Download Three-Phase Transformer Inductance Matrix Type (Two Windings)

Survey
yes no Was this document useful for you?
   Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Document related concepts
no text concepts found
Transcript
1
Basic transformer model
L11 and L22 are the self-inductance of winding 1 and 2 respectively, and L12 and
L21 are the mutual inductance between the windings.
2
Basic transformer model
Example: Consider a transformer with a 10% leakage reactance
equally divided between the two windings and a magnetising current
of 0.01 p.u.
3
Basic transformer model
4
Numerical implementation
5
Numerical implementation
6
Numerical implementation
Transformer equivalent after discretisation
7
Modelling of non-linearities
Typical studies requiring the modelling of saturation are: Inrush
current on energising a transformer, steady-state overvoltage
studies, core-saturation instabilities and ferro-resonance.
8
Modelling of non-linearities
to impose a decay time on the inrush currents, as would occur on
energisation or fault recovery:
9
Three-Phase Transformer Inductance Matrix Type
(Two Windings)
The phase windings of the transformer are numbered as
follows:
1 and 4 on phase A
2 and 5 on phase B
3 and 6 on phase C
other phase (This core geometry implies that phase winding 1 is coupled to all
windings (2 to 6)
10
Three-Phase Transformer Inductance Matrix Type
(Two Windings)
Transformer Model
The Three-Phase Transformer Inductance Matrix Type:
11
Three-Phase Transformer Inductance Matrix Type
(Two Windings)
R1 to R6 represent the winding resistances.
 The self inductance terms Lii and the mutual inductance terms Lij
are computed from the voltage ratios, the inductive component of the
no load excitation currents and the short-circuit reactances at nominal
frequency.
Two sets of values in positive-sequence and in zero-sequence allow
calculation of the 6 diagonal terms and 15 off-diagonal terms of the
symmetrical inductance matrix.
12
Three-Phase Transformer Inductance Matrix Type
(Two Windings)
The self and mutual terms of the (6x6) L matrix are obtained from
excitation currents (one three-phase winding is excited and the other
three-phase winding is left open) and from positive- and zerosequence short-circuit reactances X112 and X012 measured with threephase winding 1 excited and three-phase winding 2 short-circuited.
13
Three-Phase Transformer Inductance Matrix Type
(Two Windings)
Q11= Three-phase reactive power absorbed by winding 1 at no load when
winding 1 is excited by a positive-sequence voltage Vnom1 with winding 2
open
Q12= Three-phase reactive power absorbed by winding 2 at no load when
winding 2 is excited by a positive-sequence voltage Vnom2 with winding 1
open
X112= Positive-sequence short-circuit reactance seen from winding 1
when winding 2 is short-circuited
Vnom1, Vnom2= Nominal line-line voltages of windings 1 and 2
14
Three-Phase Transformer Inductance Matrix Type
(Two Windings)
15
Three-Phase Transformer Inductance Matrix Type
(Two Windings)
Extension from the following two (2x2) reactance matrices in positive-sequence
and in zero-sequence
16
Three-Phase Transformer Inductance Matrix Type
(Two Windings)
In order to model the core losses (active power P1 and P0 in positive- and zerosequences), additional shunt resistances are also connected to terminals of one of
the three-phase windings. If winding 1 is selected, the resistances are computed as:
17
Three-Phase Transformer Inductance Matrix Type
(Two Windings)
18
Three-Phase Transformer Inductance Matrix Type
(Two Windings)
19
Three-Phase Transformer Inductance Matrix Type
(Two Windings)
20
UMEC (Unified Magnetic Equivalent Circuit) model
Single-phase UMEC model
21
UMEC (Unified Magnetic Equivalent Circuit) model
Single-phase UMEC model
22
UMEC (Unified Magnetic Equivalent Circuit) model
Three-limb three-phase UMEC
23
UMEC (Unified Magnetic Equivalent Circuit) model
Three-limb three-phase UMEC
24
Related documents