Application sheet for Green 300 series controllers Title Number: Furnace temperature control with Solid State Relay(SSR) AP35001 Purpose Control a furnace temperature by using UT350 temperature controller. Model UT350 can drive SSR as an actuator directly. Application Electrical Furnace Controller UT350-00 File Name: UTAP3501.t3d Loop Configuration: Input Range: 0 - 1200deg C Input Type: TC type K Output Type: Voltage pulse Cycle time: 3sec. Temperature Set-point: 700deg C PID parameters P=5% I = 240sec. D= 60sec. UT350-00 Temperature signal TIC SSR Electrical Furnace Heater AC Power Supply Wiring: UT350-00 [16] MV [17] + [8] [9] [10] + Power supply [12] TC Input [13] TC type K - Heater - 12VDC Voltage Pulse Solid-state Relay Explanation This is simple example for temperature control. Model UT350 can read : the temperature from Type K sensor directly. Model UT350 also has very powerful control functions, such as Auto-Tuning, SUPER function for overshoot suppression, SUPER2 function for hunting suppression and universal control output. Customer can select a one control output from either Voltage Pulse, Relay Contact or 4 - 20mA Current output. 1st Edition, August 2001 Application sheet for Green 300 series controllers Number: Title Furnace temperature control with Thyristor(SCR) Purpose Measure the furnace temperature by using TC. PID Control for a furnace temperature, temperature sensor is a TC and actuator is a SCR. Application Electrical Furnace Controller UT350-00 AP35002 File Name: UTAP3502.t3d Loop Configuration: Input Range : 0 - 1200deg C Input Type : TC type K Output Type : Current Output Set-point : 700deg C PID parameters P= 5% I= 240sec. D= 60sec. UT350-00 UT350-00 Temperature signal TIC TIC 4 - 20mA Current signal SCR SCR Electrical Furnace Wiring: AC Power Supply Heater UT350-00 TC type K - MV + [16] [17] + [12] [13] TC Input 4 - 20mA - Heater Power supply [8] [9] [10] Explanation : Temperature signal thyristor A 4 - 20mA current output is used to drive a Thyristor unit. Thyristor unit can control the current for a heater. 1st Edition, August 2001 thyristor Application sheet for Green 300 series controllers Title Number: Heat-Exchanger Temperature control Purpose AP35003 Produce hot water with constant temperature by using plate type heat-exchanger. Application Hot water for air conditioning and environment chumber. Controller UT350-00 File Name: Loop Configuration: Input Range: Input Type: Output Type: Set-point: ID parameters Pump Interlock 0 - 100.0deg C Pt100ohm Current Output 45deg C P = 30% I = 40sec. D = 5sec. Hi-Alarm ON at 50deg C OFF at 48deg C Alarm action : UTAP3503.t3d UT350-00 Hi-Alarm TIC Temperature signal I/P Current to Pneumatic Converter Heat Exchange r Hot water 2deg C Alarm condition Very Hot water Water 50deg C Wiring: UT350-00 Alarm output1 Di2 [18] Power supply Explanation : [16] [17] MV A B B temperature sensor + STOP/RUN Stop during On [6] Do1 AL1 [7] [11] Temperature Input [12] [13] 4 - 20mA - control valve [20] [8] [9] [10] Alarm set points are displayed on "Select Panel" for easy changing during operation. The ID control function will be stoped and a preset signal (0%) will be outputed when the pump interlock signal will turn to on. The current output signal is used to drive a control valve. 1st Edition, August 2001 Application sheet for Green 300 series controllers Number: Title Packaged Air Conditioner Temperature control Purpose Control ON/OFF valve for cooling water and power switch for Heater to keep the room temperature. Application Packaged Air Conditioner Controller UT350-00 AP35004 File Name: UTAP3504.t3d Loop Configuration: Input Range: 0 - 50deg C Input Range: Pt100 ohm Set-point: 25deg C Deviation Hi-Alarm: 2deg C Deviation Low-Alarm: 2deg C Hi-Alarm hysteresis: 0.5deg C Low-Alarm hysteresis: 0.5deg C UT350-00 TIC Temperature signal Cooling water Heater ON AL2 Valve Open AL1 0.5deg C Hysteresis Cooling water 0.5deg C Hysteresis Heater Air to Room Feedback Room Air Fan SP 2deg C Dead band HY2 2deg C Dead band HY1 Wiring: UT350-00 Magnetic Switch Temperature Input A Pt100 ohm B B [11] [12] [13] Heater AL2 [5] AL1 [6] [7] Power supply SEQ Cooling water Valve [8] [9] [10] Explanation : This is a simple Heating / Cooling control example. Model UT350 has a Heating / Cooling control function; however, two alarm outputs are enough to switch a ON/OFF valve and a Heater. 1. If PV temperature is higher than (SP+2deg.C), a deviation Hi alarm turnes to ON. Then, a cooling water valve is opened. 2. If PV temperature is lower than (SP-2deg.C), a deviation Low alarm turnes to ON. Then, a heater switch is turned to on. 1st Edition, August 2001 Application sheet for Green 300 series controllers Number: Title Tank Level Control Purpose Control a Tank level by using a pressure transmitter. UT350 has a power supply function to a transmitter. Application Tank Level Control Controller UT350-30 AP35005 File Name: UTAP3505.t3d Loop Configuration: Input Range: Input Type: Output Range: Set-point: PID parameters 0 - 1,500mm 1.0 - 5.0VDC UT350-30 4 - 20mADC Level Signal LIC 1,200mm P = 10% I = OFF Transmitter D = OFF power supply MR = 0% MV 4 - 20mA MR (Manual Reset) is output when PV =SP. Control Valve Level transmitter Wiring: UT350-30 12 Pressure Input 13 + 16 + Power supply 250ohm Loop power 21 supply 22 MV 17 4 - 20mA - Level transmitter - 8 9 10 Explanation Control the tank level by Proportional control with Manual Reset function. : Proportional control may occur small offset; however, the control response is very fast. UT350 has two types of power supply function to a two-wire transmitter. All types of UT350 can supply 14.5VDC power to a transmitter. Model UT350-3_ can supply 21.6VDC power to a transmitter. A 14.5VDC will be enough for almost all analog type 2-wire transmitter. A 21.6VDC will be used to drive microprocessor based 2-wire transmitter. 1st Edition, August 2001 Application sheet for Green 300 series controllers Number: Title Pump outlet pressure control Purpose Control the voltage & frequency of a pump to control the pump outlet pressure. Application Pump outlet pressure control Controller UT350-00 AP35006 File Name: UTAP3506.t3d Loop Configuration: Input Range: Input Type: Output Range: Set-point: PID parameters 0 - 1.00 MPa 0.40 - 2.00 VDC 4 - 20mADC 0.7MPa P =150% I = 20sec. D = OFF UT350-00 PIC Pressure Input Transmitter power supply MV 4 - 20mA R Start Signal Inverter Pressure transmitter P Wiring: UT350-00 [20] MV - Loop power supply [16] 4 - 20mA [17] [8] [9] [10] Pressure transmitter + Power supply Pressure Input 100 ohm + [12] [13] [14] [15] RUN/STOP signal [18] ON: STOP Di2 P - Inverter Explanation Model UT350 has a RUN/STOP function. : RUN mode(Di is ON): STOP mode(Di2 is OFF): PID control PID computation is stopped. Preset MV is outputed as MV. UT350 can control the pump pressure without overshoot, because control output starts from 0%. UT350 can supply 14.5VDC power to a transmitter. 1st Edition, August 2001