Surge Protection Made Simple™
IEC APPLICATIONS
Figure 2 - Parallel Connection & Fusing
Figure 1 - Series Connection & Fusing
Wiring
Hazardous Voltage
Will cause severe injury or death.
Working on or near energized circuits poses a
serious risk of electrical shock. De-energize all
circuits before installing or servicing this equipment
and follow all prescribed safety procedures.
TN
*
TN
*
*
*
TN/TT Parallel conection
Main Earthing Bar
IEC 61643-1 Type I, Two-Pole
TN & TT System Installation Instructions
Main Earthing Bar
BSPS2255TN(R) & BSPS2255TT(R) Technical Data
Voltage Uc
Ifi
Iimp (10/350μS)
TN
TT
Max. Fuse
Types:
W/O Remote
With Remote
Replacement Modules
Operating Temperature
IP Rating
255V/50Hz
50kA rms
25kA (L
PE), 25kA (N
PE), 50kA (L+N
PE)
25kA (L
N), 50kA (N
PE), 50kA (L+N
PE)
125A gL/gG - Series connection - Figure 1
315A gL/gG - Parallel connection - Figure 2
BSPS2255TN
BSPS2255TT
BSPS2255TNR
BSPS2255TTR
2X - BPS255IEC*
1X - BPS255IEC*
1X - BPS50NPEIEC**
-40°C to +80°C (+60°C Series connection - Fig. 1)
IP20
TT
TT
*
**
*
**
Fuse sizes are suitable for
K=115 70°C or higher rated
cable
Main Earthing Bar
Main Earthing Bar
Fuse sizes are suitable for K=115 70°C
or higher rated cable
Visual Indication Status
Green = Good
Warranty
Red = Replace
Conductors and Busbars for Use in IEC Systems
See document 3A1502 at
www.cooperbussmann.com/surge
for details of limited warranty.
Mechanical Fixing
Fault Indication & Remote Contact Signaling (with modules installed)
Green
Green = Good
Mounting
Phillips Head Driver
Torque to 7 N•m
Red
Red = Replace
Remote Contact Signaling
Testing Remote Contact Signaling (with modules removed)
60/75°C max. 1.5mm2/14AWG
System Installation
Module Replacement
3A1514 ©2010 Cooper Bussmann St. Louis, MO 63178
Publication No. 1542/US Update 12.10 ID-No. 062576
Green
Remove/Test
REMOTE OK
www.cooperbussmann.com
⸘⏷權䩴
CN
㦻幍⮖權₢₩䟄㺣ぴ䲚ⅉ⛧扪嫛⸘
孔✛扭㘴ᇭ㉔權挄⸗⦌⹅㪖⑕✛⸘⏷
屓⸩᧤♑䏶 IEC 60364-5-53
Ed.3.1:…(VDE 0100 䵯唑 534:…) )ᇭ
⦷⸘孔⃚ⓜ㉔權㩴洛幍⮖㢾⚵㦘⮥
捷㗮⧞ᇭⰑ㨫♠䘿↊⇤㗮⧞㒥␅⸒䛤
䡄᧨庆▎扪嫛⸘孔ᇭ㦻幍⮖♹厌䞷ℝ
㦻⸘孔広㢝₼屓⸩䤓ㄣ䞷欕⩮ᇭⰑ㨫
微嘆怔扖広㢝₼䤓㟿⋋᧨⒨㦻幍⮖♙
扭㘴⦷⸒ₙ槱䤓幍⮖㦘♾厌㗮⧞ᇭ㝔
呹㕕㆏㒥劔㟈┷幍⮖⺕⺋咃德摞≬
幐㦜┰⯀㟗ᇭ
3A1514 ©2010 Cooper Bussmann St. Louis, MO 63178
Publication No. 1542/US Update 12.10 ID-No. 062576
www.cooperbussmann.com
Related documents