Survey
* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project
* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project
EWEB EMS Western Premium Economizer Checkout Procedures General Outline; Tests for Honeywell W7459A Economizer Controller; Abbreviated Logic Checks Advanced Tests: (Modules W7412, W7413, W7414, W7415 & W7340) Low Ambient Compressor Lockout; Heat Pump Relay; Demand Controlled Ventilation (DCV); Relief or Exhaust Fan; Post Purge Relay; Anti-Cycle Relay 05/03/2004 Hookup Diagram Index Hookup Unit Type Diagram 1 Gas/Cool 2 3 Gas/Cool Heat Pump Thermostat Economizer Other Controls Controller Mech/Pgm W7459 Fan Delay & Post Purge & Anti-cycle Mech/Pgm W7459 Mechanical W7459 Anti-cycle & Post Purge 4 Heat Pump Mech/Pgm W7459 Post Purge 5 Heat Pump Mech/Pgm W7459 Post Purge 6 Heat Pump Mech/Pgm W7214 Post Purge 7 Heat Pump Mech/Pgm Post Purge 8 Gas/Cool Mech/Pgm 9 Heat Pump Mech/Pgm W7212 (W7215) W7212 (W7215) W7340 10 11 Anti-cycle & Post Purge Post Purge Min OSA Activation Actuator Comments Tstat Ocp Sch A1/A2 (T7200/7300) With Fan Zone Occupancy Sensor(s) Demand Controlled Ventilation (DCV) Tstat Ocp Sch Aux (T7350) Demand Controlled Ventilation (DCV) Tstat Ocp Sch Aux (T7350) Demand Controlled Ventilation (DCV) Demand Controlled Ventilation (DCV) M7415 M7415 M7415 M7415 M7415 M7215 M7415 M7215 M7215 Testing/Sensor Simulator Hydronic cooling Pneumatic Pneumatic Timer Pneu Please contact EWEB EMS to find out more about our Western Premium Outside Air Economizer Program. For questions or comments regarding these hookup diagrams contact Dan Morehouse or Reid Hart, PE. Eugene Water & Electric Board Energy Management Services 500 E 4th Ave PO Box 10148 Eugene OR 97440 Phone 541-484-1125 Fax 541-334-4614 Program Contacts: Dan Morehouse x 3074 Reid Hart x 3079 Need two transformers Critical zone warning light Exhaust/ Relief Fan Need two transformers Exhaust/ Relief Fan Trane Reliatel Economizer Check-Out Procedure Developed by Ecotope in Fall 2002 Modified by EWEB in Spring 2004 Manufacturer-Specific Economizer Testing. The economizer function should be tested to determine that it is functioning correctly. In addition to the functionality of the components, this can include whether or not components are set to preferred settings. In general, manufacturer’s checkout procedures should be used to evaluate the functionality of the components. The data collected in this step is recorded in the “Supplemental Economizer Information” form. A knowledgeable technician can streamline the process but must be vigilant and account for environment and thermostatic conditions. The manufacturer procedures have the advantage of generally completing a checkout the same way, no matter the conditions. In following the manufacturers economizer checkout procedures, there are several conditions to verify that will not be elucidated in the checkout but are critical to the efficient operation of the economizer. They should be noted and repaired as appropriate. The following general instructions are a guide to checkout. See the specific “Supplemental Economizer Information” form instructions for specific assistance. · Verify that the damper is fully closed when the unit is off, and that the minimum air position is set with potentiometer or micro-switch rather than the linkage. On older units without minimum air potentiometers or minimum position switches, the minimum position will necessarily be set with the linkage. · Describe the minimum air setting and verify that the return dampers are completely open in this state. If minimum airflow is very high, then the return dampers should be somewhat closed. · Measure total and outdoor air flow at minimum position. To do this use flow grids or delta-T method. At a minimum, check the cooling coil split temperature with the compressor operating. If it is higher than 25oF it indicates that total air flow is excessively low. If it is lower than 12 or 10oF it indicates that refrigerant charge may be low and should be checked. · Verify that the damper opens completely, and when open, that the return dampers are closed completely. Ideal economizer operation requires the return damper to be completely closed. Typically this is not how they are installed. Linkage should be adjusted to close the return dampers as much as possible without creating building pressurization problems. · Measure total and outdoor air flow at full-open position. Do this by repeating process described previously for minimum position, except first do measurement with flow plates in place and then re-install filters and measure supply pressure for correction. Economizer Checkout 1 April 2004 · Verify that the wiring between the economizer and unit controls is correct with regard to the number of compressor and thermostat stages. Often there is a particular way the economizer should be wired depending upon the staging. This will require familiarity with both the unit and economizer controls, or the ability to quickly read wiring diagrams. Determine the number of cooling thermostat stages, and if the economizer has a dedicated cooling stage. Review Thermostat setpoints and programming. · Verify that the logic controller is okay and that economizer is enabled at the correct conditions. This requires that the logic board is checked and the sensors calibration checked. · Determining the Economizer Logic. Most modern economizers support change over and differential control with dry bulb and enthalpy sensors. Determining the logic used will be unique to each unit. This may involve looking at product literature for unusual set-ups. Items of interest are: · Changeover or differential. Generally, controllers have a terminal for a return air sensor. If the terminal is wired to a sensor then the unit runs in differential mode. If a wire is not connected or the terminals are jumped, then the unit is in changeover. In older units with relay control, you will need to decipher the wiring diagrams and locate the sensors to determine this. · Changeover setting. If a unit uses changeover logic, determine what temperature or setting is used for changeover. On Honeywell controllers with solid state sensors record the A-D setting. If the unit uses a snap disk for outdoor air temperature this setting will not adjust the changeover but record it anyway. On Trane Voyager units there is a switch block that determines the setting. Record the switch settings. · Changeover sensor types. Determine if outside air and return air sensors are drybulb, enthalpy, or dry-bulb with humidity. · Primary control sensor location. Determine if the primary control sensor (low-limit sensor) is in the mixed air position (before the cooling coil) or the discharge air position (after the cooling coil, in the fan scroll, or in the supply air). Economizer Checkout 2 April 2004 Honeywell W7459A Economizer Control Module Publications: Honeywell 63-2141, Honeywell 63-2484, Honeywell 63-2140-2, Honeywell 632499-1. The Honeywell 7459A is the most common economizer controller and comes in a wide variety of configurations. It attaches directly to the actuator, and it can be identified by appearance, in particular the number and pattern of the terminals is deterministic. Publication 63-2484 highlights many, but by no means all, of the common wiring configurations. If the controller is a model 7459B,C or D do not use these procedures. Refer to the above literature for guidance. · Check the SR/+ terminals to determine whether a return air sensor is connected. If so then the controller will use differential logic. If not, a resistor must be jumpered between the terminals and the controller will use change over logic. · Check terminal 1 for wire. This should be the stage 1 cooling wire from the unit control. · Check terminal 3 for stage two wire. Most, but not all, units are wired with Y2 going to 3. The unit wiring diagram will need to be consulted to determine if things are correct. The following tables outline the standard check out procedures recommended by Honeywell. Use non-conducting pliers whenever power is applied to the logic board, and be careful to not yank on wires. This is tricky, as the spades can be quite tight. A lever action works best, using the tips of the pliers to press into the case. Minimum Position Check (Video Test #4) a. Start with all wiring in original position. Disconnect one leg of T/T1. Note: (the C7046A and C1750 sensors have negative temperature coefficients. That means high resistance = low temperature and low resistance = high temperature). b. Characterize found damper positions and measure flows if desired. c. Measure outside, return, and mixed air temperatures. Calculate desired mixed air temperature for desired %. d. Adjust minimum position dial until desired mixed air temp is achieved. c. Restore T/T1. Economizer Checkout 3 This simulates very cold mixed air or supply air The outside air damper should be in or move to minimum position and be adjustable with the minimum air potentiometer unless an external sensor is installed. Note that different units respond differently to the minimum position potentiometer. Trane units with Honeywell controls do not respond until the potentiometer is turned half way and may limit minimum position to 50% or so, while most other units respond immediately. Use formulas or nomograph on pages 16 to 21 of Design & Application Guide for Honeywell Economizer Controls. Verify desired mixed air temperature and position. April 2004 Logic Checkout – Step 1 (Video Test #1a) a. Turn unit power off or disconnect wire from terminal TR1 (common) or TR b. Disconnect one leg of jumper or wire between from P and P1. c. Jumper TR to 1. d. Jumper T1 to T (mixed air sensor) e. If connected remove one leg of the sensor between SO to +. f. Verify 620W resistor or sensor between SR and +. g. Turn power on or restore TR Actuator Closed If pulling wire from TR/TR1, be careful to not ground the wire to other terminals or to any metal. The damper should go completely closed. Removes outside air minimum position signal; minimum is fully closed simulates call for cooling simulates warm mixed air temperature so damper will open all the way when it opens simulates very warm outdoor air temperature simulates mid-range return temperature LED should be off (indicates Economizer is off) and motor should go to or be in closed position. If motor opens verify the resistor or sensor across SR /+ has continuity. Logic Checkout – Step 2 (Video Test #1b) Actuator Open This puts the controller in differential control a. Disconnect factory installed resistor comparing two very warm temperatures. The or sensor lead from SR or + return is interpreted as the higher temperature so the LED should go on (indicates Economizer is enabled) and Motor should drive fully open. If LED goes on but motor doesn’t move, do actuator checkout. If LED is not on then controller is probably bad. Go through the system check out sequence. b. Characterize damper positions and measure flow. Logic Checkout – Step 3 (Video Test #2) Outside Temperature/Enthalpy a. Reconnect resistor or sensor leads to This simulates a mid-range outdoor temperature or SR and +. Connect 1.2K ohm enthalpy. resistor between SO and +. If there is a return air sensor, disconnect and place 620 ohm resistor between SR and +. b. Turn changeover setpoint Sets an aggressive change over setpoint. potentiometer to “A” LED should come on and motor drive open. c. Turn changeover setpoint to “D” Sets a conservative change over setpoint. LED should be off and motor driven closed. d. Disconnect 1.2K ohm resistor and restore system. If the unit does not pass the above test follow the system checkout procedures in publication 632484-1 pages 17-19 to determine the exact cause. Economizer Checkout 4 April 2004 Sensor Check out (multi-meter must be able to read tenths of a milliamp DC). Mixed Air / Supply Air Sensor Checkout a. Disconnect mixed/supply air sensor lead wires from T/T1. b. With ohmmeter, check the resistance across the sensor by connecting meter leads to sensor leads. Measure temperature at mixed air or supply air sensor. Honeywell Pub 60-2350-5. Resistance should correspond to the current mixed air temperature for the installed sensor. The controller typically expects 3.0Kohms at 77F with a 70ohm per degree sensitivity. (3.5Kohms at 70F, 4.0Kohms at 65F, 4.7Kohms at 60F. If measurement deviates from target values, clean all contacts and retest. Outdoor Air Sensor Checkout (Video Test #3) Outside Sensor a. Determine sensor type. Honeywell Pub 63-2140-2 and 63-2499-1 b. If solid state, connect a DC Reading should be between 3-25 mA. milliammeter between terminal SO of If meter indicates 0 check to see if sensor is wired the controller and the S terminal of the backwards. If not then sensor is probably bad. sensor lead (this should be the wire that Detail: Check amp readings with tables in relevant publications to determine that sensor is reading was hooked up to SO. It is also possible to do this at the sensor. The within 5 degrees of the correct temp. If positive meter lead should be on the measurement deviates from target values, clean all sensor lead, negative on the controller contacts and retest. terminal.) c1. If sensor is a snap disk, determine Typically outdoor air snap disks are set to 60F. state of switch with ohmmeter. Above 60F the switch should be open below it should be closed. Note temperature and state of switch. If switch is in wrong position for temperature (within 5 degrees), clean all contacts and retest. If it still switches at the wrong temperature then replace. c2. If snap disk is closed, warm it with Switch should open. If not replace. hand. c3. If snap disk is open, cool it with Switch should close. If not replace. water or ice. Return Air Sensor Checkout b. If return air sensor connected to Reading should be between 3-25 mA. SR/+, connect a DC milliammeter If meter indicates 0 check to see if sensor is wired between terminal SR of the controller back wards. If not then sensor is probably bad. and the S terminal of the sensor lead Detail: Check amp readings with tables in relevant (this should be the wire that was publications to determine that sensor is reading hooked up to SR. It is also possible to within 5 degrees of the correct temp. If do this at the sensor. The positive measurement deviates from target values, clean all meter lead should be on the sensor contacts and retest. lead, negative on the controller terminal.) Economizer Checkout 5 April 2004 Abbreviated Logic Checks Under many conditions all logic functions can be checked using tests that do not require wires to be attached and detached to the controller. Because of the number of control variables extreme care must be exercised to insure valid test results. Test Method 1 Requirements No Heating or Stage two cooling calls present. Outside air conditions between ~55F and 80F Changeover logic Solid State sensor or adjustable electro-mechanical switch (not snap disk) Test Conditions must be such that the “A” setting turns the controller LED on and the “D” setting turns the controller LED off. Or if electromechanical outdoor air sensor is present, conditions must fall in the range of the adjustable setpoint. Simulate a call for cooling (jumper TR to 1). Set the potentiometer to “A” or the changeover temperature to a warm enough temperature to trigger the economizer. At these air conditions the damper should open fully. Set the potentiometer to “D” or the changeover temperature to a cold enough setting to end economizer action. The damper should move to the minimum position. Advanced Module Logic Checks Advanced modules (W7212, W7213, W7214, W7215 or W7340) use the same changeover logic as the basic W7459. Follow the checkout procedures included in the literature supplied with each module. If missing, the literature is available online at http://hbctechlit.honeywell.com/ for Honeywell products and specific manufacturer’s web sites for other products. The basic logic checks are very similar to the W7459 tests previously reviewed. They should verify: · Full physical actuator and damper operation · Actuator closes damper fully · Actuator opens damper fully · Outside temperature changeover checkout · Check sensor current for both outside and return sensors to verify correct connection In addition to the basic logic checks advanced checks for DCV and exhaust fan setting require either a variable 0-10 volt source (see schematic 10 in the hookup diagrams) or at a minimum an 9-volt battery with test leads and a volt meter. Follow the checkout procedures in the literature for the specific module and test: · DCV (ISI for W7215) maximum and minimum · DCV setpoint · Exhaust setpoint if relief fan being used · For CO2 sensors, increased voltage output should be observed when exhaling at the sensor. Remember it may take up to one minute to ramp voltage up or down. Economizer Checkout 6 April 2004 Low Ambient Lockout Checkout For all premium economizers, verify the operation of the low ambient lockout function. · Measure outside air temperature · Set lockout 10oF or more below outside temperature. · Remove one of the leads from the outside sensor (SO or +O) to simulate high outside temperature; the economizer should close to minimum and the free cooling light go out. · Jumper from Red (24V hot) to Y1 and Y2 at the thermostat. · Verify that Y1 (and Y2 for 2- stage cooling) on the system board do NOT have voltage and the compressor is not running. · Reconnect outside sensor (SO and +O) and reset low-ambient lockout to 55oF. Heat Pump Relay Checkout For heat pumps with economizers with normally-heating reversing valves (O terminal), verify the operation of the heat pump function. · If free cooling light is not on: place 620 ohm resistor across SO and +O and 1.2k ohm resistor across SR and +R so that free cooling light is on. · Jumper from Red (24V hot) to G, Y1 and verify no voltage at O at the thermostat or thermostat leads; this simulates a call for heating. · Economizer should not activate and voltage should be present at Y1 system connection; compressor should operate in heating mode. · Jumper from Red (24V hot) to G, Y1 and to O at the thermostat or thermostat leads; this simulates a call for cooling. · Economizer should activate and no voltage should be present at O system connection or Y1; compressor should not operate. · Remove one of the leads (or the resistor) from the outside sensor (SO or +O) to simulate high outside temperature; the economizer should close to minimum and the free cooling light will turn off. · If outside temperature is below ambient lockout, jumper around lockout sensor. · Verify that Y1 (and Y2 for 2- stage cooling) on the system board DO have voltage and the compressor is running in cooling. · Reconnect any sensors and remove jumpers. For heat pumps with economizers with normally-cooling reversing valves (B terminal), verify the operation of the heat pump function. · If free cooling light is not on: place 620 ohm resistor across SO and +O and 1.2k ohm resistor across SR and +R so that free cooling light is on. · Jumper from Red (24V hot) to G, Y1, and B at the thermostat or thermostat leads; this simulates a call for heating. · Economizer should not activate and voltage should be present at Y1 and B system connection; compressor should operate in heating mode. · Jumper from Red (24V hot) to G and Y1 at the thermostat or thermostat leads and make sure there is no voltage at B; this simulates a call for cooling. Economizer Checkout 7 April 2004 · · · · · Economizer should activate and no voltage should be present at Y1 system connection; compressor should not operate. Remove one of the leads (or the resistor) from the outside sensor (SO or +O) to simulate high outside temperature; the economizer should close to minimum and the free cooling light will turn off. If outside temperature is below ambient lockout, jumper around lockout sensor. Verify that Y1 (and Y2 for 2- stage cooling) on the system board DO have voltage and the compressor is running in cooling. Reconnect any sensors and remove jumpers. Demand Controlled Ventilation (DCV) Setting For W7215/W7212/W7213/W7214; confirm with specific module instructions. · Set any jumpers on CO2 Sensor and calibrate. o Take outside or ventilate area without occupancy and use 400 ppm reference and adjust sensor following manufacturers procedures to read 400 ppm o Calibrate to zero with argon/nitrogen or other non- CO2 atmosphere o Automatic calibrating sensors go to 400 ppm at low point on regular schedule · Determine CO2 Sensor voltage output at 1000 ppm setpoint · Set Minimum position to 0% (full left or counter clockwise) and verify jumper on P/P1 · Set DCV Max high (full right or clockwise) · Remove one of the leads from the outside sensor (SO or +O) to simulate high outside temperature; the economizer should close to minimum and the free cooling light go out. · Adjust DCV setpoint so DCV mode is just activated at desired setpoint o Provide setpoint voltage to input or o set by dial gradations · Verify operation one of 3 ways: o Adjust variable voltage sensor simulator to increase voltage above setpoint; damper should open; Adjust variable voltage sensor simulator to reduce voltage below setpoint; damper should close. o Apply 9 volt battery to sensor terminals and damper should open to about 90%; Remove battery from sensor terminals and damper should close. o Exhale on CO2 Sensor a few times and damper should open after about a minute; Ventilate area near sensor and remove people from sensor location and damper should close. · If desired, set minimum. This is not required in most occupancies. o Remove CO2 sensor leads from controller, jumper P/P1, and verify power to controller. o Adjust to desired minimum outside air position. o Determine percentage outside air with temperature or airflow measurement. · For severe climates, it may be desirable to set a maximum setting. o Remove CO2 sensor leads from controller, jumper P/P1, and verify power to controller. o Apply 9 volt battery to sensor terminals and damper should open to about 90%; o Adjust to desired maximum outside air position. Economizer Checkout 8 April 2004 o Determine maximum percentage outside air with temperature or airflow measurement. An existing W7459 controller can be retrofit for demand controlled ventilation as shown in hookup diagram 4. For new installations, it may be better to start with DCV equipped controller like W7212 or W7215. The W7459 requires the following setup procedure: · Must have CO2 sensor with 500 to 2000 ppm range for 0-10 volts (for Honeywell: C7242 programmable or C7232 jumper; AirTest and other manufacturers apply) · Install SEPARATE 24VAC TRANSFORMER for CO2 sensor to avoid confused electronic signals · Connect Q769C converter to P/P1 and to CO2 sensor, watch polarity on sensor and P/P1 connections. Set up the controller as follows: · Jumper P/P1 and adjust the min dial until the outside air damper is full open. In this configuration, the minimum dial becomes the maximum. Watch the full clockwise spot on the dial which sometimes reverts to closing the damper. · Verify desired sensor voltage: 3.3 VDC = 1000 ppm on 0-10 VDC CO2 sensor with range of 500 to 2000 ppm · Connect Q769C to P/P1 and apply desired volts DC (3.3) · Turn Calibration potentiometer on Q769C for DCV almost full clockwise to begin opening at 3.3 VDC. · Adjust Q769C calibration screw counter clockwise until dampers are closed · Connect Sensor Relief or Exhaust Fan Setting Connect exhaust fan relay coil to dry contacts (EF and EF1) on economizer controller. Set to turn on the exhaust fan when dampers are between 60% and 80% open. Post-purge relay · · · Set thermostat fan switch to “Auto” or disconnect fan lead from thermostat. Jumper G terminal at thermostat so fan is operating. Turn off and observe that fan operation continues for one to two minutes. Anti-cycle relay · · · · · Activate cooling at thermostat or jumper R to Y1. Cycle cooling off (or remove jumper) for 5 seconds and cycle back on. Compressor should remain off for three to five minutes before restarting. With cooling activated, cut power to unit for 5 seconds and restore. Compressor should remain off for three to five minutes before restarting. Economizer Checkout 9 April 2004 Western Premium Economizer Outside Air R TR C SO Dry-Bulb Sensor S C7650A + SR Dry-Bulb Sensor S C7650A + Return Air TR TR1 3 Discharge Air Sensor C7150B or C7046A T P D Set changeover dial to "D" for differential Honeywell W7459A Economizer Controller Honeywell M7415 Actuator 2 Measure RA/OA/MA temp to set min. ventilation % 4 T T1 T1 P P1 P1 If A1/A2 not available then jumper P and P1 A1 C A2 Y1 C TR1 SR+ 1 Thermostat Occupancy Dry Contact B SO+ 5 Locate Sensor downstream of DX cooling coil A Low OSA Lockout Y1 Anticycle Cool Y2 W1 Close on Rise at 55 deg F W1 Heat W2 G G RH R Fan Delay Relay Post Purge RC Thermostat Terminals Unit Terminals Hookup Diagram 1: One-Stage Cooling; Gas Heat W7459A Economizer Controller with 2-stage Cooling Thermostat, Low-Ambient Compressor Lockout, and Dry-bulb Differential Changeover Fan 24 VAC EWEB provides suggested wiring for education only. Installer and customer to determine suitability for specific products and application. 4/2004 EWEB EMS 541-484-1125 Western Premium Economizer R TR C Outside Air SO Dry-Bulb Sensor S C7650A + SR Dry-Bulb Sensor S C7650A + Return Air TR TR1 B C D SO+ TR1 Set changeover dial to "D" for differential SR+ Honeywell W7459A Economizer Controller 5 1 3 Locate Sensor downstream of DX cooling coil A T Discharge Air Sensor C7150B or C7046A P Honeywell M7415 Actuator 2 Measure RA/OA/MA temp to set min. ventilation % 4 T T1 T1 P P1 P1 Jumper P and P1 Unit Terminals Thermostat Terminals Y1 C Low OSA Lockout Y1 Cool Y2 W1 W2 G RH Close on Rise at 55 deg F Connect to "G" if electric heat W1 Heat G Fan Delay Relay R RC Fan 24 VAC Hookup Diagram 2: One-Stage Cooling; Gas Heat W7459A Economizer Controller with 2-stage Cooling Thermostat, Low-Ambient Compressor Lockout, and Dry-bulb Differential Changeover Simplified Wiring; Compressor always on Y2 EWEB provides suggested wiring for education only. Installer and customer to determine suitability for specific products and application. 4/2004 EWEB EMS 541-484-1125 Western Premium Economizer Outside Air TR R C SO Dry-Bulb Sensor S C7650A + SR Return Air Dry-Bulb Sensor S C7650A + TR TR1 5 1 Occupancy Sensor in each room served, auxilliary dry contacts close on occupancy. 3 T Discharge Air Sensor C7150B or C7046A P B C D TR1 SO+ SR+ Locate Sensor downstream of DX cooling coil A Set changeover dial to "D" for differential Honeywell W7459A Economizer Controller 2 Honeywell M7415 Actuator Measure RA/OA/MA temp to set min. ventilation % 4 T T1 T1 P P1 P1 Thermostat Terminals Unit Terminals X Y W2 E C Low OSA Lockout Anticycle Y Close on Rise at 55 o F Compressor W2 Resistance Heat lockout: Open on Rise at 30oF OSA Aux. Heat E G G O O RH R Em. Heat Post Purge Fan Rev Valve 24 VAC RC 3PDT relay 24VAC coil Hookup 3: One-Stage Heat Pump W7459A Economizer Controller with 2-stage Mechanical Thermostat, Low-Ambient Compressor Lockout, and Dry-bulb Differential Changeover, Occupancy sensor ventilation. Note: for electro/mechanical thermostats only where first stage cooling contact activates "normally heating" reversing valve. 3PDT relay starts fan and economizer witn "O" and maintains "Y" for heat. EWEB provides suggested wiring for education only. Installer and customer to determine suitability for specific products and application. 5/2004 EWEB EMS 541-484-1125 Western Premium Economizer Outside Air R C Dry-Bulb Sensor S C7650A + TR SO SR Dry-Bulb Sensor S C7650A + Return Air TR TR1 5 1 24 VAC Provide separate sensor transformer with Q769C CO2 Sensor C7242 or C7232 + Locate CO2 sensor in space or return air 3 T Discharge Air Sensor C7150B or C7046A P B C D TR1 SO+ SR+ Locate Sensor downstream of DX cooling coil A Set changeover dial to "D" for differential Honeywell W7459A Economizer Controller 2 Honeywell M7415 Actuator While P/P1 jumpered, set "min." dial to allow MAXIMUM OSA desired 4 T T1 T1 P P1 P1 - Adaptor + Q769C Low OSA Lockout Close on Rise at 55oF Unit Terminals DPDT relay 24VAC coil Y1 Y1 Y2 Y2 W2 W2 Heat lockout: Open on Rise at 30oF OSA E Compressor Compr. 2 Aux. Heat E G G O O RH R RC C Em. Heat Post Purge Fan Rev Valve 24 VAC X Thermostat Terminals Hookup 4: One- or Two-Stage Heat Pump Retrofit Demand Ventilation (DCV) on W7459A Economizer Controller with 2-stage Thermostat, Low-Ambient Compressor Lockout, and Dry-Bulb Differential Changeover Requires 2-stage HP thermostat. "Normally heating" reversing valve shown. For "B" (normally-cooling reversing valve), reverse contact positions shown in relay. EWEB provides suggested wiring for education only. Installer and customer to determine suitability for specific products and application. 5/2004 EWEB EMS 541-484-1125 Western Premium Economizer Outside Air TR R C SO Dry-Bulb Sensor S C7650A + SR Dry-Bulb Sensor S C7650A + Return Air TR TR1 5 1 Locate Sensor downstream of DX cooling coil Discharge Air Sensor C7150B or C7046A T T T1 P B C D SO+ SR+ 3 A TR1 Set changeover dial to "D" for differential Honeywell W7459A Economizer Controller 2 Honeywell M7415 Actuator Measure RA/OA/MA temp to set min. ventilation % 4 T T1 T1 P P1 P1 Thermostat Occupancy Contact Thermostat Terminals A1 A2 Y1 End Switch: Close when damper opens 15% more than minimum ventilation position. With pre-approval by EWEB, in critical zones (servers, equipment, medical diagnostic) failure indicator may be used in place of low ambient compressor lock-out. Unit Terminals Y1 Cool Y2 W1 W1 Heat W2 G Fan Delay Relay RH R Post Purge C C G RC L1 L2 Open on Rise at 55 deg F OSA Fan 24 VAC L3 Schematic 5: Critical Zone One-Stage Cooling Three possible indicator lights: W7459A Economizer Controller with L1: Red LED indicates "Failed 2-stage Cooling Thermostat, Economizer in Cooling" (required) L2: Red LED indicates "Failed Low-Ambient Failure Warning, and Economizer in Heating" (optional) Dry-Bulb Differential Changeover L3: Green LED indicates "Free Economizer Cooling" (optional) EWEB provides suggested wiring for education only. Installer and customer to determine suitability for specific products and application. 4/2004 EWEB EMS 541-484-1125 Western Premium Economizer C O P Discharge Air Sensor C7150B or C7046A T R TR N P1 T1 See Hookup Diagram 7 for M7415 connection TR1 24 VAC Hot Com 24 VAC Hot 24 VAC Com + Ctrl 2-10 VDC Control Signal - Ctrl Honeywell M7215 Actuator Honeywell W7214A Economizer Controller 1 AQ1 Outside Air 2 AQ+ 4 Dry-Bulb Sensor S C7650A + SO 3 SO+ 5 SR SR+ Return Air Dry-Bulb Sensor S C7650A + EF EF1 L1 Exhaust Fan Locate CO2 sensor in space or return air CO2 Sensor C7242 L2 + DPDT relay 24VAC coil Low OSA Close on Rise Lockout at 55 deg F Thermostat Terminals Unit Terminals Y1 Y1 Y2 Y2 W2 Heat lockout: Open on Rise at 30oF OSA Compressor Compr. 2 W2 E E G G O O RH R RC C Aux. Heat Em. Heat Post Purge Fan Rev Valve 24 VAC X Hookup 6: One- or Two-Stage Heat Pump W7214A Economizer Controller with 2-stage Thermostat, Demand Ventilation (DCV) Low-Ambient Compressor Lockout, and Dry-Bulb Differential Changeover Requires 2-stage HP thermostat. "Normally heating" reversing valve shown. For "B" (normally-cooling reversing valve), reverse contact positions shown in relay. EWEB provides suggested wiring for education only. Installer and customer to determine suitability for specific products and application. 5/2004 EWEB EMS 541-484-1125 Western Premium Economizer C N1 P Discharge Air Sensor C7150B or C7046A T R 24 VAC TR N P1 TR1 Provide separate actuator transformer with Q769C 24 VAC Hot T1 Com + Ctrl - Ctrl TR TR1 Honeywell W7212A Economizer Controller 1 AQ1 Outside Air 2 AQ+ 4 Dry-Bulb Sensor S C7650A + SO 3 SO+ SR SR+ Return Air Dry-Bulb Sensor S C7650A + Thermostat Occupancy Dry Contact or Hot "Aux" Terminal. Thermostat Terminals 5 EF Adaptor Q769C Honeywell M7415 Actuator EF1 L1 Exhaust Fan DPDT relay 24VAC coil Low OSA Lockout L2 Close on Rise at 55 deg F Unit Terminals A1 Y1 Y1 Y2 Y2 E + Note: Connection of W7215A or W7460 is similar, although layout is different and Q/Q1 are jumpered. A2/ Aux W2 - T T1 P1 P Heat lockout: Open on Rise at 30oF OSA Compressor Compr. 2 W2 Aux. Heat E G G O O RH R RC C Em. Heat Post Purge Fan Rev Valve 24 VAC X Hookup 7: One- or Two-Stage Heat Pump W7212A Economizer Controller/M7415 with 2-stage Thermostat with Occupancy contact Low-Ambient Compressor Lockout, and Dry-Bulb Differential Changeover Requires 2-stage HP thermostat. "Normally heating" reversing valve shown. For "B" (normally-cooling reversing valve), reverse contact positions shown in relay. EWEB provides suggested wiring for education only. Installer and customer to determine suitability for specific products and application. 4/2004 EWEB EMS 541-484-1125 Western Premium Economizer Discharge Air Sensor C7150B or C7046A C N1 P T R P1 T1 24 VAC Hot Com 24 VAC Hot 24 VAC Com + Ctrl 2-10 VDC Control Signal - Ctrl Honeywell M7215 Actuator 1 2 AQ+ Outside Air 4 SO S + 3 SO+ SR SR+ Return Air Dry-Bulb Sensor C7650A See Hookup Diagram 7 for M7415 connection Honeywell W7212A Economizer Controller AQ1 Dry-Bulb Sensor C7650A TR1 TR N 5 EF EF1 L1 S + Locate CO2 sensor in space or return air Exhaust Fan CO2 Sensor C7242 L2 + Thermostat Terminals Y1 Close on Rise at 55 deg F Low OSA Lockout Unit Terminals Y1 Y2 Y2 W1 W1 W2 W2 G G RC RH R X C Anticycle Cool Compr. 2 Heat Heat 2 Fan Delay Relay Post Purge Fan 24 VAC Hookup 8: One- or Two-Stage Heating/Cooling W7212A Economizer Controller with 2-stage Thermostat, Demand Ventilation (DCV) Low-Ambient Compressor Lockout, and Dry-Bulb Differential Changeover EWEB provides suggested wiring for education only. Installer and customer to determine suitability for specific products and application. 4/2004 EWEB EMS 541-484-1125 Western Premium Economizer ExF MAT Discharge Air Sensor 10k NTC Thermistor See Hookup Diagram 7 for M7415 connection 2-10 VDC + Feedback 2-10 Ctrl + 2-10 Ctrl - 24 VAC Hot 24 VAC Com + OAH - /OAE OAT Outside Air RAT Dry-Bulb + Sensor C7650A S 2-10 VDC Control Signal Honeywell M7215 Actuator Honeywell W7340 Economizer Controller + RAH - /RAE + DCV - Return Air Dry-Bulb + Sensor C7650A S P L1 Configure economizer module for "Enthalpy Sensors" using control configuration procedure in Honeywell document 63-2569. Locate CO2 sensor in space or return air CO2 Sensor C7242 P1 MBUS MBUS + TR1 24V COM TR 24V AC + Close on Rise at 55 deg F - Low OSA Lockout Thermostat Terminals DPDT relay 24VAC coil Exhaust Fan MBUSMBUS+ L2 Demand Limit Compressor lockout Jumper on Reliatel LTB Block Unit Terminals Y1 Y1 Y2 Y2 W2 W2 E Heat lockout: Open on Rise at 30oF OSA Compressor Compr. 2 Aux. Heat E G G O O RH R RC C Em. Heat Post Purge Fan Rev Valve 24 VAC X Hookup 9: One- or Two-Stage Heat Pump W7340 Econo. Controller (Trane Reliatel) 2-stage Thermostat, Demand Ventilation (DCV) Low-Ambient Compressor Lockout, and Dry-Bulb Differential Changeover Requires 2-stage HP thermostat. "Normally heating" reversing valve shown. For "B" (normally-cooling reversing valve), reverse contact positions shown in relay. EWEB provides suggested wiring for education only. Installer and customer to determine suitability for specific products and application. 5/2004 EWEB EMS 541-484-1125 Sensor Simulator & Tester Black mA Meter set > 50 mA before energizing Red Volt Meter Parts List Sensor Simulator Potentiometers, 1 watt: 500 ohm, 1k ohm, 50k ohm 2A Fuse and fuseholder (2) Resistors 220 ohm, 1/2 watt Resistor 5.6k ohm, 1/4 watt Resistor 33 ohm, 1/4 watt LED, green SPDT ON-OFF-ON switch (2) 9V batteries & connectors (3) leads; alligator clips both ends Box, crimp connectors Circuit Protector leads; alligator clips, insulated spades, 3A circuit breaker Red Red 0-10+ V DC output or 4-20+ mA output when connected to control input device. Black Red White - + 220 ohm 1k ohm "Fine" 500 ohm "V/mA" 5.6k ohm Turn off when not in use, as voltage divider uses power even when there are no external connections. Alkaline 9V batteries will provide 8-12 hours of "on" use depending on external loading. 50k ohm "Rough" LED 220 ohm 33 ohm Red 9V 9V Battery Snap connectors Low Battery setting will provide more voltage or current, but will consume battery faster. Remote minimum damper position For Honeywell economizer connect white leads to P/P1; 240 ohms for closed OSA damper to 0 ohms for open OSA damper 9V Blk Circuit Protector Use a lead with in-line circuit breaker for transformer common connection to protect economizer controller and transformer until correct connections are verified. Schematic 10: Testing Unit Test box with: 0-10 VDC or 4-20 mA adjustable output Battery Powered (2-9V) Variable Resistor 0 ohms to 50k ohms with "Rough" and "Fine" dials White Thermistor Simulator Set minimum of 330 ohms for 12 V max. Set minimum of 1200 ohms for 24V max. ON OFF Lo Bat 2A Green 3A Green EWEB provides suggested wiring for education only. Installer and customer to determine suitability for specific products and application. 5/2004 EWEB EMS 541-484-1125 Hookup Diagram 11: Pneumatic OSA Economizer Western Premium Economizer Pneumatic controllers and actuators. Dry-bulb differential changeover; interlocked control; sequenced actuators. Suggested configuration; consult with EWEB for other existing conditions. Parts List (Added Parts Only, shown dark) (Honeywell part numbers shown, equivalents may be used) (2-3) Ratio Relays 3:10 input:output (H'ny'l RP971A1007) Lockout Relay (H'ny'l RP470B) and bleed restrictor Snap Relay (H'ny'l RP471A) Low Ambient cooling lockout and E/P or snap acting relay (2) Direct-Acting Temperature controllers for OA/RA Minimum outside air setting pneumatic potentiometer with unoccupied period outside air lockout. M E/P Relay Lockout and Snap Relays are connected to outside and return air dry-bulb temperature controllers. Whenever return air is warmer than outside air, dampers return to minimum outside air setting . Min OSA Setting High Selector Low Selector Snap Relay (pilot type shown; bleed-type controllers may be used) Control Signal Table (Typical Values) Item Actuator Ratio Relays Ratio/Setting Operation Example Heat 3-8 psi NO RR 3:10; set 3 Vent 3-13 psi NC RR 3:10; set 7 Ratio Relays allow the existing actuator spring ranges to be used. Depending on spring ranges, all 3 may not be needed. Set ratio relays so heating valve closes fully before outside air opens above minimum and outside air is fully open before cooling valve begins to open (unless the changeover has locked out the economizer). Alternate method: If at least a 2 psi gap between heating and cooling valve ranges: activate mixed air controlled economizer when heating valve is closed before cooling valve opens. M Ratio Relay Provide chilled water or chiller ambient lockout when outside air is below 55oF. Ratio Relay Return Air Ratio Relay E/P Relay M Exhaust Air M HWS CHWS DA Controller M M EWEB EMS 541-484-1125 Closed at 7; Open at 10 Cool 9-13 psi NC RR 3:10; set 10 Closed at 11.8; Open at 13 Lockout Relay Outside Air Open at 3; Closed at 4.5 Mixed Air Optional direct-acting low-limit mixed air controller, set 55F with associated low selector relay. Discharge Air Existing Sensor and receiver controller, discharge controller, or room thermostat EWEB provides suggested connections for education only. Installer and customer to determine suitability for specific products and application. 5/2004