Switchgear
Technical Data
TD280015EN
Effective July 2015
Supersedes R280-90-18 8/2012
COOPER POWER
SERIES
Communications Point Data Base
for Serial and Ethernet Communications Protocol DNP3
For use with Eaton’s Cooper Power series
Form 6 Recloser Control
Form 6 DNP3 Device Profile Data Dictionary
Form 6 DNP3 Map Points
July 1, 2015
v3.00
THE INFORMATION CONTAINED IN THIS DOCUMENT IS THE PROPERTY OF EATON.
UNAUTHORIZED REPRODUCTION OR MODIFICATION IS PROHIBITED.
Document
1.00
1.01
Date
5/30/2001
5/30/2001
1.02
1.03
1.04
1.05
5/8/2002
10/30/2002
11/20/2002
8/29/2003
1.06
1.07
2.00
3.00
3/10/2004
10/28/2005
8/24/2012
7/1/2015
Description
Initial release.
Changed wording on SGF "enable" to "block"
Made hot line tag CROBs self-resetting.
Added Binary Input 59 as "CCI:Control Circuit Interrupted"
Added CROBs 18 (Combined Trip / Close) and 19 (Sync-Check Enable)
Changed nomenclature of binary inputs and outputs.
Added TS crob definitions, updated counter & binary
input definitions match the 'DNP Tables at last compilation' file
Added TS binary input and counter definitions
Minor edits in the Class 0 - 3, Binarys tab.
Updates and re-release for ProView 5.0
Updates and re-release for ProView 5.1
Page 1
Cover Page
Form 6 DNP3 Device Profile Data Dictionary
INPUT SUBSYSTEM
Binary Inputs
Description
Recloser Closed
Recloser Open
Control is Locked Out
Any Control or System Alarm
Above Minimum Trip
Supervisory Off
Non-Reclosing
Ground Trip Blocked
SEF Blocked
CLPU Blocked
Fast Trips Blocked
Profile Selected (Normal)
Profile Selected (Alt1)
Profile Selected (Alt2)
Profile Selected (Alt3)
Hot Line Tag
Bus Voltage Present (Phase A)
Bus Voltage Present (Phase B)
Bus Voltage Present (Phase C)
Reverse Power Flow
Battery Test in Progress
No AC Power
Battery Alarm
ci8:Alt1 (TB3:9-10)
ci9:Alt2 (TB3:11-12)
ci10:Alt3 (TB3:13-14)
ci11:Nrml (TB3:15-16)
co1:aux (TB1:11-12,13)
co2:ok (TB1:14-15)
co3:hlt (TB1:16-17)
co4:gtb (TB1:18-19)
ss1:lo (TB1:9-10)
co5:nr (TB3:17-18)
co6:alm (TB3:19-20,21)
co7:nrm (TB4:1-2)
co8:alt1 (TB4:3-4)
co9:alt2 (TB4:5-6)
co10:alt3 (TB4:7-8)
co11:frq (TB4:9-10)
co12:vlt (TB4:11-12,13)
Reclose Retry Enabled
Default Static Variation
Obj 01 Var 01 Binary input w/o status
Index
00
01
02
03
04
05
06
07
08
09
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
Default Event Variation
Obj 02 Var 2 Binary input with time
Default
Hex Index Event
Class
00
01
02
03
04
05
06
07
08
09
0A
0B
0C
0D
0E
0F
10
11
12
13
14
15
16
17
18
19
1A
1B
1C
1D
1E
1F
20
21
22
23
24
25
26
27
28
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Page 2
Class 0 - 3, Binarys
Form 6 DNP3 Device Profile Data Dictionary
INPUT SUBSYSTEM
Binary Inputs
Description
A Phase Fault Trip
B Phase Fault Trip
C Phase Fault Trip
Ground Fault Trip
SEF Trip
ci1:RTrip (TB1:3-4)
ci2:SClose (TB1:5-6)
ci3:STrip (TB1:7-8)
ci4:GTB (TB3:1-2)
ci5:NRecl (TB3:3-4)
ci6:TargR (TB3:5-6)
ci7 (TB3:7-8)
Ground Overcurrent Alarm
Phase Overcurrent Alarm
Negative Sequence Overcurrent Alarm
Hot Line Tag On from Workbench
Hot Line Tag On from Communications
Hot Line Tag On from Front Panel Switch
Control Circuit Interrupted
Default Static Variation
Obj 01 Var 01 Binary input w/o status
Index
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
Default Event Variation
Obj 02 Var 2 Binary input with time
Default
Hex Index Event
Class
29
1
2A
1
2B
1
2C
1
2D
1
2E
1
2F
1
30
1
31
1
32
1
33
1
34
1
35
1
36
1
37
1
38
1
39
1
3A
1
3B
1
Page 3
Class 0 - 3, Binarys
Form 6 DNP3 Device Profile Data Dictionary
INPUT SUBSYSTEM
Binary Inputs (Triple-Single)
Description
Recloser Closed (Phase A)
Recloser Open (Phase A)
Control is Locked Out
Any Control or System Alarm
Above Minimum Trip
Supervisory Off
Non-Reclosing
Ground Trip Blocked
SEF Blocked
CLPU Blocked
Fast Trips Blocked
Profile Selected (Normal)
Profile Selected (Alt1)
Profile Selected (Alt2)
Profile Selected (Alt3)
Hot Line Tag
Bus Voltage Present (Phase A)
Bus Voltage Present (Phase B)
Bus Voltage Present (Phase C)
Reverse Power Flow
Battery Test in Progress
No AC Power
Battery Alarm
ci8:Alt1 (TB3:9-10)
ci9:Alt2 (TB3:11-12)
ci10:Alt3 (TB3:13-14)
ci11:Nrml (TB3:15-16)
co1:aux (TB1:11-12,13)
co2:ok (TB1:14-15)
co3:hlt (TB1:16-17)
co4:gtb (TB1:18-19)
ss1:lo (TB1:9-10)
co5:nr (TB3:17-18)
co6:alm (TB3:19-20,21)
co7:nrm (TB4:1-2)
co8:alt1 (TB4:3-4)
co9:alt2 (TB4:5-6)
co10:alt3 (TB4:7-8)
co11:frq (TB4:9-10)
co12:vlt (TB4:11-12,13)
Reclose Retry Enabled
Default Static Variation
Obj 01 Var 01 Binary input w/o status
Index
00
01
02
03
04
05
06
07
08
09
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
Default Event Variation
Obj 02 Var 2 Binary input with time
Default
Hex Index Event
Class
00
01
02
03
04
05
06
07
08
09
0A
0B
0C
0D
0E
0F
10
11
12
13
14
15
16
17
18
19
1A
1B
1C
1D
1E
1F
20
21
22
23
24
25
26
27
28
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Page 4
Class 0 - 3, Binarys (TS)
Form 6 DNP3 Device Profile Data Dictionary
INPUT SUBSYSTEM
Binary Inputs (Triple-Single)
Description
A Phase Fault Trip
B Phase Fault Trip
C Phase Fault Trip
Ground Fault Trip
SEF Trip
ci1:RTrip (TB1:3-4)
ci2:SClose (TB1:5-6)
ci3:STrip (TB1:7-8)
ci4:GTB (TB3:1-2)
ci5:NRecl (TB3:3-4)
ci6:TargR (TB3:5-6)
ci7 (TB3:7-8)
Ground Overcurrent Alarm
Phase A Overcurrent Alarm
Negative Sequence Overcurrent Alarm
Hot Line Tag On from Workbench
Hot Line Tag On from Communications
Hot Line Tag On from Front Panel Switch
Control Circuit Interrupted (Phase A)
Recloser Closed (Phase B)
Recloser Open (Phase B)
Control is Locked Out (Phase B)
Control Circuit Interrupted (Phase B)
Recloser Closed (Phase C)
Recloser Open (Phase C)
Control is Locked Out (Phase C)
Control Circuit Interrupted (Phase C)
Phase B Overcurrent Alarm
Phase C Overcurrent Alarm
Ganged Mode
1-3 Mode
1-1 Mode
USEF Blocked
Profile Selected (Alt 4)
Profile Selected (Alt 5)
Default Static Variation
Obj 01 Var 01 Binary input w/o status
Index
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
61
62
63
64
65
66
67
68
69
70
71
72
73
74
75
Default Event Variation
Obj 02 Var 2 Binary input with time
Default
Hex Index Event
Class
29
1
2A
1
2B
1
2C
1
2D
1
2E
1
2F
1
30
1
31
1
32
1
33
1
34
1
35
1
36
1
37
1
38
1
39
1
3A
1
3B
1
3C
1
3D
1
3E
1
3F
1
40
1
41
1
42
1
43
1
44
1
45
1
46
1
47
1
48
1
49
1
4A
1
4B
1
Page 5
Class 0 - 3, Binarys (TS)
Form 6 DNP3 Device Profile Data Dictionary
INPUT SUBSYSTEM
Counters
Description
Trip Counter (Phase A)
Trip Counter (Phase B)
Trip Counter (Phase C)
Trip Counter (Ground)
Trip Counter (SEF)
Total Trip Counter
Default Static Variation
Obj 20 Var 2 16 bit Counter
Index
00
01
02
03
04
05
Default Event Variation
Obj 22 Var 2 16 bit Counter w/o time
Default
Hex Index Event Deadband
Class
00
01
02
03
04
05
1
1
1
1
1
1
10000
10000
10000
10000
10000
10000
Page 6
Class 0 - 3, Counters
Form 6 DNP3 Device Profile Data Dictionary
INPUT SUBSYSTEM
Counters (Triple-Single)
Description
Trip Counter (Phase A)
Trip Counter (Phase B)
Trip Counter (Phase C)
Trip Counter (Ground)
Trip Counter (SEF)
Total Trip Counter
Operations Counter (Phase A)
Operations Counter (Phase B)
Operations Counter (Phase C)
Default Static Variation
Obj 20 Var 2 16 bit Counter
Index
00
01
02
03
04
05
06
07
08
Default Event Variation
Obj 22 Var 2 16 bit Counter w/o time
Default
Hex Index Event Deadband
Class
00
01
02
03
04
05
06
07
08
1
1
1
1
1
1
1
1
1
10000
10000
10000
10000
10000
10000
10000
10000
10000
Page 7
Class 0 - 3, Counters (TS)
Form 6 DNP3 Device Profile Data Dictionary
INPUT SUBSYSTEM
Analog Inputs
Description
Default Static Variation
Obj 30 Var 2 16 bit
Index
Default Event Variation
Obj 32 Var 2 16 bit w/o time
Default
Division
Hex Index Event
Scale Factor
Class
Units
Deadband
Low
High
Threshold Threshold
A Phase Primary Current Magnitude
B Phase Primary Current Magnitude
C Phase Primary Current Magnitude
3I0 Primary Current Magnitude
00
01
02
03
00
01
02
03
2
2
2
2
10
10
10
10
Amps
Amps
Amps
Amps
100
100
100
100
10
10
10
10
10000
10000
10000
10000
A Phase Primary Voltage Magnitude
B Phase Primary Voltage Magnitude
C Phase Primary Voltage Magnitude
04
05
06
04
05
06
2
2
2
1
1
1
Volts
Volts
Volts
1000
1000
1000
10
10
10
10000
10000
10000
A Phase Power Factor
B Phase Power Factor
C Phase Power Factor
07
08
09
07
08
09
2
2
2
10000
10000
10000
1
1
1
10
10
10
10000
10000
10000
A Phase Primary Apparent Power
B Phase Primary Apparent Power
C Phase Primary Apparent Power
10
11
12
0A
0B
0C
2
2
2
1
1
1
kVA
kVA
kVA
1000
1000
1000
10
10
10
10000
10000
10000
A Phase Primary Real Power
B Phase Primary Real Power
C Phase Primary Real Power
13
14
15
0D
0E
0F
2
2
2
1
1
1
kW
kW
kW
1000
1000
1000
10
10
10
10000
10000
10000
A Phase Primary Reactive Power
B Phase Primary Reactive Power
C Phase Primary Reactive Power
16
17
18
10
11
12
2
2
2
1
1
1
kvar
kvar
kvar
1000
1000
1000
10
10
10
10000
10000
10000
Line Frequency
19
13
1
100
Hz
10
10
10000
A Phase Primary Demand Currents
B Phase Primary Demand Currents
C Phase Primary Demand Currents
20
21
22
14
15
16
2
2
2
10
10
10
Amps
Amps
Amps
100
100
100
10
10
10
10000
10000
10000
Battery Voltage
Battery Current
23
24
17
18
3
3
100
1000
Volts
Amps
5
1
10
10
10000
10000
Page 8
Class 0 - 3, Analog Inputs
Form 6 DNP3 Device Profile Data Dictionary
OUTPUT SUBSYSTEM - Control Output Relay Block Operations and Status
Default Static Variation
Description
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Index Hex Index Obj Var
00
01
02
03
04
05
06
07
08
09
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
00
01
02
03
04
05
06
07
08
09
0A
0B
0C
0D
0E
0F
10
11
12
13
14
15
16
17
18
19
1A
1B
1C
1D
1E
1F
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
01
01
01
01
01
01
01
01
01
01
01
01
01
01
01
01
01
01
01
01
01
01
01
01
01
01
01
01
01
01
01
01
Desc
Operation Type
Operation
(Support)
Mask
CROB
CROB
CROB
CROB
CROB
CROB
CROB
CROB
CROB
CROB
CROB
CROB
CROB
CROB
CROB
CROB
CROB
CROB
CROB
CROB
CROB
CROB
CROB
CROB
CROB
CROB
CROB
CROB
CROB
CROB
CROB
CROB
Self-Resetting
Self-Resetting
Latched
Latched
Latched
Latched
Latched
Self-Resetting
Self-Resetting
Self-Resetting
Self-Resetting
Self-Resetting
Self-Resetting
Self-Resetting
Self-Resetting
Self-Resetting
Self-Resetting
Latched
Self-Resetting
Latched
Latched
Self-Resetting
Self-Resetting
Latched
Latched
Latched
Latched
Latched
Latched
Latched
Latched
Latched
0xff
0xff
0xff
0xff
0xff
0xff
0xff
0xff
0xff
0xff
0xff
0xff
0xff
0xff
0xff
0xff
0xff
0xff
0xff
0xff
0xff
0xff
0xff
0xff
0xff
0xff
0xff
0xff
0xff
0xff
0xff
0xff
Default
Condition
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Conditioned by
Supervisory State Description
(Factory Default)
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
No
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
* Close Mechanism
* Trip Mechanism
Block Reclosing
Block Ground Trip
Block SEF
Block CLPU
Block Fast Trips
* Profile - Normal
* Profile - Alt1
* Profile - Alt2
* Profile - Alt3
* Reset Targets
* Reset Demand Meters
* Reset Alarms
* Test Battery
*, *** Hot Line Tag Set
*, *** Hot Line Tag Reset
Enable Reclose Retry
Combined Trip and Close
Enable Sync Check
Block USEF
* Profile - Alt4
* Profile - Alt5
Not Used
Not Used
Not Used
Not Used
Not Used
Not Used
Not Used
Not Used
Not Used
* Momentary/Self Resetting, always read FALSE
*** Hot Line Tag activates a latching relay in the control "close" circuit.
Crosshatch
indicates point is supervised regardless of setting
Binary Output
Binary Output
Binary Output
00
01
02
00
01
02
10 02
10 02
10 02
Status
Status
Status
* Close Mechanism
* Trip Mechanism
Block Reclosing
Page 9
CROB
Form 6 DNP3 Device Profile Data Dictionary
OUTPUT SUBSYSTEM - Control Output Relay Block Operations and Status
Default Static Variation
Description
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Index Hex Index Obj Var
03
04
05
06
07
08
09
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
03
04
05
06
07
08
09
0A
0B
0C
0D
0E
0F
10
11
12
13
14
15
16
17
18
19
1A
1B
1C
1D
1E
1F
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
02
02
02
02
02
02
02
02
02
02
02
02
02
02
02
02
02
02
02
02
02
02
02
02
02
02
02
02
02
Desc
Status
Status
Status
Status
Status
Status
Status
Status
Status
Status
Status
Status
Status
Status
Status
Status
Status
Status
Status
Status
Status
Status
Status
Status
Status
Status
Status
Status
Status
Operation Type
Operation
(Support)
Mask
Default
Condition
Conditioned by
Supervisory State Description
(Factory Default)
Block Ground Trip
Block SEF
Block CLPU
Block Fast Trips
* Profile - Normal
* Profile - Alt1
* Profile - Alt2
* Profile - Alt3
* Reset Targets
* Reset Demand Meters
* Reset Alarms
* Test Battery
*, *** Hot Line Tag Set
*, *** Hot Line Tag Reset
Enable Reclose Retry
Combined Trip and Close
Enable Sync Check
Block USEF
* Profile - Alt4
* Profile - Alt5
Not Used
Not Used
Not Used
Not Used
Not Used
Not Used
Not Used
Not Used
Not Used
* Momentary/Self Resetting, always read FALSE
*** Hot Line Tag activates a latching relay in the control "close" circuit.
Page 10
CROB
Form 6 DNP3 Device Profile Data Dictionary
OUTPUT SUBSYSTEM - Control Output Relay Block Operations and Status (Triple-Single)
Default Static Variation
Description
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Index Hex Index Obj Var
00
01
02
03
04
05
06
07
08
09
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
00
01
02
03
04
05
06
07
08
09
0A
0B
0C
0D
0E
0F
10
11
12
13
14
15
16
17
18
19
1A
1B
1C
1D
1E
1F
20
21
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
01
01
01
01
01
01
01
01
01
01
01
01
01
01
01
01
01
01
01
01
01
01
01
01
01
01
01
01
01
01
01
01
01
01
Desc
Operation Type
Operation
(Support)
Mask
CROB
CROB
CROB
CROB
CROB
CROB
CROB
CROB
CROB
CROB
CROB
CROB
CROB
CROB
CROB
CROB
CROB
CROB
CROB
CROB
CROB
CROB
CROB
CROB
CROB
CROB
CROB
CROB
CROB
CROB
CROB
CROB
CROB
CROB
Self-Resetting
Self-Resetting
Latched
Latched
Latched
Latched
Latched
Self-Resetting
Self-Resetting
Self-Resetting
Self-Resetting
Self-Resetting
Self-Resetting
Self-Resetting
Self-Resetting
Self-Resetting
Self-Resetting
Latched
Self-Resetting
Latched
Latched
Latched
Latched
Latched
Latched
Latched
Latched
Latched
Latched
Self-Resetting
Self-Resetting
Latched
Self-Resetting
Self-Resetting
0xff
0xff
0xff
0xff
0xff
0xff
0xff
0xff
0xff
0xff
0xff
0xff
0xff
0xff
0xff
0xff
0xff
0xff
0xff
0xff
0xff
0xff
0xff
0xff
0xff
0xff
0xff
0xff
0xff
0xff
0xff
0xff
0xff
0xff
Default
Condition
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Conditioned by
Supervisory State Description
(Factory Default)
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
No
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
* Close Mechanism (Phase A)
* Trip Mechanism (Phase A)
Block Reclosing
Block Ground Trip
Block SEF
Block CLPU
Block Fast Trips
* Profile - Normal
* Profile - Alt1
* Profile - Alt2
* Profile - Alt3
* Reset Targets
* Reset Demand Meters
* Reset Alarms
* Test Battery
*, *** Hot Line Tag Set
*, *** Hot Line Tag Reset
Enable Reclose Retry
Combined Trip and Close (Phase A)
Enable Sync Check
* Trip Mechanism (Phase B)
* Trip Mechanism (Phase C)
* Close Mechanism (Phase B)
* Close Mechanism (Phase C)
* Activate Ganged Mode
* Activate 1-3 Mode
* Activate 1-1 Mode
* Trip All Phases
* Close All Phases
Combined Trip and Close (Phase B)
Combined Trip and Close (Phase C)
Block USEF
* Profile - Alt4
* Profile - Alt5
* Momentary/Self Resetting, always read FALSE
*** Hot Line Tag activates a latching relay in the control "close" circuit.
Crosshatch
indicates point is supervised regardless of setting
Binary Output
00
00
10 02
Status
* Close Mechanism (Phase A)
Page 11
CROB (TS)
Form 6 DNP3 Device Profile Data Dictionary
OUTPUT SUBSYSTEM - Control Output Relay Block Operations and Status (Triple-Single)
Default Static Variation
Description
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Index Hex Index Obj Var
01
02
03
04
05
06
07
08
09
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
01
02
03
04
05
06
07
08
09
0A
0B
0C
0D
0E
0F
10
11
12
13
14
15
16
17
18
19
1A
1B
1C
1D
1E
1F
20
21
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
02
02
02
02
02
02
02
02
02
02
02
02
02
02
02
02
02
02
02
02
02
02
02
02
02
02
02
02
02
02
02
02
02
Desc
Status
Status
Status
Status
Status
Status
Status
Status
Status
Status
Status
Status
Status
Status
Status
Status
Status
Status
Status
Status
Status
Status
Status
Status
Status
Status
Status
Status
Status
Status
Status
Status
Status
Operation Type
Operation
(Support)
Mask
Default
Condition
Conditioned by
Supervisory State Description
(Factory Default)
* Trip Mechanism (Phase A)
Block Reclosing
Block Ground Trip
Block SEF
Block CLPU
Block Fast Trips
* Profile - Normal
* Profile - Alt1
* Profile - Alt2
* Profile - Alt3
* Reset Targets
* Reset Demand Meters
* Reset Alarms
* Test Battery
*, *** Hot Line Tag Set
*, *** Hot Line Tag Reset
Enable Reclose Retry
Combined Trip and Close
Enable Sync Check
* Trip Mechanism (Phase B)
* Trip Mechanism (Phase C)
* Close Mechanism (Phase B)
* Close Mechanism (Phase C)
* Activate Ganged Mode
* Activate 1-3 Mode
* Activate 1-1 Mode
* Trip All Phases
* Close All Phases
Combined Trip and Close (Phase B)
Combined Trip and Close (Phase C)
Block USEF
* Profile - Alt4
* Profile - Alt5
* Momentary/Self Resetting, always read FALSE
*** Hot Line Tag activates a latching relay in the control "close" circuit.
Page 12
CROB (TS)
Technical Data TD280015EN
Communications
Point Data Base

Effective July 2015
Eaton
1000 Eaton Boulevard
Cleveland, OH 44122
United States
Eaton.com
Eaton’s Cooper Power Systems Division
2300 Badger Drive
Waukesha, WI 53188
United States
Eaton.com/cooperpowerseries
© 2015 Eaton
All Rights Reserved