Download  

Survey
yes no Was this document useful for you?
   Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project

Document related concepts
no text concepts found
Transcript
DD‐NLH‐096 Island Interconnected System Supply Issues and Power Outages Page 1 of 1 1 Q. Please provide the design values of the cables and the projected operating temperatures. 2 3 4 5 A. 6 7 System voltage: 8 9 The cable specifications (design values) are as follows: +‐350 kVdc Continuous bipole power rating 900 MW Converter technology Line Commutated Converter 10 Continuous current rating 1,286 A 11 Five minute overload current rating 2,572 A 12 13 The maximum cable operating temperature is 55 degrees Celsius. 
Related documents