Application sheet for Green 300 series controllers
Title
Number:
Furnace temperature control with Solid State Relay(SSR)
AP35001
Purpose
Control a furnace temperature by using UT350 temperature controller. Model
UT350 can drive SSR as an actuator directly.
Application
Electrical Furnace
Controller
UT350-00
File Name:
UTAP3501.t3d
Loop Configuration:
Input Range: 0 - 1200deg C
Input Type:
TC type K
Output Type: Voltage pulse
Cycle time:
3sec.
Temperature Set-point: 700deg C
PID parameters
P=5%
I = 240sec.
D=
60sec.
UT350-00
Temperature
signal
TIC
SSR
Electrical
Furnace
Heater
AC Power
Supply
Wiring:
UT350-00
[16]
MV
[17]
+
[8]
[9]
[10]
+
Power supply
[12]
TC Input
[13]
TC type K
-
Heater
-
12VDC Voltage Pulse
Solid-state
Relay
Explanation
This is simple example for temperature control. Model UT350 can read
:
the temperature from Type K sensor directly. Model UT350 also has very
powerful control functions, such as Auto-Tuning, SUPER function for
overshoot suppression, SUPER2 function for hunting suppression and
universal control output.
Customer can select a one control output from either Voltage Pulse, Relay
Contact or 4 - 20mA Current output.
1st Edition, August 2001
Application sheet for Green 300 series controllers
Number:
Title
Furnace temperature control with Thyristor(SCR)
Purpose
Measure the furnace temperature by using TC. PID Control for a furnace
temperature, temperature sensor is a TC and actuator is a SCR.
Application
Electrical Furnace
Controller
UT350-00
AP35002
File Name:
UTAP3502.t3d
Loop Configuration:
Input Range : 0 - 1200deg C
Input Type : TC type K
Output Type : Current Output
Set-point :
700deg C
PID parameters
P=
5%
I=
240sec.
D=
60sec.
UT350-00
UT350-00
Temperature
signal
TIC
TIC
4 - 20mA
Current signal
SCR
SCR
Electrical
Furnace
Wiring:
AC Power
Supply
Heater
UT350-00
TC type K
-
MV
+
[16]
[17]
+
[12]
[13] TC Input
4 - 20mA
-
Heater
Power supply
[8]
[9]
[10]
Explanation
:
Temperature signal
thyristor
A 4 - 20mA current output is used to drive a Thyristor unit. Thyristor unit
can control the current for a heater.
1st Edition, August 2001
thyristor
Application sheet for Green 300 series controllers
Title
Number:
Heat-Exchanger Temperature control
Purpose
AP35003
Produce hot water with constant temperature by using plate type heat-exchanger.
Application
Hot water for air conditioning and environment
chumber.
Controller
UT350-00
File Name:
Loop Configuration:
Input Range:
Input Type:
Output Type:
Set-point:
ID parameters
Pump
Interlock
0 - 100.0deg C
Pt100ohm
Current Output
45deg C
P = 30%
I = 40sec.
D = 5sec.
Hi-Alarm
ON at 50deg C
OFF at 48deg C
Alarm action :
UTAP3503.t3d
UT350-00
Hi-Alarm
TIC
Temperature
signal
I/P
Current to
Pneumatic
Converter
Heat
Exchange
r
Hot water
2deg C
Alarm
condition
Very Hot
water
Water
50deg C
Wiring:
UT350-00
Alarm output1
Di2 [18]
Power supply
Explanation
:
[16]
[17]
MV
A
B
B
temperature sensor
+
STOP/RUN
Stop during On
[6] Do1
AL1 [7]
[11]
Temperature Input
[12]
[13]
4 - 20mA
-
control valve
[20]
[8]
[9]
[10]
Alarm set points are displayed on "Select Panel" for easy changing during
operation.
The ID control function will be stoped and a preset signal (0%) will be outputed
when the pump interlock signal will turn to on.
The current output signal is used to drive a control valve.
1st Edition, August 2001
Application sheet for Green 300 series controllers
Number:
Title
Packaged Air Conditioner Temperature control
Purpose
Control ON/OFF valve for cooling water and power switch for Heater to keep the
room temperature.
Application
Packaged Air Conditioner
Controller
UT350-00
AP35004
File Name:
UTAP3504.t3d
Loop Configuration:
Input Range:
0 - 50deg C
Input Range:
Pt100 ohm
Set-point:
25deg C
Deviation Hi-Alarm: 2deg C
Deviation Low-Alarm: 2deg C
Hi-Alarm hysteresis: 0.5deg C
Low-Alarm hysteresis: 0.5deg C
UT350-00
TIC
Temperature
signal
Cooling water
Heater ON AL2 Valve Open AL1
0.5deg C
Hysteresis
Cooling water
0.5deg C
Hysteresis
Heater
Air to Room
Feedback
Room Air
Fan
SP
2deg C
Dead band
HY2
2deg C
Dead band
HY1
Wiring:
UT350-00
Magnetic Switch
Temperature Input
A
Pt100 ohm
B
B
[11]
[12]
[13]
Heater
AL2
[5]
AL1
[6]
[7]
Power supply
SEQ
Cooling water
Valve
[8]
[9]
[10]
Explanation
:
This is a simple Heating / Cooling control example. Model UT350 has a Heating /
Cooling control function; however, two alarm outputs are enough to switch a ON/OFF
valve and a Heater.
1. If PV temperature is higher than (SP+2deg.C), a deviation Hi alarm turnes to ON.
Then, a cooling water valve is opened.
2. If PV temperature is lower than (SP-2deg.C), a deviation Low alarm turnes to ON.
Then, a heater switch is turned to on.
1st Edition, August 2001
Application sheet for Green 300 series controllers
Number:
Title
Tank Level Control
Purpose
Control a Tank level by using a pressure transmitter.
UT350 has a power supply function to a transmitter.
Application
Tank Level Control
Controller
UT350-30
AP35005
File Name:
UTAP3505.t3d
Loop Configuration:
Input Range:
Input Type:
Output Range:
Set-point:
PID parameters
0 - 1,500mm
1.0 - 5.0VDC
UT350-30
4 - 20mADC
Level Signal
LIC
1,200mm
P = 10%
I = OFF
Transmitter
D = OFF
power supply
MR = 0%
MV 4 - 20mA
MR (Manual Reset) is output when PV =SP.
Control Valve
Level
transmitter
Wiring:
UT350-30
12
Pressure Input 13
+
16
+
Power
supply
250ohm
Loop power 21
supply 22
MV 17 4 - 20mA
-
Level transmitter
-
8
9
10
Explanation
Control the tank level by Proportional control with Manual Reset function.
:
Proportional control may occur small offset; however, the control response is
very fast.
UT350 has two types of power supply function to a two-wire transmitter.
All types of UT350 can supply 14.5VDC power to a transmitter.
Model UT350-3_ can supply 21.6VDC power to a transmitter.
A 14.5VDC will be enough for almost all analog type 2-wire transmitter.
A 21.6VDC will be used to drive microprocessor based 2-wire transmitter.
1st Edition, August 2001
Application sheet for Green 300 series controllers
Number:
Title
Pump outlet pressure control
Purpose
Control the voltage & frequency of a pump to control the pump outlet pressure.
Application
Pump outlet pressure control
Controller
UT350-00
AP35006
File Name:
UTAP3506.t3d
Loop Configuration:
Input Range:
Input Type:
Output Range:
Set-point:
PID parameters
0 - 1.00 MPa
0.40 - 2.00 VDC
4 - 20mADC
0.7MPa
P =150%
I = 20sec.
D = OFF
UT350-00
PIC
Pressure Input
Transmitter
power supply
MV
4 - 20mA
R
Start Signal
Inverter
Pressure
transmitter
P
Wiring:
UT350-00
[20]
MV
-
Loop power supply
[16]
4 - 20mA
[17]
[8]
[9]
[10]
Pressure
transmitter
+
Power supply
Pressure Input
100 ohm
+
[12]
[13]
[14]
[15]
RUN/STOP signal
[18]
ON: STOP
Di2
P
-
Inverter
Explanation
Model UT350 has a RUN/STOP function.
:
RUN mode(Di is ON):
STOP mode(Di2 is OFF):
PID control
PID computation is stopped.
Preset MV is outputed as MV.
UT350 can control the pump pressure without overshoot, because control
output starts from 0%.
UT350 can supply 14.5VDC power to a transmitter.
1st Edition, August 2001