Download Diapositive 1 - Schneider Electric

Survey
yes no Was this document useful for you?
   Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Document related concepts

General Electric wikipedia , lookup

Alternating current wikipedia , lookup

Grid energy storage wikipedia , lookup

Rectiverter wikipedia , lookup

Distributed generation wikipedia , lookup

Transcript
EM3500 Project Overview
Version 1.4 (GKR)
Schneider Electric
Sept 2011
1
EM3500 Family of Energy Meters
● Compact meter with ANSI 12.20 0.5% accuracy
● Reactive energy class 2%
● DIN-rail or wall mounting
● Built in backlit LCD display
● Simplifies set-up
● Allows you to easily verify installation and troubleshoot problems
● Provides easy access to all measurement data
● All models support a wide range of measurement applications
● 90-600V CATIII directly, up to 32,000V w/PTs
● 5-32,000 Amps
● Single phase, split-phase, 3—phase (delta or wye)
● All Models provide a full range of data measurements
● Models with the output configurations & protocol to meet your needs
● Modbus, BACnet & LON (coming soon)
● Uses low-voltage CTs (1V or 1/3V)
● Eliminates safety hazard of current-output CTs
● Do not require shorting bars
● Separate 90-600V control power for maximum flexibility
● Use any measurement voltage or separate source, UPS, etc.
● Operating Temperature -30°C to 70°C
Schneider Electric
2
2
Standard Measurements – all Models
● Energy Consumption
● Accumulated totals of all phases for real, reactive and apparent energy
● Real Energy totals for each phase
● Average Power Demand
● Real, reactive and apparent
● Selectable interval length or sync interval to external controller
● Single interval or rolling block average
● Records maximum real, reactive and apparent demand – can be reset when desired
● Instantaneous measurements
● Power
●Real, reactive and apparent
●Sum of phases and by phase
● Voltage - Average of phases and by phase
● Current - Sum of all phases and by phase
● Power factor - Average of all phases and by phase
● Frequency
● Alarms to simply installation and provide problem notification
● Phase loss
● Voltage, current or frequency out of range
● Low power factor
Schneider Electric
3
3
Output/Protocol Configurations
● Pulse output (EM3502)
● Pulse outputs of real and reactive energy consumption
● Real-time alarm output
● All other measurements are available on the built-in display
● Modbus output (EM355x)
● 2-wire RS-485 serial communication with Modbus RTU protocol
● 1200 baud to 38,400 baud
● Also has Pulse Outputs for real energy consumption and real-time alarms
● BACnet output (EM3560)
● 2-wire RS-485 serial comm with BACnet MS/TP protocol
● 9600 baud to 115,200 baud
● Also has two Pulse Inputs to accommodate sensors measuring other forms of energy
● LON (EM3570 – coming soon)
● Bi-direction model with on board data logging
● 2-wire LON FT10 serial communication with LONworks protocol
● Supports the new LONmark SmartEnergy2 utility meter profile
● Includes Lonworks Plug-in for remote configuration, measurement overview & logging
data access
● Also has two Pulse Inputs to accommodate sensors measuring other forms of energy
Schneider Electric
4
4
Native Data Logging Functionality Available
●Built-in data logging (EM3555, EM3560)
● For jobs that specify log data be stored locally on product
● Retrieve data lost when network or controllers are down
● Log up to 3 32-bit measurement variables with full timestamp
● Log up to 10 16-bit measurement variables (EM3555 Modbus model only)
● Select the measurement variables you want to log
● Select the timing intervals you want
● Log up to 5760 records (up to 45 days at 15-minute intervals)
● Wrap or stop when memory fills
Schneider Electric
5
5
EM3500SERIES ACCESSORIES
Schneider Electric
6
EM3500 Series Accessories
● Low-Voltage (0-1/3 V) Split-Core CTs
Part Number Current
LVCT00102 100 A
LVCT00202 200 A
LVCT00302 300 A
LVCT00403 400 A
LVCT00603 600 A
LVCT00803 800 A
LVCT00804 800 A
LVCT01004 1000 A
LVCT01204 1200 A
LVCT01604 1600 A
LVCT02004 2000 A
LVCT02404 2400 A
Frequency
50 / 60 Hz
50 / 60 Hz
50 / 60 Hz
50 / 60 Hz
50 / 60 Hz
50 / 60 Hz
50 / 60 Hz
50 / 60 Hz
50 / 60 Hz
50 / 60 Hz
50 / 60 Hz
50 / 60 Hz
0.34 kg
0.34 kg
0.34 kg
0.58 kg
0.58 kg
0.58 kg
0.87 kg
0.87 kg
0.87 kg
0.87 kg
0.87 kg
0.87 kg
Weight
Solid-Core LVCTs Coming in 2012
• 50A
• 100A
• 200A
• 400A
• 800A
● 1V CTs are supported as well, but default setting is 1/3V
● Fuse Packs – EMFP1, EMFP2, EMFP3
● NEMA 4 housing
● Lock & Keys for NEMA 4 housing (requires user installation)
Schneider Electric
7
EM3555 BI-DIRECTIONAL
ENERGY METER
Schneider Electric
8
EM3555 Bi-directional Energy Meter
● All the benefits of EM3500 family
● All EM3500 family common measurements
● Additionally measures both energy delivered and energy
received
● Full four-quadrant measurement of Reactive Energy
● Modbus models additionally support Sun-Spec-compliant
register blocks
● Common Sun-Spec 1.0 register block
● Meter model Sun-Spec 1.1 register block
● CSI approved
● Great for applications with solar, wind, local generation
sources
● Also used for applications utilizing re-generative braking
(elevators, etc.)
Schneider Electric
9
9
Additional Bi-directional Data Measurements
●Accumulated Energy measurements
● Real Energy
●Net Real Energy (Import – Export)
●Real Energy Imported – by phase and total
●Real Energy Exported – by phase and total
● Reactive Energy
●Net Reactive Energy (Import – Export)
●Quadrant 1 Reactive Energy (Lagging Imported - Inductive) – by phase and total
●Quadrant 2 Reactive Energy (Leading Exported - Capacitive) – by phase and total
●Quadrant 3 Reactive Energy (Lagging Exported - Capacitive) – by phase and total
●Quadrant 4 Reactive Energy (Leading Imported - Inductive) – by phase and total
● Apparent Energy
●Net Apparent Energy (Import – Export)
●Apparent Energy Imported – by phase and total
●Apparent Energy Exported – by phase and total
●Maximum Demand (average power over Demand interval)
●Total Imported Real Power Maximum Demand
●Total Imported Reactive Power Maximum Demand
●Total Imported Apparent Power Maximum Demand
●Total Exported Reactive Power Maximum Demand
●Total Exported Real Power Maximum Demand
●Total Exported Apparent Power Maximum Demand
Schneider Electric
10
10
EM3560 BACNET ENERGY METER
Schneider Electric
11
EM3560 – Native BACnet MS/TP
Has measurement capability comparable to
EM3550 (with logging added)
Key Differentiators from other BACnet meters:
● Native BACnet MS/TP protocol
● 115.2 kbaud serial communications
● Pulse Inputs for other Energy sensors
● Native Trend_Log objects (data logging)
● Local LCD Display & User Interface
What customer benefits do these provide?
Schneider Electric
12
12
Native BACnet MS/TP protocol
• Native - built into the meter – does not require a separate
gateway and power supply
• BACnet MS/TP – as compared to BACnet IP – most
meters that support BACnet only support BACnet IP
● Most customers WANT BACnet MS/TP rather than BACnet IP
– Adding a device with BACnet IP requires a separate network drop
on a particular subnet and a dedicated IP address – the installer
must request these from the customer’s IT group
– Adding a device with BACnet MS/TP can be done easily by the
installer using a shielded twisted pair that they can run themselves
● To get BACnet IP support, simply add a BACnet router to one or
more EM3560 Meters
Schneider Electric
13
13
115.2 kbaud Serial Comm
● A commonly requested feature on other BACnet
products is faster baud rate support
● A serial (MS/TP) link with multiple devices can only
operate as fast as the slowest device
● Many BACnet system builders prefer to operate
their serial links at 76.8 kbaud
● The EM3560 supports this and also adds 115.2
kbaud
Schneider Electric
14
14
Pulse Inputs for other Energy
sensors
● The Modbus protocol is heavily used by Energy Management systems.
● Pulse outputs on Modbus EM355x models let BAS/BMS systems access
Energy Consumption while the Energy Management system utilizes the
full data set of a meter.
● Since BACnet is primarily used by BAS/BMS systems, the need for
additional output is not common.
● BAS/BMS systems that monitor energy consumption want to see all
forms energy consumption
● Electrical
● Natural Gas
● Hot Water
● Chilled Water
● Steam
● The EM3560 provides 2 pulse inputs with accumulators (energy
counters) that can be connected to simple flow sensors with pulse
outputs, and make their accumulated energy readings available via
BACnet.
Schneider Electric
15
15
Native Data Logging
●Some system designs specify local storage of measurement history
on device
●Can be recovered later if local controller or communication link fails
●Customers can always set up external Trend Logs on local
controllers, but they only store when the local controllers and
communication link are operating
●EM3560 has three native Trend log objects
● Each stores up to 5760 time-stamped records (60 days at 15 min intervals)
● Log interval is tied internally to demand interval
● Each object can be pointed to any of the 52 Data values
● Timestamps do rely on our real-time clock, which does not have a battery
backup
●Software must generate a BACnet Time_Synchronization event when EM3560 power is
restored
●An alarm bit (Binary_Object) is provided to indicate if this is needed
Schneider Electric
16
16
LCD Display & User Interface
●Simplifies setup & commissioning
●Enter or view the Device ID directly
●Set up Comm parameters
●Many MS/TP products require a PC, special cables,
custom software, etc.
Schneider Electric
17
17
EM3560
BACnet
Energy Meter
Programming
Model
Object_Identifier
x,xxx,xxx
Object_Type
Object_Name
Vendor_Name
Vendor_Identifier
Model_Name
Firmware_Revision
Application_Software_ Version
Location
Description
Protocol_Version
Protocol_Revsion
Local_Date
Local_Time
Segmentation_Supported
Max_Master
Max_Info_Frames
Max_APDU_Length_Accepted
APDU_Timeout
Number_of_APDU_Retries
System_Status
Protocol_Sevices_Supported
Protocol_Object_Types_ Supported
Device
Veris E50 Series Energy Meter - S/N: <serial number>
Veris Industries, LLC
133
EM3560 Energy Meter
“xyyy”.
“RS= xyyy, OS=xyyy, BACnet Gateway=xyyy”
<Location>
Veris EM3560 DIN-Rail Energy Meter S/N <serial number>
1
4
Date
Time
NO_SEGMENTATION (3)
1-127 (Factory Default is 127)
1
480
60000
0
Operational (0)
0b0000000000001011010000000000000011110000
0b1011000010000000000010000000000
Object_List
DE1,AI1,AI2,AI3,AI4,AI5,AI6,AI7,AI8,AI9,AI10,AI11,AI12,AI1
3,AI14,AI15,AI16,AI17,AI18,AI19,AI20,AI21,AI22,AI23,AI2
4,AI25,AI26,AI27,AI28,AI29,AI30,AI31,AI32,AI33,AI34,AI3
5,AI36,AI37,AI38,AI39,AI40,AI41,AI42,AI43,AI44,AI45,AI4
6,AI47,AI48,AI49,AI50,AI51,AI52,AV1,AV2,AV3,AV4,AV5,A
V6,AV7,AV8,AV9,AV10,AV11,BI1,BI2,BI3,BI4,BI5,BI6,BI7,B
I8,BI9,BI10,BI11,BI12,BI13,BI14,BI15,TR1,TR2,TR3
Device_Address_Binding
Database_Revsion
{}
0
(1) Device object:
(3) Trend_Log objects:
5760 Timestamped Log Records
TL3 - Total Real Power Present Demand
TL2 - Reactive Energy Consumption
TL1 - Real Energy Consumption
•
•
•
•
•
•
•
•
•
1-13-2011 1:00:00 - x.xxxxx kWh
1-13-2011 1:15:00 - x.xxxxx kWh
1-13-2011 1:30:00 - x.xxxxx kWh
1-13-2011 1:45:00 - x.xxxxx kWh
1-13-2011 2:00:00 - x.xxxxx kWh
1-13-2011 2:15:00- x.xxxxx kWh
…
…
2-22-2011 7:15:00 - x.xxxxx kWh
(11) Analog_Value objects:
(52) Analog_Input objects:
(15) Binary_Input objects:
Writable 32-bit Present_Value
Used for Configuring the meter
Read-only 32-bit Present_Value
Used for Accessing data values
Read-only 1-bit Present_Value
Used for Alarms
AV1
AV2
• Object ID
Config
• Object
Name
System_Type
CT_Ratio_Primary
• Description
CT_Ratio_Secondary
• Present_Value
PT_Ratio
• UnitsSystem_Voltage
Display_Units
Phase_Loss_Voltage_Threshold
• Reliability
AV11
BI1
BI2
AI1
AI2
Phase_Loss_Imbalance_Threshold
Subintervals
Subinterval_Length
Schneider Electric
• Object
ID Volts_BC
Energy
Volts_AC
KW_Total
• Object
Name
KVAR_Total Volts_AN
Volts_BN
KVA_Total
• Description
Volts_CN
PF_Total
Volts_LL_Avg Current_A
• Present_Value
Volts_LN_Avg Current_B
Current_C
• UnitsCurrent_Avg
Reserved_
KW_A
AI24
KW_B
• Reliability
Frequency
KW_C
AI52
PF_A
PF_B
PF_C
Volts_AB
KVA_C
KVAR_A
KVAR_B
KVAR_C
KW_Present_Demand
KVAR_Present_Demand
KVA_Present_Demand
KW_Max_Demand
KVAR_Max_Demand
KVA_Max_Demand
• Object
ID
Volts_Error_A
Volts_Error_B
• Object
Name
Volts_Error_C
Current_Error_A
• Description
Current_Error_A
Current_Error_A
• Present_Value
Frequency_Error
Reserved_BI8
• Reliability
Phase_Loss_A
Phase_Loss_B
Phase_Loss_C
Power_Factor_A
Power_Factor_B
Power_Factor_C
RTC_Error
Pulse_Count_1
KVAh
kVARh
KVA_A
Pulse_Count_2
KVA_B
KWH_C
KWH_A
KWH_B
BI15
18
EM3500
Schneider Electric
19