Survey
* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project
* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project
BALANCED THREE-PHASE CIRCUITS Osman Parlaktuna Osmangazi University Eskisehir, TURKEY BALANCED THREE-PHASE VOLTAGES A set of balanced three-phase voltages consists of three sinusoidal voltages that have identical amplitudes and frequencies but are out of phase with each other by exactly 1200. The phases are referred to as a, b, and c, and usually the a-phase is taken as the reference. abc (positive) phase sequence: b-phase lags a-phase by 1200, and Vc-phase leads a-phase by 1200. c Va Vm 00 Va Vb Vm -1200 Vc Vm + 1200 Vb Circuit Analysis II Spring 2005 Osman Parlaktuna acb (negative) phase sequence: b-phase leads a-phase by 1200, and c-phase lags a-phase by 1200. Vb Va Vm 00 Va Vb Vm + 1200 Vc Vm -1200 Vc Another important characteristic of a set of balanced three-phase voltages is that the sum of the voltages is zero. Va Vb Vc 0 Circuit Analysis II Spring 2005 Osman Parlaktuna THREE-PHASE VOLTAGE SOURCES A three-phase voltage source is a generator with three separate windings distributed around the periphery of the stator. The rotor of the generator is an electromagnet driven at synchronous speed by a prime mover. Rotation of the electromagnet induces a sinusoidal voltage in each winding. The phase windings are designed so that the sinusoidal voltages induced in them are equal in amplitude and out of phase with each other by 1200. The phase windings are stationary with respect to the rotating electromagnet. Circuit Analysis II Spring 2005 Osman Parlaktuna There are two ways of interconnecting the separate phase windings to form a 3-phase source: in either a wye (Y) or a delta (). Circuit Analysis II Spring 2005 Osman Parlaktuna ANALYSIS OF THE Y-Y CIRCUIT VN VN Van VN Vbn VN Vcn 0 Z0 Z A Z1a Zga ZB Z1b Zgb ZC Z1c Zgc Circuit Analysis II Spring 2005 Osman Parlaktuna BALANCED THREE-PHASE CIRCUIT The voltage sources form a set of balanced threephase voltages, this means Va,n, Vb,n, Vc,n are a set of balanced three-phase voltages. The impedance of each phase of the voltage source is the same: Zga=Zgb=Zgc. The impedance of each line conductor is the same: Z1a=Z1b=Z1c. The impedance of each phase of the load is the same: ZA=ZB=ZC There is no restriction on the impedance of the neutral line, its value has no effect on the system. Circuit Analysis II Spring 2005 Osman Parlaktuna If the circuit is balanced, the equation can be written as VN ( 1 1 V Vbn Vcn ) a n Z0 Z Z Z Z A Z1a Z ga ZB Z1b Z gb ZC Z1c Z gc Since the system is balanced, Va n Vbn Vcn 0 and VN 0 This is a very important result. If VN=0, there is no potential difference between n and N, consequently the current in the neutral line is zero. Hence we may either remove the neutral line from a balanced Y-Y circuit (I0=0) or replace it with a perfect short circuit between n and N (VN=0). Both are convenient to use when modeling balanced 3-phase circuits. Circuit Analysis II Spring 2005 Osman Parlaktuna When the system is balanced, the three line currents are Van Vbn Vcn IaA , IbB , IcC Z Z Z The three line currents from a balanced set of three-phase currents, that is, the current in each line is equal in amplitude and frequency and is 1200 out of phase with the other two line currents. Thus, if we calculate IaA and know the phase sequence, we can easily write IbB and IcC. Circuit Analysis II Spring 2005 Osman Parlaktuna SINGLE-PHASE EQUIVALENT CIRCUIT We can use line current equations to construct an equivalent circuit for the a-phase of the balanced Y-Y circuit. Once we solve this circuit, we can easily write the voltages and currents of the other two phases. Caution: The current in the neutral conductor in this figure is IaA, which is not the same as the current in the neutral conductor of the balanced three-phase circuit, which is I0=IaA+IbB+IcC Circuit Analysis II Spring 2005 Osman Parlaktuna LINE-TO-LINE AND LINE-TONEUTRAL VOLTAGES The line-to-line voltages are VAB, VBC, and VCA. The line-to-neutral voltages are VAN, VBN, and VCN. Using KVL VAB VAN VBN VBC VBN VCN VCA VCN VAN For a positive (abc) phase sequence where a-phase taken as reference VAN V 00 VBN V -1200 VCN V + 1200 Circuit Analysis II Spring 2005 Osman Parlaktuna VAB V 00 V -1200 3V 300 VBC V -1200 V 1200 3V - 900 VAB V 1200 V 00 3V 1500 • The magnitude of the line-to-line voltage is 3 times the magnitude of the line-to-neutral voltage. • The line-to-line voltages form a balanced three-phase set of voltages. •The set of line-to-line voltages leads the set of line-to-neutral voltages by 300 •For a negative sequence, the set of line-to-line voltages lags the set of line-to-neutral voltages by 300 Circuit Analysis II Spring 2005 Osman Parlaktuna EXAMPLE A balanced three-phase Y-connected generator with positive sequence has an impedance of 0.2+j0.5 Ω/ and an internal voltage of 120V/ . The generator feeds a balanced three-phase Y-connected load having an impedance of 39+j28 Ω/. The line connecting the generator to the load is 0.8+j1.5 Ω/. The a-phase internal voltage of the generator is specified as the reference phasor. Calculate the line currents IaA, IbB, IcC 120 00 IaA 2.4 36.870 A 40 + j30 IbB 2.4 156.870 A IcC 2.4 83.130 A Circuit Analysis II Spring 2005 Osman Parlaktuna Calculate the three phase voltages at the load VAN, VBN, VCN VAN (39 j 28)( 2.4 36.87 0 ) 115.22 1.190 V VBN 115.22 121.190 V VCN 115.22 118.810 V Calculate the line voltages VAB, VBC, VCA VAB ( 3 300 )VAN 199.58 28.810V VBC 199.58 - 91.190V VCA 199.58 148.810V Circuit Analysis II Spring 2005 Osman Parlaktuna Calculate the phase voltages at the terminals of the generator Van, Vbn, Vcn Van 120 (0.2 j 0.5)( 2.4 36.87 0 ) 118.9 0.320 V Vbn 118.9 120.320 V Vcn 118.9 119.680 V Calculate the line voltages at the terminals of the generator Vab, Vbc, Vca Vab ( 3 300 )Van 20594 . 29.680V Vbc 20594 . 90.320V Vca 20594 . 149.680V Circuit Analysis II Spring 2005 Osman Parlaktuna Backfill: Resistive Delta/Wye Conversion Circuit Analysis II Spring 2005 Osman Parlaktuna Delta/Wye continued... Circuit Analysis II Spring 2005 Osman Parlaktuna Other way, Wye to Delta... Circuit Analysis II Spring 2005 Osman Parlaktuna ANALYSIS OF THE Y- CIRCUIT If the load in a three-phase circuit is connected in a delta, it can be transformed into a Y by using the to Y transformation. When the load is balanced, the impedance of each leg of the Y is ZY=Z/3. After this transformation, the a-phase can be modeled by the previous method. When a load is connected in a delta, the current in each leg of the delta is the phase current, and the voltage across each leg is the phase voltage. Circuit Analysis II Spring 2005 Osman Parlaktuna To demonstrate the relationship between the phase currents and line currents, assume a positive phase sequence and IAB I 00 , IBC I -1200 , ICA I 1200 IaA I AB ICA I 00 I 1200 3I - 300 IbB IBC I AB I -1200 I 00 3I -1500 IcC ICA IBC I 1200 I -1200 3I 900 The magnitude of the line currents is 3 times the magnitude of the phase currents and the set of line currents lags the set of phase currents by 300. For the negative sequence, line currents lead the phase currents by 300. Circuit Analysis II Spring 2005 Osman Parlaktuna Positive sequence Circuit Analysis II Negative sequence Spring 2005 Osman Parlaktuna EXAMPLE The Y-connected load of the previous example feeds a -connected load through a distribution line having an impedance of 0.3+j0.9/. The load impedance is 118.5+j85.8 /. Transforming load into Y and drawing a-phase of the circuit gives 118.5 j85.8 39.5 j 28.6 / 3 Circuit Analysis II Spring 2005 Osman Parlaktuna Calculate the line currents IaA, IbB, and IcC 120 00 IaA 2.4 36.870 A 40 j30 IbB 2.4 156.870 A IcC 2.4 8313 . 0A Calculate the phase voltages at the load terminals: Because the load is connected, the phase voltages are the same as the line voltages. VAN (39.5 j 28.6)( 2.4 36.870 ) 117.04 0.960V VAB 3 300 VAN 202.72 29.040V VBC 202.72 90.960V VCA 202.72 149.040V Circuit Analysis II Spring 2005 Osman Parlaktuna Calculate the phase currents of the load. I AB IBC 1 300 IaA 139 . 6.870 A 3 = 139 . 126.870 A ICA 139 . 11313 . 0A Calculate the line voltages at the source terminals Van (39.8 j 29.5)(2.4 36.870 ) 118.9 - 0.320V Vab 3 300 Van 20594 . 29.680V Vbc 20594 . 90.320V Vca 20594 . 149.680V Circuit Analysis II Spring 2005 Osman Parlaktuna AVERAGE POWER IN A BALANCED Y LOAD PA VAN IaA cos(vA iA ) PB VBN IbB cos(vB iB ) PC VCN IcC cos(vC iC ) In a balanced three-phase system, the magnitude of each line-to-neutral voltage is the same as is the magnitude of each phase current. The argument of the cosine functions is also the same for all three phases. V VAN VBN VCN I IaA IbB IcC vA iA vB iB vC iC Circuit Analysis II Spring 2005 Osman Parlaktuna For a balanced system, the power delivered to each phase of the load is the same PA PB PC P V I cos PT 3P 3V I cos PT 3( VL ) I L cos 3VL I L cos 3 Where PT is the total power delivered to the load. Circuit Analysis II Spring 2005 Osman Parlaktuna COMPLEX POWER IN A BALANCED Y LOAD Reactive power in a balanced system Q V I sin QT 3Q 3V I sin Complex power in a balanced system S VAN I*aA VBN I*bB VCN I*cC V I* S P jQ V I* ST 3S 3VL I L Circuit Analysis II Spring 2005 Osman Parlaktuna POWER CALCULATIONS IN A BALANCED DELTA LOAD PAB VAB I AB cos(vAB ivAB ) PBC VBC IBC cos(vBC ivBC ) PCA VCA ICA cos(vCA ivCA ) For a balanced system VAB VBC VCA V I AB IBC ICA I vAB iAB vBC iBC vCA iCA PAB PBC PCA P V I cos Circuit Analysis II Spring 2005 Osman Parlaktuna PT 3P 3V I cos IL PT 3( )VL cos 3VL I L cos 3 Q V I sin QT 3Q 3V I sin S P jQ V I* ST 3S 3VL I L Circuit Analysis II Spring 2005 Osman Parlaktuna INSTANTANEOUS POWER IN THREE-PHASE CIRCUITS In a balanced three-phase circuit, the total instantaneous power is invariant with time. Thus the torque developed at the shaft of a three-phase motor is constant, which means less vibration in machinery powered by three-phase motors. Considering a-phase as the reference, for a positive phase sequence, the instantaneous power in each phase becomes pA v AN iaA Vm Im cos t cos(t ) pB v BN ibB Vm Im cos(t 1200 )cos(t 1200 ) pC vCN icC Vm I m cos(t 1200 )cos(t 1200 ) pT pA pB pC 15 . Vm I m cos Circuit Analysis II Spring 2005 Osman Parlaktuna EXAMPLE A balanced three-phase load requires 480 kW at a lagging power factor of 0.8. The line has an impedance of 0.005+j0.025/. The line voltage at the terminals of the load is 600V Calculate the magnitude of the line current. 600 * IaA (160 j120)103 3 I*aA 577.35 36.870 A Single phase equivalent Circuit Analysis II IaA 577.35 - 36.870 A I L 577.35 A Spring 2005 Osman Parlaktuna Calculate the magnitude of the line voltage at the sending end of the line. 600 Van VAN ZLIaA ( 0.005 j 0.025)(577.35 - 36.870 ) 3 357.51 157 . 0V VL 3 Van 619.23V Calculate the power factor at the sending end of the line pf cos[157 . 0 ( 36.870 )] = cos 38.440 0.783 Lagging Circuit Analysis II Spring 2005 Osman Parlaktuna EXAMPLE Determine all the load currents: Transforming to Y as 60/3=20, and drawing aphase of the circuit gives: 120 00 IaA 7.5 00 Arms 4 20 // 30 VAN (7.5 00 )(12) 90 00Vrms Circuit Analysis II Spring 2005 Osman Parlaktuna In the original Y connected load I AN IBN 90 00 3 00 Arms 30 3 - 1200 Arms ICN 3 1200 Arms For the original delta-connected load VAB 90 3 0 0 30 0 155.88 300 Vrms I AB IBC 155.88 30 0 2.6 300 Arms 60 2.6 90 0 Arms ICA 2.6 1500 Arms Circuit Analysis II Spring 2005 Osman Parlaktuna Unbalanced Three Phase Systems An unbalanced system is due to unbalanced voltage sources or unbalanced load. In a unbalanced system the neutral current is NOT zero. Unbalanced three phase Y connected load. Line currents DO NOT add up to zero. In= -(Ia+ Ib+ Ic) ≠ 0 Eeng 224 ‹#› Eeng 224 ‹#› Three Phase Power Measurement Two-meter method for measuring three-phase power Eeng 224 ‹#› Residential Wiring Single phase three-wire residential wiring Eeng 224 ‹#›