 January 31, 2005 two redundant, parallel connected power supplies is to be considered. The Designer shall determine if parallel power supplies are warranted and present the need for City Project Manager approval. Reference the Drawing Library for examples of the preferred single and redundant power supply configurations. C. Each instrument loop connected to a common power supply and each loop connected to a Foxboro analog input module shall be fused at the point of supply with a 50 mA fuse located in a fusible terminal block provided with a blown fuse indicator. D. All field located analog instruments shall generate a 4-20 mA signal. E. All installed devices operating from the converted 4-20 mA loop shall be designed to operate from 1-5 VDC. If connection is made to a single device that accepts 1-5 VDC only and the field cable is providing 4-20 mA, the added 250Ω resistor shall be connected, along with the enclosure instrument cable, at the device termination, not the field terminal strip where the field cable is connected. F. Each analog device connection within an enclosure shall be the same instrument cable as that used for field connections, except cable that does not leave the enclosure shall be #20 AWG with 600-volt insulation. The wire shall be sized to limit voltage drop to less than two volts. G. The design shall be configured so the panel builder is not required to use only one conductor of a Twisted Shielded Pair (TSP) instrument cable or be required to strip more than four inches of cable insulation to install the circuit as designed. H. Conductor colors for instrument cables shall be “red” for positive and “black” for negative. I. Each instrument control enclosure shall have a low resistance, copper ground bus bar installed. The ground bus bar shall be connected through a ground wire to the ground connection located at the source of power for the panel. Each ground bus bar shall also be grounded to the enclosure back-panel through the use of “star” washers on threaded screws. K. The shield (or drain wire) for instrument cables for analog circuits shall be grounded at one-point throughout the entire circuit. The point of grounding shall be as required by the instrument manufacturer for the device specified. L. The ground bus shall be used to ground all enclosure located instruments and control components that are required to be grounded by the manufacturer. XIX. Emergency Stop Circuits A. Typical design for an emergency stop circuit shall be a red mushroom head, maintained, push/pull, non illuminated, pushbutton switch connected in series with the device to be de-energized such as a motor starter, solenoid, and control valve, etc. Measurement and Control Design Standards Page 17 of 20 January 31, 2005 B. This requirement is not intended to exclude other emergency stop devices from being included in the design whenever appropriate for the use. The Designer shall always consider the most appropriate device providing the greatest degree of protection. Other commonly available and used devices are as follows: 1. Light curtains. 2. Limit switches (mechanical, magnetic proximity and photoelectric). 3. Safety mats. 4. Pull chains and ropes. C. The emergency stop circuit should be designed such that a common voltage to all devices is turned off when the emergency stop function is activated. The use of relays to turn off multiple devices is to be avoided. To achieve this design for systems with multiple voltage sources, add contacts to the emergency stop switch as required. D. When pull chains and ropes are used as emergency stop switches, the chains/ropes are to be tied to a pull switch specifically designed for the purpose. These switches are of heavy duty construction and have contacts that once opened, must be manually reset at the switch itself. E. The emergency stop device must be designed to be hardwired connected directly to the device to be de-energized in an emergency stop condition. The DCS shall not be utilized to perform emergency stop functions. The DCS shall only monitor the status of the emergency stop device. XX. Field Start Stop Switches A. Field Start/Stop switches shall be located adjacent to the equipment that the switches operate. B. Field Start/Stop switches shall only be active when the associated equipment LOR switch is in the Remote position. C. Field Start/Stop switches shall connect to DCS I/O discrete inputs. The Start position shall be connected to one input and the Stop position shall be connected to a separate input. D. When the Start button is depressed the DCS will place the associated equipment control into the Remote-Manual mode and issue a start command. The command shall remain latched until a stop command is issued. E. When the Stop button is depressed the DCS shall issue a Stop command. Once the associated equipment has been identified as stopped the DCS shall place the associated equipment control into the Remote-Automatic mode. Measurement and Control Design Standards Page 18 of 20 January 31, 2005 XXI. Actuators A. Process Control Valve Actuators shall be pneumatic. All other Valve actuators shall be electric. B. All Gate Actuators shall be electric. C. All Valve and Gate Actuators shall have a manual override (hand wheel). D. All Electric Actuators shall be provided with local open/close/stop and HOR switches. XXII. Data Collection Electrical power monitoring devices shall be connected to the DCS using 4 - 20 mA analog loops or discrete inputs. XXIII. A. B. Alarms Alarms are defined as all conditions, either event (discrete) or value (analog) driven, that require timely operator notification for the purpose of initiating operator response. The intended response can be either the recording of information or the modification of the process monitored. The design requirement for establishing an alarm condition is normally intuitive. Examples include high levels in a reservoir, wet well or other similar high liquid level condition, high levels of life threatening chemicals such as chlorine should be alarmed. A complete list of proposed alarm conditions shall be provided by the designer to the City Project Manager at completion of Schematic Design for approval. C. Typically alarms shall be value based derived from analog signals generated by field instruments such as flow and level transmitters monitored by the DCS with alarms generated as determined by the software program resident in the DCS. The use of this type of alarm generation results in maximum flexibility as alarm set-points can be adjusted easily and alarms configured without modification of hard wired devices. D. Crucial alarms should be primarily value (analog) based but may also require a hardwired, event-based alarm used for backup should the primary analog device fail. The City Project Manager should help identify these cases by the completion of the Schematic Design Phase. E. Analog circuits shall alarm at two percent above or below scale and out of range. F. The preference for discrete alarm design is to require the energizing of the alarm circuit though the action of closing a normally open set of contacts controlled by the alarm monitoring control component. Measurement and Control Design Standards Page 19 of 20 January 31, 2005 G. For critical systems where the failure of the alarm circuit to energize due to broken wires, loose connections, etc., would result in equipment damage and/or would create a safety hazard to on-site personnel, the alarm circuit shall be designed fail safe. This means that under normal, safe conditions, the alarm circuit is energized. To alarm, the circuit must be de-energized. The Owner must approve the use of fail safe alarm circuits during initial design reviews before the use of these circuits can be included in the final design. H. Critical alarms shall be local latching with field reset only. This requirement is meant to establish the necessity for field observation to ensure that the condition has actually cleared before the alarm can be reset. I. A class of specialized alarms shall be “Help Me” switches. The intent of this switch is to provide emergency notification for injured personnel to signal for assistance. J. The “Help Me” switch shall be a single, blue mushroom head, maintained, push-pull, non-illuminated, pushbutton switch mounted in a small control enclosure and placed at strategic areas throughout the facility. These pushbutton switches shall in turn be connected to the DCS system for monitoring. K. A unique nameplate shall be mounted immediately above each “Help Me” switch. The nameplate shall be as described in the Process Identification, Finishes and Labeling Design Standards. L. Eyewash stations shall include a flow switch alarm to be connected to the DCS system. XXIV. Alarm Indication A. Except for localized alarming, all other alarm logic functions shall be provided by the Foxboro DCS. B. The strobe light color for the “Priority 1 Life Safety Alarm” shall be red. The “High Alarm” would be activated at a pre-defined value based on the level of danger and activate the strobe light. If the level of danger increases, the “High-High Alarm” would activated at a higher pre-defined value and activate the horn. Alarms are latching. The acknowledge button will silence the horn. The strobe light will shut off only after the level of danger has dropped below the pre-defined “High Alarm.” C. When horns and strobe lights are used as alarms, the devices shall have warning nameplates mounted within one-foot of the horn/strobe. This nameplate shall be red with white letters and be capable of being read at a minimum distance of 20 feet and shall identify the type of alarm and provide instructions as to the appropriate response the alarm demands, such as “Evacuate.” D. Horns for critical alarms shall not be located outside of buildings typically. This requirement is intended to keep outdoor noise levels to a minimum. —End of Section— Measurement and Control Design Standards Page 20 of 20 January 31, 2005