Survey
* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project
* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project
RLC AIR COOLED LIQUID CHILLER INSTALLATION, COMMISSIONING, OPERATION AND MAINTENANCE R134a RLC-A & RLC-A R/P/D R407C RLC-B Part No. 035B09025-0GB Subject to change without notice ALL RIGHTS RESERVED GB Table of Contents 1 2 SUPPLIER INFORMATION 4 INSTALLATION 1.1 Introduction 3 4.1 Location 17 1.2 Warranty 3 4.2 External Water System 17 1.3 Safety 3 4.3 Water Connections 20 1.4 Emergency Stops/Shutdown 4 4.4 Electrical Supplies 21 1.5 About this Manual 4 4.5 Electrical Connections 22 1.6 Safety Labels 5 1.7 Material Safety Data 7 5 PRODUCT DESCRIPTION COMMISSIONING 5.1 Preliminary Checks 25 5.2 Starting 25 2.1 Introduction 10 5.3 Performance Check 26 2.2 General Specification 10 5.4 Customer Handover 26 2.3 Compressors 10 2.4 Refrigerant Circuits 11 6.1 Regulation and Control Logic 27 2.5 Evaporators 11 6.2 Compressor Starting Logic 27 2.6 Air Cooled Condensers 11 6.3 Water Temperature Regulation (IN) 28 2.7 Heat Recovery Condensers 11 2.8 Power And Controls 12 Water Temperature Regulation (OUT) 28 2.9 “Chiller Control” 12 6.5 Control Panel 31 2.10 Accessories 13 6.6 Unit Starting 32 2.11 Interface Board 13 6.7 Set Point 33 2.12 Options 13 6.8 Heat Recovery Operation 33 2.13 Theory Of Operation 14 6.9 Alarm Display and Reset 33 6 OPERATION 6.4 3 TRANSPORTATION, HANDLING AND STORAGE 3.1 Inspection 15 3.2 Handling 15 3.3 Anchorage 16 3.4 Storage 16 6.10 Unit Shutdown 33 6.11 Electromechanical Safety Devices 33 1 7 MAINTENANCE 10 SPARE PARTS 7.1 General Requirements 35 10.1 Recommended Spares 66 7.2 Daily Maintenance 35 10.2 Recommended Compressor Oils 66 7.3 Refrigerant Charge 36 10.3 Wiring Diagrams 66 7.4 Refrigerant Circuits 36 7.5 Compressors 36 7.6 Condenser Coils 37 7.7 Condenser Fans 37 7.8 Filter Drier 37 7.9 Sight Glass 37 11 DE-COMMISSIONING, DISMANTLING AND DISPOSAL 11.1 General 7.10 Thermostatic Expansion Valve 38 7.11 Evaporator 38 8 TROUBLE SHOOTING 39 9 TECHNICAL DATA 2 9.1 Pressure Drop Graphs 41 9.2 Safety Switch Setting 43 9.3 Operational Limits 44 9.4 Physical Data 46 9.5 Total Unit Electrical Data 49 9.6 Compressor Electrical Data 50 9.7 Fan Electrical Data 51 9.8 Sound Power Levels 52 9.9 Dimension, Weight and Isolator Data 53 9.10 Piping and Instrumentation Diagrams 56 9.11 General Arrangements 60 67 1 SUPPLIER INFORMATION 1.1 Introduction RLC Series chillers are manufactured to the most stringent design and construction standards to ensure high performance, reliability and adaptability to all types of air conditioning installations. The unit is intended for cooling water (and heating water in the case of heat recovery chillers of those fitted with a desuperheater) and is not suitable for purposes other than those specified in this manual. If the unit is used improperly, or for different purposes without the prior agreement of Itelco-Clima or their agents, then such use would be outside the scope and may be unsafe. This manual contains all the information required for correct installation and commissioning of the unit, together with operation and maintenance instructions. The manual should be read thoroughly before attempting to operate or service the unit. With the exception of the operations detailed in this manual, all installation, commissioning and maintenance tasks must be performed by suitably trained and qualified personnel from an Authorised Service Centre. The manufacturer is not liable for injury or damage resulting from incorrect installation/commissioning or operation, insufficient maintenance and/or failure to follow the procedures and instructions contained in this manual. 1.2 Warranty The unit is supplied finished, tested and ready to work. The unit warranty will be void if any modification to the unit is carried out without written agreement of the manufacturer. For warranty purposes, the following conditions must be satisfied: ■ The initial start of the unit must be carried out by trained personnel from an Authorised Service Centre. ■ Maintenance must be carried out by properly trained personnel. ■ Only genuine spare parts must be used. ■ All the scheduled maintenance operations detailed in this manual must be performed at the specified times. Failure to satisfy any of these conditions will automatically void the warranty. 1.3 Safety The installation of the unit must be carried out according to the Machinery Safety Directive (CEE 98/37), to the Low Voltage Directive (73/23/EEC), to the Electromagnetic Interference Directive (89/336/EEC) as modified by Directive (92/31/EEC) and according to normal rules for technical matters prescribed by the applicable country regulations. Do not operate the unit before having observed all the above. WARNING The unit must be earthed and no installation or maintenance work should be attempted on the electrical equipment without first switching off and isolating the main power supply and any control supplies. Failure to observance of the above safety measures may result in fire or electrocution should a shortcircuit occur. 3 WARNING The unit contains refrigerant vapour and liquid under pressure within the heat exchangers, compressors and pipework. Release of refrigerant can be a danger and cause injury. Fan guards must be fitted at all times and not removed unless the main power supply has been isolated. 1.4 Emergency Stops/Shutdown The isolator switch on the electrical panel will shutdown the unit, when set to the 0 (Off) position. The unit should be restarted in accordance with the procedure detailed in this manual. 1.5 About this Manual WARNING WARNING WARNING CAUTION CAUTION It is the responsibility of the user to ensure that the unit is suitable for the conditions of use and that installation and regular maintenance is carried out by personnel with the appropriate skills and in accordance with this manual. Support of the unit must be provided as indicated in this manual, failure to provide proper support may put personnel at risk of injury. The unit is not designed to withstand loads or stresses from adjacent equipment, pipework and structures. Any such extraneous loads or stress may cause failure or collapse which can be a danger and cause injury. In such cases the warranty will be void. For safety reasons, the instructions contained in this manual must be followed categorically; furthermore, damage caused by misuse is not covered by the warranty. This manual uses the following conventions: WARNING Warning messages alert you to a specific procedure or practice which, if not followed correctly, could cause serious personal injury. Caution messages appear before procedures which, if not observed, could result in damage to the unit. CAUTION Notes contain particularly important comments which are set off from the text. The user should ensure that reasonable care is taken by other trades to avoid damage/abuseto the unit during and after installation. Hints provide useful information to improve operation efficiency HINTS Do not discard or burn the packaging in the environment. CAUTION 4 The contents of this manual, and any other documentsupplied with the unit, are the property of Itelco-Clima which reserves all rights. They may not be reproduced, in whole or in part, without the written authorisation of Itelco-Clima. 1.6 Safety Labels The following labels are fitted to each unit in the locations stated: Refrigerant Identification - Outside Panel Door TENERE SU QUESTA LINEA GANCIO DI SOLLEVAMENTO KEEP LIFT HOOK ON THIS LINE Centre of Gravity - Base Frame Electrical Warning Adjacent to Isolator Switch Unit Identification Inside of Outer Panel Door 5 QUESTO COMPRESSORE RICHIEDE UN CORRETTO SENSO DI ROTAZIONE RISPETTARE LA CORRETTA SEQUENZA DELLE FASI CAUTION THIS COMPRESSOR REQUIRES PROPER DIRECTION OF ROTATION CHECK PROPER ELECTRICAL PHASING Scroll Compressor Direction of Rotation Compressor ATTENZIONE INSERIRE LE RESISTENZE DI RISCALDAMENTO OLIO ALMENO 12 ORE PRIMA DI OGNI AVVIAMENTO (SE PREVISTE). 881000215/B ATTENZIONE PRIMA DELLA MESSA IN TENSIONE ASSICURARSI CHE LE VITI DEI CIRCUITI ELETTRICI SIANO SERRATE COMPLETAMENTE. WARNING ENERGIZE THE CRANCKCASE HEATER FOR AT LEAST 12 HOURS BEFORE EACH STARTING (IF FITTED). BEFORE TIGHTENING-UP, TO TIGHTEN ALL TERMINAL SCREWS ESPECIALLY THOSE IN MAIN CIRCUIT. Start up Warning Outside of Electrical Panel Door Lifting Point - Base Frame EIN - INLET ENTRÉE - ENTRATA AUS - OUTLET SORTIE - USCITA Connection Identification - Adjacent to Connections Test Certificate Inside of Outer Panel Door Earth Point - In Panel Adjacent to Connection 6 1.7 Material Safety Data Refrigerant Data: Safety Data: R407C, R134a Toxicity Low. In contact with skin Liquid splashes or spray may cause freeze burns. Unlikely to be hazardous by skin absorption. Thaw affected areas with water. Remove contaminated clothing carefully - may adhere to skin in case of freeze burns. Was affected areas with plenty of warm water. If symptoms occur (irritation or blistering) obtain medical attention. In contact with eyes Vapour has no effect. Liquid splashes or spray may cause freeze burns. Immediately irrigate with eyewash solution or clean water for at least 10 minutes. Obtain immediate medical attention. Ingested Highly unlikely to occur - but should this occur freeze burn will occur. Do not induce vomiting. Provided patient is conscious, wash mouth with water and give about 250 ml (0.5 pint) to drink. Obtain immediate medical attention. Inhalation R407C, R134a: High atmospheric concentrat ions may lead anaesthetic effect, including loss of consciousness. Very high exposures may cause an abnormal heart rhythm and prove suddenly fatal. At higher concentration there is a danger from asphyxiation due to reduced oxygen content of atmosphere. Remove patient to freshair, keep warm and at rest. Administer oxygen if necessary. Apply artificial respiration if breathing has ceased or shows signs of failing. In event of cardiac arrest apply external cardiac massage. Obtain immediate medical attention. Further Medical Advice Symptomatic and supportive therapy is indicated. Cardiac sensitisation has been described which may, in the presence of circulating catecholamines such as adrenalin, give rise to cardiac arrhythmias and subsequent arrest following exposure to high concentrations. Long term exposure R407C, R134a: A lifetime inhalation study in rats has shown that exposure to 50,000 ppm resulted in benign tumours of the testis. This is not considered to be of relevance to humans exposed to concentrations at or below the occupational exposure limit. Occupational exposure limits R407C, R134a: Recommended limit: 1000 ppmv/v - 8 hr TWA. Stability R407C, R134a: Not specified. Conditions to avoid Use in presence of naked flames, red hot surfaces and high moisture levels. Hazardous reactions May react violently with sodium, potassium, barium and other alkali and alkaline earth metals. Incompatible materials: Magnesium and alloys containing more then 2%magnesium. Hazardous decomposition products R407C, R134a: Halogen acids by thermal decomposition and hydrolysis. 7 8 General precautions Avoid inhalation of high concentrations of vapours. Atmospheric concentrations should be minimised and kept as low as reasonably practicable below the occupational exposure limit. The vapour is heavier than air and collects at low level and in confined areas. Ventilate by extraction at lowest levels. Respiratory protection Where doubt exists on atmospheric concentration, HSE approved breathing apparatus should be worn. This should be self contained or of the long breather type. Storage Keep containers dry and in a cool place away from fire risk, direct sunlight, and all sources of heat such as radiators. Keep at temperatures not exceeding 45 deg C. Protective clothing Wear overalls, impervious gloves and goggles/face protection. Spill / Leak procedure Ensure suitable personal protective clothing and respiratory protection is worn. Provided it is safe to do so, isolate the source of the leak. Allow small spillages to evaporate provided there is suitable ventilation. Large spillages: Ventilate area. Contain spillages with sand, earth or any suitable absorbent material. Prevent liquid from entering drains, sewers, basements and work pits since vapour may create a suffocating atmosphere. Disposal Best to recover and recycle. If this is not possible, destruction is to be in an approved facility whichis equipped to absorb and neutralise acids and other toxic processing products. Fire extinguishing data R407C. R134a: Non-flammable at atmospheric conditions. Containers Fire exposed containers should be kept cool with water sprays. Containers may burst if overheated. Fire fighting protective equipment Self contained breathing apparatus and protective clothing must be worn in fire conditions. Refrigerant Oil Data: Safety Data Oil Polyester (POE) Classification Non-hazardous In contact with skin Minimally irritating. No first aid necessary. Exercise reasonable personal cleanliness including cleansing exposed skin areas several times daily with soap and water. Launder soiled work clothes at least weekly. In contact with eyes As with most foreign materials flush with plenty of eyewash solution or clean water. Ingested Obtain immediate medical attention. Inhalation Obtain immediate medical attention. Conditions to avoid Strong oxidisers, caustic or acid solutions, excessive heat. May degrade some paints and rubber materials. Respiratory protection Use in well ventilated areas. Protective clothing Goggles or face shield should be worn. Gloves not necessary, but recommended, especially for prolonged exposure. Spill / Leak procedure Wear suitable protective equipment, especially goggles. Stop source of spill. Use absorbent materials to soak up fluid (i.e. sand, sawdust, and commercially available materials). Disposal Incinerate the oil and all associated wastes in a approved facility in accordance with local laws and regulations governing oily wastes. Fire extinguishing datra Use dry chemical, carbon dioxide or foam spraying water on hot or burning liquid, may cause frothing or splashing. If a leak or spill has not ignited use water spray to disperse the vapours and to provided protection for persons attempting to stop the leak. Containers Fire exposed containers should be kept cool with water sprays. Fire fighting protective equipment Self contained breathing apparatus should be worn in fire conditions. 9 2 PRODUCT DESCRIPTION 2.1 Introduction The RLC range of twin refrigerant circuit water chillers are designed to be located outside on the roof of a building or at ground level. The range includes the following models: Models Description RLC-A 210 to 525 Water chillers charged with refrigerant R134a RLC-B 210 to 800 Water chillers charged with refrigerant R407C The following options are available: Option Description /R 100% (total) heat recovery on both refrigerant circuits tosupply simultaneous chilled and warm water. During heat recovery the refrigerant flows via the heat recovery condensers /P 50% (partial) heat recovery on a single refrigerant circuit to supply simultaneous chilled and warm water. During heat recovery the refrigerant flows via the heat recovery condenser /D Heat is recovered via a desuperheater installed on the compressor discharge line. /Q Low noise emission, using mufflers and continuous fan speed control 2.2 General Specification RLC models are completely assembled with all interconnecting refrigerant piping and wiring ready for field installation. 10 The unit is pressure tested, evacuated and finally charged with refrigerant and includes an initial oil charge. After assembly a full run test is performed, with water flowing through the evaporators, to verify that each refrigerant circuit operates correctly. The unit base and frame is of heavy gauge galvanised steel fastened with stainless steel screws and bolts. Compressor and refrigerant circuit components are located in an acoustically lined enclosure. All panels are easily removed for access to components. Galvanised steel parts are painted with baked-on enamel coloured white RAL 9001. 2.3 Compressors Model Compressor RLC-A da 210 a 525 Two reciprocating compresRLC-B da 210 a 800 sors with part wind starting RLC-A 210 to 525 and RLC-B 210 to 800 Compressor lubrication is force-fed by a reversible oil pump to all crankshaft and bearing surfaces through a fine mesh stainless steel oil strainer. The compressor motors are refrigerant gas cooled, with integral temperature-sensing solid state overload protection in each phase. The motor terminal boxes are to IP-54 weather protection. Compressor capacity control is provided by solenoid-actuated, capacity control valves, which are controlled by the unit microprocessor. This method efficiently and effectively matches low load conditions as required. Gas flow is sufficient at all times to cool the motors. 2.4 Refrigerant Circuits 2.6 Air Cooled Condensers Two complete refrigerant circuits are supplied on each unit. All piping is ACR copper, with brazed joints. Refrigerant circuits include: a service valve for refrigerant charging, suction discharge and liquid line isolating valves, sight glass with moisture indicator, thermal expansion valve with external equaliser. Solenoid valve, filter drier and differential oil pressure switch on sizes 210 to 800. High and low pressure switches and safety valves on sizes 300 to 800. The condenser coils are seamless copper tubes, arranged in staggered rows, mechanically expanded into corrugated aluminium fins. Integral subcooling is included. The design working pressure of the coil is 28 bar g. The condenser fans are direct drive with aluminium aerofoil blades. Each fan has a painted galvanised steel protection guard. 2.5 Evaporators The three phase totally enclosed fan motors are to IP-54 weather protection and have thermocontact protection embedded in their windings. RLC-A and RLC-B models 210 upwards each have a single steel shell and copper tube evaporator. 2.7 Heat Recovery Condensers The dual-circuit evaporator is a direct-expansion type, with the refrigerant in the tubes, which are formed in a hair-pin configuration, and chilled liquid flowing through the baffled shell. The evaporator is covered with flexible, closed-cell, foam insulation. The heat recovery condensers are cleanable shell and tube type with seamless high pressure shell and external finned copper tubes rolled into tube sheets. The condenser shell is factory insulated with flexible closed cell insulation and has a heater mat for antifreeze protection down to -20°C. Water connection to the evaporator is via threaded connections on models 210 to 360 and victualic type on models 400 upwards. The design working pressure is 25 bar g on the refrigerant side and 10 bar g on the water side. All evaporators have a heating element controlled by a thermostat for frost protection to -10°C. Water vent and drain connections are included on all evaporators. The evaporator design working pressure on the water side is 10 bar g and on the refrigerant side 25 bar g. Full heat recovery units have two heat recovery condensers and partial heat recovery units have one condenser. All heat recovery units are equipped with cooling-heat recovery mode change-over valve(s) and controller(s). A factory wired control sensor, not including sensor pocket, is provided for field installation. 11 2.8 Power And Controls The control unit implements the following logic: All units are equipped with a “Chiller Control” microprocessor control and management system. ■ LED and visual display of unit alarms and unit operation. All controls and motor starting equipment necessary for unit operation are factory wired and tested. ■ Compressor start-up logic (part-winding and cut out), power adjustment on 2 or 4 steps. Power and control components are separated and accessed via individual doors. The power section has a door interlocked isolator. The total enclosure is fitted with a second upward opening door. The panel is designed to IP-54 weather protection. ■ Display of compressor working hours and evaporator temperature. ■ Anti-cycling and anti-start-up surge timers. ■ Automatic compressor lead/lag start-up sequence. Fan cut out. The power compartment contains: ■ General switch. ■ ■ Main isolator, compressor contactors and fuses, fan contactors and fuses. Management of set points and parametric data: ■ User level - The machine operator can adjust data at the keyboard with the ‘SET’, ‘+’ and ‘-’ keys. Service Level - System password access for authorised Service personnel. The control compartment contains: ■ Anti-frost thermostat; auxiliaries transformer, fuses and relays. ■ ■ The “Chiller Control” microcomputer keypad and display, mounted in the control section door. The display panel has keypad type buttons identified by symbols, colour coded to Eurovent standards, and LED’s to display function status: 2.9 Chiller Control The “Chiller Control” unit consists of an expandable interface board and a control unit. The expandable interface board monitors inputs and provides control outputs as follows: ■ Digital inputs, such as alarms and commands. ■ Analog inputs, such as temperature and pressure measurements. ■ Digital outputs for control relay and remote control switch operation. 12 ■ Green indicates Normal operation ■ Yellow indicates Caution ■ Red indicates Stop 2.10 Accessories 2.12 Options Flow Switch Condenser Coil-fin Protection Supplied loose for field installation by contractor. Painted galvanised steel guards mounted on the exterior of the unit. Anti-vibration Mounts Air Cooled Condenser Options Open spring isolator mounts with fixing down holes, supplied loose for field installation by contractor. Copper fins or vinyl coated fins. Improved Capacity Control Gauge Kit Six or eight step control instead of standard four step control for semi-hermetic compressor models. Factory fitted mechanical dial gauges for suction and discharge pressure indication of each refrigeration circuit. Fan-speed Control Extra Temperature and Pressure Sensors Maintains constant condensing temperature, during operation in low ambient conditions. 2.11 Interface Board An optional communications interface enables the unit to be controlled and managed from a local station via RS232 up to 500m, or via modem and a telephone line. Remote management and control can therefore be met by integrating twith a Building Management System. To display compressor suction and discharge pressures and evaporation temperature of each refrigeration circuit. Time Programme Board Factory mounted to programme set point hours per day (Maximum of four different set points over 24 hours per day and 5 days). Also implements chiller on/off schedule. Generally used with ice storage systems. Nomenclature R L C - 360 A / R / P / D REFRIGERATOR LARGE CAPACITY COOLING ONLY COMMERCIAL USE SIZE DESUPERHEATER PARTIAL RECOVERY TOTAL RECOVERY REFRIGERANT A = R134a B = R407c 13 WITH 50% HEAT RECOVERY CONDENSER COIL CONDENSER COIL COOLER HEAT RECOVERY CONDENSER COOLER HP LIQUID LP VAPOUR LP LIQUID HP VAPOUR LP VAPOUR HP LIQUID RLC-A & RLC-B 2.13 HP VAPOUR LP LIQUID RLC-A /P Theory Of Operation Cooling Mode Heat Recovery Mode Low pressure liquid refrigerant enters the cooler (Evaporator) and is evaporated and superheated by the heat energy absorbed fromthe chilled water passing through the cooler shell. Low pressure vapour enters the compressor where pressure and superheat are increased. Heat is rejected via the air cooled condenser coil and fans. The fully condensed and subcooled liquid refrigerant then enters the expansion valve where pressure reduction and further cooling takes place before returning to the cooler. During heat recovery operation the refrigerant passes to the water cooled condenser instead of the air cooled condenser. The high pressure superheated refrigerant vapour enters the condenser shell, whereheat is rejected to thewarm water in the tubes, and is condensed. High pressure liquid refrigerant then passes through the expansion valve, where pressure reduction and cooling takes place, before returning to the cooler. Excess heat is rejectedat theair cooledcondenser. WITH 100% HEAT RECOVERY CONDENSER COIL WITH DESUPERHEATERS CONDENSER COILS DESUPERHEATER DESUPERHEATER CONDENSER COIL HEAT RECOVERY CONDENSER LP VAPOUR HEAT RECOVERY CONDENSER HD LIQUID RLC-A /R 14 HP VAPOUR COOLER LP LIQUID LP VAPOUR HP LIQUID HP VAPOUR RLC-A /D RLC-B/D (to Model 400) LP LIQUID 3 TRANSPORTATION, HANDLING AND STORAGE ■ Insert a spreader bar or frame between the cables, vertical to the unit’s centre of gravity. RLC series chillers are supplied fully assembled, (with the exception of the rubber vibration pads supplied with the unit) which are installed on site. Units are pre-charged with refrigerant and oil in the correct quantity required for operation. ■ Attach the crane hook at the unit’s centre of gravity. ■ Cable length shall be such that they do not form an angle of less than 45 degrees to the horizontal when under tension. 3.1 Inspection Immediately upon receiving the unit, it should be inspected for possible damage which may have occurred during transit as goods are shipped exworks at purchaser’s risk. In addition, ensure that all ordered components have been received. If any damage is evident, it should be noted on the carrier’s freight bill and a claim entered in accordance with the advice note instructions. If the damage is other than superficial, immediately advise your local Itelco-Clima representative. International Lifting Lugs Itelco-Clima accepts no responsibility for shipping damage, even in cases where the factory has arranged for shipping. 3.2 Handling RLC series chillers are designed to be lifted using lifting lugs and cables. A spreader bar or frame should be used with the cables, to avoid crushing the unit. L > Unit Width L Before moving the unit ensure that the installation site is suitable to receive the unit and to support its weight and mechanical impact. During handling, avoid touching sharp parts (for example coil fins). Never move the machine on rollers or lift the machine using a fork lift truck. CAUTION Proceed as follows to lift and move the machine: ■ Insert and secure the lifting lugs through the marked holes in the base frame. ■ Attach the cables to the lifting lugs. CAUTION Care should be taken to avoid damaging the side-mounted coil fins and panelling when lifting and moving the unit to the installation site. The sides of the unit should be protected with stiff cardboard or plywood. CAUTION 15 CAUTION Do not remove the protective plastic wrapping and the coil protectors, which prevent dirt, dust and other foreign matter from entering the fan grilles or damaging the external surfaces, until the unit is ready for operation. 3.4 Storage If the unit is to be stored prior to installation, certain precautions should be taken to prevent damage, corrosion or deterioration: ■ Ensure that all openings, such as water connections, are securely capped or sealed. ■ Do not store where exposed to ambient air temperatures exceeding 45°C for R134a or 42°C for R407c units, preferably out of direct sunlight. ■ The finned heat exchangers should remain covered to protect the fins from potential corrosion, particularly where building work is in progress. ■ Store the unit in a location where minimum activity is likely to take place in order to limit the risk of accidental damage. ■ Do not steamclean the unit. ■ Remove the keys necessary to gain access to the control panel and deposit them with a responsible person on site. 3.3 Anchorage RLC Series chillers are provided with 18 mm diameter holes in the base frame for retaining the spring damper mounts if required. It is not necessary to anchor theunit to foundations, except in areas of high risk of earthquake, or where the unit is located at high level on a steel mounting frame. Periodic visual examination during storage is recommended. 16 4 INSTALLATION ■ The unit should not be sited in air wells, courtyards or other restricted spaces where noise would be reverberated off the walls, or where air expelled by fans could be channelled back to condenser inlets. ■ The installation position should ensure adequate clearances for air circulation and maintenance, refer to Section 9 for details. 4.1 Location WARNING Before installing the unit, make sure that the building structure and/or mounting surface can support the unit weight. Overall weights and weight distribution is detailed in Section 9. The unit has been designed for floor mounting in outside locations. Rubber anti-vibration pads are supplied as standard and they must be positioned centrally, underneath each of the supporting plates. When the unit is to be installed on the ground, a concrete slab must be provided to ensure uniform weight distribution. Special mounts are not normally required. However, if the unit is to be installed directly above inhabited rooms, it is advisable to set the unit on spring damper mounts (supplied as accessories, refer to Section 9) to minimise the vibrations transmitted to the structure. 4.2 External Water System CAUTION The external water system should consist of the following: ■ A circulation pump providing sufficient output and hydraulic head. ■ To ensure that repetitive starts of compressors is avoided, which can cause damages, the primary system water content should be no less than 10 litres per kW of cooling capacity. If the total volume in primary system pipework and evaporator is insufficient, an insulated buffer tank should be installed. ■ A diaphragm-type expansion tank with safety valve outlet which must be visible. The following factors must be considered when selecting a location for the unit: ■ The units longitudinal axis should be parallel to prevailing winds to ensure balanced air flow over the condenser coils. ■ The unit should not besited downwind of boiler flues. ■ The unit should not be sited downwind of sources of grease-laden air such as extractor vents for large kitchens. In such cases, accumulated grease on the condenser fins can trap air-borne contaminants, thus leading to rapid soiling or clogging. ■ The unit should not be sited in areas exposed to heavy snowfall. ■ The external water hydraulic circuit must ensure constant water flow to the evaporator under all operating or adjustment conditions. The tank should be sized to accommodate a 2% increase in total fluid volume in the system (evaporator, lines, user circuits and water reservoir where provided). The Expansion tank need not necessarily be insulated, as water does not normally circulate therein. ■ A flow switch to deactivate the unit when water is not circulating. The unit should not be sited in areas exposed to flooding or beneath downpipes, etc. The flow switch must be connected in series with external interlocks as shown on wiring diagram in control panel. CAUTION 17 Follow the manufacturer’s instructions carefully when installing the flow switch. In general, the flow switch should be installed on the pump delivery, upstream of the unit, on a horizontal pipe run of at least 10 pipe diameters from any bend, valve or other item which could interfere with water flow upstream or downstream of the flow switch. A Normally Open differential pressure switch may be installed instead of the flow switch. The pressure switch senses water pressure drop across the evaporator. In addition: ■ Install air vent valves at the highest points of the lines. ■ Install shutoff valves on the evaporator and heat recovery condenser inlet and outlet water lines. ■ Provide suitable drainage points (with plugs, cocks etc.) at the lowest points of the lines. ■ Install a valved by-pass around the evaporator. ■ Insulate the pipework to prevent heat loss. ■ A filter/strainer located on the suction side of the evaporator or heat recovery condenser. ■ A water flow measuring device. 18 FLOW SWITCH INSTALLATION UNIT EXTERNAL WATER SYSTEM Typical Connection Diagram Key I GA T S R F Fl Pressure gauge tapping Flexible connections Thermometer Gate valves Drain tap Strainer Flow switch Standard evaporators provided on RLC units are designed to chill mixtures of water and ethylene glycol with a corrosion-inhibiting additive down to –10°C. The amount of ethylene glycol to be added is as follows. Amounts are shown as a percentage by weight of the circuit design water content: operation from + 5 to 0 °C : 20% CAUTION Before filling the system, ensure that it is free from foreign matter, sand, stones, rust flakes, solder, slag or other materials which could damage the evaporator. operation from 0 to -5 °C : 30% operation from -5 to -10 °C : 40% It is advisable to by-pass the unit when flushing out the lines. A strainer screen must be installed upstream of the chiller. Water used to fill the circuit may have to be treated to ensure that the PH value is correct. 19 Where two or more units are connected in parallel it is recommended that the connections be made through a “Reverse Return” circuit (as shown below) in order to balance the pressure drop in each unit circuit. Typical Parallel Hydraulic Connection Key A B S VG E1 E2 E3 RLC-A 360 to 525 and RLC-B 400 to 800 From circulating pump Chilled water to the system Gate valves Balancing valve Evaporator, 1st unit Evaporator, 2nd unit Evaporator, 3rd unit Connect the external water supply lines to the water inlet and outlet fittings on the left hand side of the unit, when viewed from the electrical panel. The unit is provided with Victaulic fittings, refer to section 9 for diameters and locations. RLC-A Heat Recovery Models (/R and /P) A factory wired control sensor (6 mm diameter x 30 mm long) is provided for field installation. 4.3 Water connections The water inlet and outlet connections must be connected correctly as shown on the labels fitted adjacent to the fittings. RLC-A 210 to 300 and RLC-B 210 to 360 Connect the external water supply lines to the water inlet and outlet fittings at rear of the unit. CAUTION The unit is provided with threaded pipe fittings, refer to section 9 for diameters and locations. 20 A sensor pocket, which is not supplied, should be installed by the contractor in the common pipework leaving the condenser(s). 4.4 Electrical Supplies Ensure that the power supply is off before working on the electrical system. WARNING The unit must be provided with an earth connection. Magnetic thermal differential breakers are recommended, to prevent damage due to electrical phase loss. Power supplies to the compressors and the fans are through contactors controlled by the control panel. Each motor is provided with an internal thermal overload cut-out and external fuses. WARNING CAUTION Supply and isolating devices shall be designed so that the lines are fully independent. It is the installers responsibility to ensure that all external wiring complies with applicable safety regulations. Supply cables should be routed through the cable entries on the unit front and enter the electrical panel through a hole at the bottom of the panel. The Manufacturer is not responsible for injury or damage of any kind resulting from failure to observe these precautions. The unit complies with EN 60 204-1. The following connections are required: ■ One three-phase line and earth for the power circuit supply. The electrical distribution system must be able to supply all the unit power, refer to Section 9. The disconnect switches and circuit breakers must be sized to handle the unit starting current, refer to section 9. 21 4.5 Electrical Connections The installation of the unit on the final site must be carried out according to the Machinery Safety directive (98/37/EC), to the Low Voltage Directive (73/23/EEC), to the Electromagnetic Interference directive (89/336/EEC) and according to normal rules for technical matters prescribed by the applicable country regulations. Do not operate the unit before having observed all the above. Supply lines shall consist of insulated copper conductors sized for maximum current draw. Terminal connections should be made in accordance with the connection diagram in this manual and the diagram supplied with the unit. Before connecting the supply lines, check that the mains voltage is within the range shown in the Electrical Data in Section 9. CAUTION For the 3 phase power supply, also check that the phase unbalance does not exceed 2%. The check is performed by measuring the difference between the voltage of each phase pair and the average mains voltage during operation. The maximum measured difference (unbalance) shall not exceed 2% of the average voltage. If the unbalance is unacceptable, the electricity supply company must be asked to correct the fault. Supplying the unit with a line whose unbalance exceeds the specified value will automatically void the warranty. CAUTION 22 MORSETTIERA DELL'UNITÁ UNIT TERMINAL BOARD MORSETTIERA ESTERNA EXTERNAL TERMINAL BOARD LINE 400-3-50 FLOW SWITCH OR EXTERNAL INTERLOCK (24V) INTERLOCK (OPTIONAL) (24V) CIRC PUMP ETC REMOTE INDICATION VOLTAGE ON (VF) REMOTE ON/OFF CONTROL (VOLT FREE CONTACT) COMMON (NO) GENERAL ALARM VOLT FREE (NC) COMPRESSOR ‘1’ ON VOLT FREE COMPRESSOR ‘2’ ON VOLT FREE RLC-A e RLC-B Electrical Connections 23 UNIT TERMINAL BOARD MORSETTIERA DELL'UNITÁ EXTERNAL TERMINAL BOARD MORSETTIERA ESTERNA LINE 400-3-50 FLOW SWITCH OR EXTERNAL INTERLOCK (24V) INTERLOCK (OPTIONAL) (24V) CIRC PUMP ETC REMOTE INDICATION VOLTAGE ON (VF) REMOTE ON/OFF CONTROL (VOLT FREE CONTACT COMMON (NO) GENERAL ALARM VOLT FREE (NC) COMPRESSOR ‘1’ ON VOLT FREE COMPRESSOR ‘2’ ON VOLT FREE REMOTE ON/OFF HEAT RECOVERY (VOLT FREE CONTACT) RLC-A, RLC-B with Heat Recovery, Electrical Connections 24 5 COMMISSIONING CAUTION The unit must be started by trained personnel from an Authorised Service Centre. failure to satisfy this requirement will void the warranty. The operations performed by service personnel are limited to unit starting, and do not include other work on system such as electrical connection, water connection, etc. All other preparatory work, including oil pre-heating (for at least 12 hours) must be performed by installer. ■ Adjust the water system so that the flow rates are as specified. ■ Check that the water quality is as specified. ■ Check the position of the safety and anti-icing thermostat sensors. ■ Check that the oil heaters, if fitted have been energised for at least 12 hours. 5.2 Starting The starting sequence is as follows. ■ Turn on the master isolating switch (12 hours before). ■ Check that the compressor oil is sufficiently warm (minimum temperature at the oil pan exterior must be approximately 40°C) and that the auxiliary control circuit is energised. ■ Check that all external equipment is in running order and that the associated control equipment is correctly calibrated. 5.1 Preliminary Checks The following operations must be performed before starting the unit and should be performed before service personnel arrive. ■ With master isolating switch off, check the supply cable cross-section, the ground connection, the electrical terminal clamps are tight and that all contactors operate correctly. ■ Check that the voltage and phase unbalance of the power supply is within limits, refer to Section 4. ■ Start the liquid pump and check that the water flow rate is as required. ■ Connect (non-energised) contacts of the flow switch and the pump thermal overload cut-out or other devices (where provided) to terminals 1-2 and 3-4 respectively. ■ Set the desired fluid inlet temperature on the control panel (refer to Section 6). ■ Start the unit (refer to Section 6). Check that the external water circuit components (pumps, user equipment, filters, expansion tank and reservoir where provided) have been correctly installed as advised by manufacturer and that the inlet and outlet water connections are correct. ■ Check the correct Scroll compressor direction of rotation. ■ After around 15 minutes of operation, check that no air bubbles are visible through the sight glass on the fluid line. ■ ■ ■ Check that the external water circuit is full and that the fluid circulates freely with no signs of leakage or air bubbles. If ethylene glycol antifreeze is used, check that the percentage concentration is correct. Check that the pump direction of rotation is correct, and allow fluid to circulate for at least 24 hours (12 hours for each pump). Then clean the basket filters on the pump suction. CAUTION If air bubbles are visible, the unit has lost part of its charge through one or more leaks. The leaks must be eliminated refer to Section 7. ■ Repeat the starting procedure after eliminating the leaks. ■ Check that the oil level is correct. MAX MIN 25 MAX MAX MIN MIN MIN RLC-A 210, 240, 300, 360, 400, 450, 525 RLC-B 210, 240, 300, 360 Sight Glass Sight Glass RLC-B 400, 450, 525, 600, 700, 800 Sight Glass 5.3 Performance Check Check the following: ■ Evaporator manifold inlet water temperature. ■ Evaporator manifold outlet water temperature. ■ Evaporator manifold outlet water flow rate. ■ Compressor current at startup and stable operating conditions. ■ Fan current at startup and stable operating conditions. Check that the saturated evaporation and condensation temperatures during operation at high and low pressure by connecting gauges to the schrader valves on the high and low pressure refrigerant circuits. High pressure side Approximately 15 to 18°C above coil inlet air temperature Low pressure side Approximately 5 to 7°C below chilled water outlet temperature 5.4 ■ 26 Customer Handover Familiarise the user with the machine operating instructions in Section 6. 6 OPERATION RLC series chillers are equipped with a microprocessor control logic and regulation management system. The system consists of a unit logic board and a liquid crystal control panel which manages the control, starting, shutdown and display functions. ■ When the alarmis activated, control logic locks out the unit. Reset is automatic. ■ Unit alarm management and display ■ High pressure alarm. When the alarmis activated, control logic locks out the associated refrigerating circuit and opens the compressor control chain (fail-safe mode). Alarmis reset from the pressure switch and manually from panel. ■ ■ 6.2 Compressor starting logic Control logic automatically manages all functions connected with compressor starting. ■ Anti-cycling timer delay. Prevents compressor starting attempts from being made in quick succession (360 seconds/6 minutes) (Note 1). ■ Starting delay. Low pressure alarm. Prevents compressors from starting simultaneously (10 seconds) (Note 1). When the alarmis activated, control logic locks out the associated refrigerating circuit. Alarm operation is delayed approximately 30 seconds after starting (Note 1). Alarm is reset manually from panel. Part wind starting is used to reduce starting current. Panel logic automatically manages this starting mode, in which only a part of the compressor winding is activated during starting. Differential oil pressure alarm. When the alarmis activated, control logic locks out the associated refrigerating circuit. Alarm operation is delayed approximately 120 seconds (Note1). Alarmis reset manually from panel. ■ Fan thermal overload cut-out alarm. Activation of this alarm locks out the associated circuit and fans. Alarmis triggered by fan motors. Reset is automatic. 6.1 Regulation and control logic Control logic automatically manages the following functions: External interlock alarm. Compressor thermal overload cut-out alarm. ■ Automatic compressor starting sequence change. Used to ensure that compressors operate for the same number of hours. Note 1 These parameters are variable. Changes must be carried out by Itelco-Clima authorised personnel only. When the alarmis activated, control logic locks out the associated refrigerating circuit and opens the compressor control chain. Alarm is reset manually from panel. ■ Anti-freezing alarm. This alarm is activated when water temperature at evaporator outlet drops below 3 °C (Note 1). Alarm is reset manually from panel. 27 The water temperature can be controlled from the inlet or the outlet. 6.3 Water Temperature Regulation (IN) Regulation is performed via inlet water temperature SET POINT as shown below. The band is divided into a number of steps. G1 OFF G2 OFF G1 ON The control regulates the output of the compressor as a function of the system; control is in two steps, four steps or optionally six or eight. Depending on the required set point and the proportional band (pre selected to be 5°C), the controller determines the number of functioning compressors and possible unloading. Key 1 2 The above always refers to nominal water flow with a dT equal to 5°C. Tr G1 - G8 G3 OFF G2 ON G4 OFF G3 ON G5 OFF G4 ON G6 OFF G5 ON G7 OFF G6 ON G8 OFF G7 ON G8 ON 8-step Type Regulation SET POINT Programmed set point Width of regulation band (set to 5°C) Water return temperature Steps of unloading 6.4 Water Temperature Regulation (OUT) Regulation is performed via outlet water temperature SET POINT as shown below: When the temperature of the water leaving the unit remains within the neutral zone the capacity loading of the chiller remains unchanged. G2 OFF G1 OFF G2 OFF G1 ON G2 ON G1 ON 2-Step Type Regulation When the temperature of the water leaving the unit increases and goes outside the neutral zone the controller increases the capacity loading. When the temperature of the water leaving the unit decreases and goes outside the neutral zone the controller decreases the capacity loading. BAND ZONE G1 OFF G2 OFF G1 ON G3 OFF G2 ON G4 OFF G3 ON 4-step Type Regulation NEUTRAL T. WATER (OUT) G4 OFF TR IMPOSTAZIONE SET SET Outlet Water Temperature Regulation 28 RLC-A, RLC-B Control Panel 29 RLC-A R/P/D Control Panel (Heat Recovery) 30 6.5 Control panel Key Function Display Displays operating and fault parameters. SET POINT + key. (increase temperature SET POINT). SET POINT - key. (rreduces temperature SET POINT). Key Funtion Voltage indicator LED. Indicates that unit is connected to power supply. Anti-freezing alarm LED. Indicates that water temperature at evaporator outlet is below safe limit. External interlock alarm LED. SET POINT display key. Page key. Calls data display pages. Circuit 1 or 2 power key and LED. (Select circuit 1 or 2). 100% power level indicating LED for circuit 1 and 2 compressors. Compressor partialisation indicating LED for circuit 1 and 2 compressors Circuit 1 or 2 high pressure alarm LED. Indicates that high pressure switch for circuit 1 or 2 has been activated. Fan thermal overload alarm LED Indicates that a fan thermal overload cut-out has been activated. Warm weather mode start key and LED. Starts the unit in the cooling mode. Led lights up to indicate operating in cooling mode. Heat Recovery start key and LED. Starts the unit heat recovery mode. Led lights up to indicate operating in recovery mode. Service mode key and LED. (For use only by authorised service personnel). Circuit 1 or 2 low pressure alarm LED. Indicates that low pressure switch for circuit 1 or 2 has been activated. Circuit 1 or 2 differential oil pressure alarm LED (semihermetic compressor only). Indicates that differential oil pressure switch for circuit 1 or 2 has been activated. Circuit 1 or 2 compressor thermal overload alarm LED. Indicates tht compressor thermal overload has been activated for circuit 1 or 2. 31 6.6 Unit Starting Data and Temperature Display Proceed as follows to start the unit: ■ ■ Display 1 (Models RLC 150 to RLC 800) Turn the master isolating switch to the ON position to energise unit. Check that In Tmp Wat Out Tmp Wat LED (voltage indicator) goes on. The following display will appear on screen: Evaporator inlet water temperature Evaporator outlet water temperature ■ Wait (circa 10 sec.) for this message to disappear and check that there are no active alarm signals. ■ key for each circuit. unit is now in stand-by and ciated circuits are on. Press Air temperature LED’s for the asso- key to start the unit in the cooling mode. LED will go on. Compressor operation and power level will be indicated by ■ LED’s for each circuit. Check that SET POINT is as desired (SET POINT established at the factory is 8°C). If necessary, change the set point as described in 6.7. 32 Condenser Coils Air Tmp Prepare the two circuits for operation by pressing the ■ Display 2 ■ Display 3 The heat recovery function is by means of a fourway valve in the discharge line from the compressor to the condenser. The four-way valve diverts hot refrigerant gas to the recovery condenser, when the thermostat is calling for heat. Hour Counter When the leaving warm water temperature reaches the set point of the thermostat the four-way valve diverts the refrigerant to the air cooled condenser and the heat is dissipated to the ambient air. As the warm water temperature leaving the recovery vessel falls below the set point of the thermostat the four-way valve diverts the refrigerant back to the heat recovery condenser. Operating hours for compressors 1 and 2. Press key to scroll displays. Alarm readouts are shown at the foot of display 3. Press page key again to return to display 1. 6.7 Set point To display cooling mode SET POINT: ■ Press key with unit operating in cooling mode. To change SET POINT, Proceed as follows: 6.9 Alarm Display and Reset Alarms are indicated by the associated panel LED’s and by messages on the liquid crystal display. The letters “AL” will appear in the upper right corner of display to indicate that an alarm is active or has been stored in memory. To display alarm, press page key appears. several times until the alarm display To reset and delete memorised alarms, press page key ■ Display SET POINT as directed above; ■ Press page key changed. ■ Change digit using ■ Press ■ To change SET POINT with compressors off, de- until the following display appears: to move onto the digit to be and keys; key to confirm; activate the two circuits by pressing keys. 6.8 Heat Recovery Operation The heat recovery option is activated by the heat recovery start key on the control panel, which is illuminated when activated. Heat recovery operation is controlled by a factory wired thermostat, mounted by the installer, in the warm water flow from the heat recovery condenser(s). Then press key to delete and reset alarms 6.10 Unit Shutdown ■ Press warm weather mode key unit. to stop the ■ Turn master isolating switch to OFF position to de-energise the unit. 6.11 Electromechanical Safety Devices Each refrigerating circuit on the RLC Series units is protected by anti-freezing devices implemented by the “Chiller Control” panel and a set of electromechanical safety devices including a high pressure switch, a low pressure switch and a differential oil pressure switch (units with semi-hermetic compressor only). 33 Ant-freezing device (supplied with unit) Low pressure switch Units are provided with anti-freezing device consisting of an electric heating element in contact with the refrigerant/water heat exchanger. Heating element is activated whenever water temperature drops below 2°C, even when the unit is off. An antifreeze alarm stops the unit if outlet water temperature drops below 3°C. During the cold season, it is advisable to drain water circuit to prevent ice damage to lines. If this is not possible, do not cut off power supply to the unit to ensure that the anti-freeze heating element will be activated if needed. Automatic-reset switch opens contacts. Circuit can be reset manually through “Chiller Control” panel. Differential oil pressure switch This instrument is provided on circuits with semihermetic compressor. Switch senses pressure differential across compressor casing and compressor oil delivery. Switch cut-in is delayed 120 seconds to allow pressure to rise after compressor start-up. Circuit can be reset manually through control panel. High pressure switch Manual-reset switch opens contacts. Circuit can be reset manually through “Chiller Control” panel, after resetting device. Alarm Displays 34 Compressor 1 or 2 Thermal Overload Cut-out Circuit 1 or 2 Fan Thermal Overload Cut-out Circuit 1 or 2 HIGH Pressure Switch * Circuit 1 or 2 HIGH Pressure Limit Exceeded Evap. Outlet 1 Water Low Temp. Limit Exceeded * Circuit 1 or 2 Low Pressure Limit Exceeded Evap. Outlet 2 Water Temp. Limit Exceeded Evap. Inlet Water High temperature Limit Exceeded Evap. Inlet Water Low Temperature Limit Exceeded circuit 1 or 2 LOW Pressure Switch Compressor 1 or 2 Maintenance Circuit 1 or 2 Differential Oil Pressure Switch Analogue Input for Remote Setpoint Out of Range Temperature Set Point Out of Range External Interlock Mistake in Interface Managing EPROM Damaged Timer Missing or Not Working * Only if optional pressure and temperature sensors are fitted Scheduled Maintenance Operation 7.1 General Requirements The RLC range has been designed to work continuously provided they are regularly maintained and operated within the limitations given in this manual. each unit should be maintained in accordance with the schedule by the operator/customer, backed up by regular service and maintenance visits by an authorised Service Centre. It is the responsibility of the owner to provide for these regular maintenance requirements and/or enter into a maintenance agreement with a Service Centre to protect the operation of the unit. If damage or a system failure occurs due to improper maintenance during the warranty period, manufacturer shall not be liable for costs incurred to return the unit to satisfactory condition. This maintenance section applies only to the basic RLC unit and may, on individual contracts, be supplemented by additional requirements to cover any modifications or ancillary equipment as applicable. Daily Unless otherwise indicated, the maintenance operations described below can be performed by any properly trained maintenance technician. Check evaporator leaving liquit temperature Check heat evaporator pressure drop Check electrical power consumption Check suction pressure and temperature Check discharge pressure and temperature Check compressor oil level Check for gas bubbles in refrigerant Check finned coil cleanliness Check oil heater efficiency Check Remote Control Unit Check low pressure switch Check high pressure switch Check diff. oil pressure switch Check heat exchanger insulation Check clamp tightness Check terminal screw tightness Clean outside surface with soapy water Straighten coil fins Check density of any circulating brine Drain evaporator of add antifreeze End of Season Never discard used compressor oil, as it contains refrigerant in solution. Return used oil to the oil manufacturer. The Safety Section of this manual should be read carefully before attempting any maintenance operation on the unit. The maintenance checks should be carried out in accordance with the maintenance schedule detailed below by a competent person. Please note, however, that RLC series units are not generally user serviceable and no attempt should be made to rectify faults or problems found during daily checks. If in any doubt, contact an Authorised Service Centre. Start of Season WARNING Never release refrigerant to the atmosphere when emptying the refrigerating circuit. Suitable retrieval equipment must be used. If reclaimed refrigerant cannot be re-used. It must be returned to the manufacturer. 7.2 Daily Maintenance Monthly WARNING MAINTENANCE Weekly 7 • • • • • • • • • • • • • • • • • • • • 35 7.3 Refrigerant Charge CAUTION Never introduce liquid refrigerant in the low pressure side of circuit. Extreme care must be taken to ensure that circuit is correctly charged. An insufficient charge will lead to poor machine performance. In extreme cases, the low pressure switch will cut in and lock the circuit. Excessive charge will raise the condensation pressure (which in extreme cases will cause the high pressure switch to cut in and lock the circuit) with a consequent increase in power consumption. Under no circumstances must the compressor be used as a vacuum pump to purge circuit. CAUTION The refrigerant circuit must be charged whenever it is emptied for maintenance purposes (leak repair, compressor replacement, etc.). Charge quantities are given in Section 9. Before charging, the ci rcuit must be vacuum-purged and dried, reaching a minimum absolute pressure of 50 Pa. The refrigerant gas must be introduced to eliminate vacuumand to charge the circuit to 90% of the total required gas in liquid formthrough the appropriate charging valve on liquid line at condenser outlet. A refrigerant container should then be connected to the charging valve on suction line, the container should be held so that only gaseous phase refrigerant is released. The compressor should be started and gas allowed to flow from the refrigerant container until liquid in the sight glass runs clear and gas temperature at evaporator outlet has stabilised at around 5°C. 36 7.4 Refrigerant Circuits Each RLC Series unit is equipped with two fully independent refrigerating circuits. Units are equipped with a single tube bundle evaporator with two separate circuits on refrigerant side and a single circuit on water side. 7.5 Compressors Compressors are supplied with the correct quantity of lubricant required for operation. Under normal operating conditions, refrigerant charge and lubricant will last the life of the machine. Fluid top-up is not required as long as refrigerating circuit operates correctly and no repair operations have been carried out. Should it be necessary to replace compressor (e.g. as a result of winding burnout or mechanical failure), contact an authorised ServiceCentre. CAUTION RLC models functioning with refrigerant R407C and R134a employ compressors charged with polyester oils. During compressor maintenance, or the opening of any part of the refrigerant circuit, remember that this oil is extremely hydroscopic, and, therefore, avoid long exposure to the ambient air, which would require that the complete oil charge be replaced. 7.6 Condenser Coils 7.8 Filter Drier Condenser coils feature copper tubes and aluminium fins. Should refrigerant leakage take place as a result of accidental impact or damage. The coils must only be repaired or replaced by an Authorised Service Centres. Refrigerating circuits are provided with filter/driers. To ensure high condenser coil serviceability and heat exchange, the condenser surfaces must be kept free of impurities such as leaves, fibres, insects, dirt etc. Soiled condenser coils will increase power consumption. In addition, the maximum pressure alarm may cut in and lock out the unit. Filter/drier clogging will be indicated by bubbles in the sight glass, or by a difference in temperature upstream and downstreamof filter/drier. Take care not to damage aluminium fins during cleaning. The filter/driers are inspectable cartridge type on models 210/800, and non-inspectable strainer type on smaller units. If bubbles persist after changing cartridge, the machine has lost part of its refrigerant charge through one or more leaks which must be identified and repaired. 7.9 Sight Glass CAUTION The condenser should be cleaned using compressed air directed parallel to aluminium fins and in the opposite direction to that of normal air circulation. A vacuum cleaner may be used to clean the condenser coil from outside. The coil may also be cleaned with soapy water using a suitable spray nozzle. 7.7 Condenser Fans The sight glass is used to observe refrigerant flow and moisture content. Bubbles in flow indicate that filter/drier (where provided) is clogged, or that refrigerant charge is low. A colour indicator is located inside the sight glass. Compare the colour of the indicator with the scale on the sight glass lock ring to determine the moisture content of refrigerant. If moisture content is too high, proceed as follows: Each condenser fan features a wing-profile impeller and cylindrical nozzle. The fan motor bearings are lubricated for life. For machines with hermetic compressors, discharge the circuit without releasing refrigerant to the atmosphere. Vacuum-purge the circuit and replenish the charge. Ensure that fans rotate in the direction indicated by arrowbefore starting machine following repair work involving 3-phase disconnection (air flow up wards). For machines with semi-hermetic compressors, change the filter cartridge, operate the unit for one day and check the moisture content again. If fan rotation is not correct, disconnect and invert two of the three phases supplying the motor. No further action is required if the moisture content returns to normal. If the moisture content is still too high, change the filter/drier again, start the unit and operate for a further day. 37 7.10 Thermostatic Expansion Valve 7.11 Evaporator RLC refrigerating circuits are provided with a thermostatic expansion valve with an external equaliser. Valves are calibrated at the factory for a 5°C temperature rise. Check the heat exchanger water side for cleanliness at regular intervals. This may be accomplished by checking water side pressure drop (refer to Section 9) or simply by checking the fluid temperatures at heat exchanger inlet and outlet and comparing them with evaporation temperatures. To check the temperature rise: Read the suction pressure on the units gauge panel or on a pressure gauge connected to charging valve on suction side. Using the pressure gauge temperature scale, determine the saturated suction temperature Tsa corresponding to this pressure. Determine the effective suction temperature Tse using a contact thermometer applied to the evaporator gas outlet fitting. Temperature rise S is given by: S = Tse - Tsa The temperature rise can be corrected using the adjuster screw on the thermostatic expansion valve. Turn the adjuster screw through a single revolution and operate the unit for five minutes. Then check the temperature rise again and correct as necessary. If the thermostatic expansion valve does not react to temperature rise calibration, it is probably malfunctioning and must be replaced. Valve replacement must be performed by an authorised Service Centre. 38 For effective heat exchange, the water outlet temperature and the saturated evaporation temperature should differ by 5 to 7°C. A larger difference indicates that the heat exchanger is operating inefficiently, and is thus soiled. If soiled, the heat exchanger must be chemically cleaned by authorised Itelco-Clima service personnel. For other types of service (special maintenance, heat exchanger replacement, etc.), contact an authorised Service Centre. 8 TROUBLE SHOOTING The following table details possible unit faults, their probable cause and suggested remedies. For any other problems not immediately recognisable and/or for technical assistance, call an Authorised Service Centre. Fault Probable Cause Remedy Differential oil pressure switch cuts on, break circuit Defective differential pressure switch operation. Check switch operation, replacing if necessary. Low oil level as a result of circuit leakage. Determine location of leak and repair. Start up with cold oil. Check oil heater operation. Compressor lube circuit malfunction. Call an Authorised Centre. Low refrigerant charge. Top up charge. Drier/filter clogged. Replace drier/filter Loss of efficiency in one or both circuits. Check compressor valves, replacing if necessary (semi-hermetic compressor only). Temperature rise of thermostatic valve out of calibration. Increase setting. Unit operates continuously, but without cooling. Suction line freezes. Check charge. Excessive noise. Vibrating lines. Secure lines. Check line retention. Thermostatic expansion valve hiss. Top up charge. Check filter/drier, replacing if necessary. Noisy compressor. Check condition of valves. Bearings have seized; replace compressor. Check that compressor retaining nuts are tight. Low compressor oil level. One or more gas or oil leaks in circuit Identify and eliminate all leaks Mechanical damage to compressor. Call an Authorised Service Centre Faulty crankcase oil heater. Check electrical circuit and crankcase heater element operation, replacing any defective components. 39 Fault Probable Cause Remedy One or both compressors not working. Power circuit interrupted. Check power circuit for earth leakage and shorts. Check fuses. High pressure switch activation. Reset pressure switch from panel and re-start machine. Identify and eliminate causes of pressure switch activation. Control circuit fuse blown Check control circuit for earth leakage and shorts. Change fuses. Loose terminal clamps. Check clamp tightness. Power circuit thermal overload cut-out activation. Check operation of control and safety devices. Identify and eliminate cause of activation. Incorrect wiring. Check control and safety device wiring. Line voltage too low. Check line voltage. If problem due to system, eliminate it. If problem is due to distribution network, inform the electricity supply company. Compressor motor short-circuited. Check motor winding continuity. Compressor seizure Replace compressor. Gas leakage. Identify and eliminate leakage. Insufficient charge. Top up charge. Pressure switch failure. Replace pressure switch. High pressure switch malfunction. Check switch operation, replacing if necessary. Delivery valve partially closed. Open valve, replacing if necessary. Non-condensables in circuit. Purge circuit. Condenser fan(s) inoperative. Check wiring and motors. Repair or replace if necessary. Liquid line too hot. Insufficient charge. Identify and eliminate causes of charge loss and top up charge. Liquit line freezes Liquid line valve partially closed. Check that all valves are open. Receiver/drier clogged. Replace cartridge. Low pressure switch cuts in, braking circuit. High pressure switch cuts in, braking circuit. 40 9 TECHNICAL DATA 9.1 Pressure Drop Graphs PRESSURE DROP (kPa) RLC-A & RLC-B All Models - Evaporator FLOW RATE (l/s) 41 PRESSURE DROP (kPa) RLC-A R/P Models – Heat Recovery Condenser FLOW RATE (l/s) Note: R Models - Pressure drop is for each Condenser 42 PRESSURE DROP (kPa) RLC-A /D Models - Desuperheater FLOW RATE (l/s) Note: Pressure drop is for each Desuperheater 9.2 Safety Switch Settings RLC-A & RLC-B All Models Model 210 240 300 360 400 450 Low Pressure Switch bar 0,4 (0,2)(2) High Pressure Switch bar 28 (22)(2) TUV High Pressure Switch(1) bar 25 0,8 Oil Pressure Switch bar Anti Freezing Thermostat °C Safety Valve bar 525 600 700 800 3 None 24 Nota: 1 Also heat recovery, heat pump in the winter mode 2 RLC-A models 43 9.3 Operational Limits RLC-B All models 210 Model Evaporator Water Outlet Temperature Evaporator (Water) 15 6 15 Brine Outlet °C -5 15 -5 15 °C l/s 3 1,5 8 10 3 2,3 8 10 kPa 7,5 to 85 bar 10 °C -5 to 48 °C -20 to 48 Standard Unit Pa 0 Units with Speed Control Pa 0 Pa 100 Units with High Pressure Fans Power Supply Voltage 400 V, 3 Ph, 50 Hz Recommended System Water Volume(1) V l 342 to 462 1250 300 Model Evaporator (Water) 450 525 600 700 800 °C 6 15 6 15 5 15 5 15 5 15 5 15 5 15 5 15 Brine Outlet °C -5 15 -5 15 -5 15 -5 15 -5 15 -5 15 -5 15 -5 15 °C l/s 3 4 8 16 3 4 8 3 8 3 8 16 5,2 22 5,8 25 3 7 8 28 3 8 8 33 3 10 8 42 3 11 8 48 Maximum Pressure Water/Brine Side Standard Unit Air on Temperature Unit with Condenser Speed Control kPa 7 bar 10 °C -10 to 48 -5 to 46 -10 to 46 °C -20 to 48 -20 to 46 -20 to 46 Standard Unit Pa 0 Unit with Speed Control Pa 0 Pa 100 Units with High Pressure Fans Power Supply Voltage 400 V, 3 Ph, 50 Hz Recommended System Water Volume(1) V l 1350 1600 Note: 1 Table shows minimum water/brine volume of the primary water system 44 400 Water Outlet Temperature Spread Flow Rate Water/Brine Maximum External Static Pressure 360 1500 Min. Max. Min. Max. Min. Max. Min. Max. Min. Max. Min. Max. Min. Max. Min. Max. Pressure Drop Water/Brine Condenser (Air) Max. 6 Maximum Pressure Water/Brine Side Standard Unit Air on Temperature Units with Condenser Speed Control Evaporator Water Outlet Temperature Min. °C Temperature Spread Flow Rater Water/Brine Maximum External Static Pressure Max. Water Outlet Pressure Drop Water/Brine Condenser (Air) 240 Min. 2050 342 to 462 2450 2850 3250 3900 4480 RLC-A All Models 210 Model Evaporator Water Outlet Temperature Evaporator (Water) RLC-A/R/P Desuperheater RLC-A/D 15 5 15 Brine Outlet °C -10 15 -10 15 °C l/s 3 2,3 8 10 3 2,3 8 10 kPa 7,5 to 85 bar 10 °C -5 to 48 °C -20 to 48 Standard Unit Pa 0 Units with Speed Control Pa 0 Pa 100 °C °C 35 to 50 3 to 10 °C 40 to 70 Units with High Pressure Fans Water Outlet Temperature Spread Water Outlet Power Supply Voltage 400 V, 3 Ph, 50 Hz Recommended System Water Volume(1) V l Evaporator (Water) RLC-A/R/P Desuperheater RLC-A/D 400 450 525 Max. Min. Max. Min. Max. Min. Max. Min. Max. 5 15 5 15 5 15 5 15 5 15 Brine Outlet °C -10 15 -10 15 -10 15 -10 15 -10 15 °C l/s 3 4 8 16 3 4 8 16 3 4 8 16 3 4 8 16 3 4 8 16 kPa 7,5 to 85 bar 10 °C -10 to 48 °C -20 to 48 Standard Unit Pa 0 Units with Speed Control Pa 0 Pa 100 °C °C 35 to 50 3 to 10 °C 40 to 70 Maximum Pressure Water/Brine Side Standard Unit Air on Temperature Units with Condenser Speed Control Condenser HRC 360 Min. °C Temperature Spread Flow Rate Water/Brine Maximum External Static Pressure 1500 Water Outlet Pressure Drip Water/Brine Condenser (Air) 342 to 462 1250 300 Model Evaporator Water Outlet Temperature Max. 5 Maximum Pressure Water/Brine Side Standard Unit Air on Temperature Units with Condenser Speed Control Condenser HRC Min. °C Temperature Spread Flow Rate Water/Brine Maximum External Static Pressure Max. Water Outlet Pressure Drop Water/Brine Condenser (Air) 240 Min. Units with High Pressure Fans Water Outlet Temperature Spread Water Outlet Power Supply Voltage 400 V, 3 Ph, 50 Hz Recommended System Water Volume(1) V l 1350 1600 342 to 462 2050 2450 2850 Note: 1 Table shows minimum water/brine volume of the primary water system 45 9.4 Physical Data RLC-B 210 - 240 Model 210 Type Circuit 1 Theoretical Displacement m3/h 107 Compressor Evaporator Theoretical Displacement Quantity Number of Cylinders Revs. per Minute Oil Charge per Compressor Number of Loading Stages Quantity Type (Direct Expansion) Number of Refrigerant Circuits Water Volume per Evaporator Refrigerant Volume Face Area Air Cooled Condenser Note: 1 Per condenser 46 m3/h 107 127 rpm 2 6 1450 2 6 1450 dm3 7,4 7,7 100/50 1 100/50 1 Shell and Tube l dm m2 3 Number of Rows Fan Diameter Number Fans Power Input at 890 rpm Air Flow Rate Refrigerant Charge R 407C Operational Weight Aluminium Fins Shipping Weight Copper/Copper Coils RLC/R Additional Weight RLC/P RLC/D Length Width Dimensions Height 127 semi-hermetic Type Circuit 2 240 semi-hermetic mm kW m3/s kg kg kg kg kg kg kg mm mm mm 2 2 33 33 16,7 8,3 16,7 8,3 2 3 710 6 0,9 24 2 x 15 1780 1740 344 190 95 40 4040 2040 1730 710 6 0,9 22 2 x 21 1890 1850 344 200 100 50 4040 2040 1730 RLC-B 300 - 800 Model 300 360 400 450 525 semi-hermetic 600 700 800 151 180 202 180 180 180 180 Type Circuit 1 Theoretical Displacement m3/h semi-hermetic Type Circuit 2 Compressor Theoretical Displacement Quantity Number of Cylinders Revs. per Minute Oil Charge per Compressor m3/h 151 180 210 243 284 324 406 464 rpm 2 8 1450 2 8 1450 2 8 1450 2 6 1450 2 7 1450 2 8 1450 2 7 1450 2 8 1450 dm3 7,7 7,7 7,5 20 20 20 20 20 100-50 100-50 1 1 100-75 50-25 1 100-75 50-25 1 100-75 50-25 1 100-75 50-25 1 2 55 27,4 11 2 55 27,4 11 2 87 38,9 16 2 125 60 16 2 222 80 20 2 206 92,3 24,6 2 3 2 3 3 4 4 4 710 8 0,9 32 2 x 21 2430 2380 258 250 115 50 5040 2040 1730 710 8 0,9 30 2 x 30 2570 2520 389 250 125 60 5040 2040 1730 800 6 1,5 35 2 x 33 4500 4400 700 600 200 150 4860 2240 2225 800 6 1,5 34 2 x 40 4800 4700 700 800 400 200 4860 2240 2225 800 8 1,5 44 2 x 44 5200 5100 700 800 400 200 4860 2240 2225 800 8 1,5 43 2 x 50 5600 5500 736 800 400 200 4860 2240 2225 800 10 1,5 53 2 x 63 6640 6450 700 660 400 200 6100 2260 2250 800 12 1,5 64 2 x 74 7050 6900 700 660 400 200 7100 2260 2250 Number of Loading Steps Evaporator Quantity Type (Direct Expansion) Number of Refrigerant Circuits Water Volume per Evaporator Refrigerant Volume Face Area Air Cooled Condenser dm3 dm3 m2 Number of Rows Fan Diameter Number Fans Power Input at 890 rpm Air Flow Rate Refrigerant Charge R 407C Operational Weight Aluminium Fins Shipping Weight Copper/Copper Coils RLC/R Additional Weight RLC/P RLC/D Length Dimensions Width Height 180 mm kW m3/s kg kg kg kg kg kg kg mm mm mm 100-75 100-75 50-25 50-25 1 1 Shell and Tube 2 2 80 133 44,8 52,9 16 16 Note: 1 Per condenser 47 RLC-A 210 - 525 Model 210 240 300 360 semi hermetic 400 450 525 151 181 210 284 348 406 464 Type Circuit 1 Theoretical Displacement m3/h Type Circuit 2 Compressor Theoretical Displacement Quantity Number of Cylinders Revs. per Minute Oil Charge per Compressor semi hermetic m3/h Evaporator Air Cooled Condenser Note: 1 Per condenser 48 210 284 348 406 464 2 2 8 1450 2 8 1450 2 7 1450 2 6 1450 2 7 8 1450 rpm 1450 l 7,7 7,7 7,5 23 20 20 20 100 50 1 ED 135 2 100 50 1 ED 135 2 100 50 1 ED 220 2 100 50 1 ED 220 2 100-75 50-25 1 ED 310 2 100-75 50-25 1 ED 360 2 100-78 50-28 1 ED 420 2 l 33 33 48 48 80 95 115 dm3 m2 16,7 8,3 16,7 8,3 27,4 11 27,4 11 38,9 16 44,8 16 52,9 16 2 3 2 3 2 3 3 710 6 0,9 24 710 6 0,9 22 710 8 0,9 32 800 6 1,5 35 800 6 1,5 35 800 6 1,5 34 800 8 1,5 44 Number of Rows Fan Diameter Number Fans Power Input at 890 rpm Air Flow Rate Heat RLC-A/R/P Recovery /R 2 Condenser Condenser /P 1 Condenser Water Volume(1) Refrigerant Volume(1) RLC-A/D Desuperheater Refrigerant Volume Refrigerant Charge R 134A Operational Weight Aluminium Fins Shipping Weight Copper/Copper Coils RLC-A/R Additional Weight RLC-A/P RLC-A/D Length Dimensions Width Height 181 2 8 1450 Number of Loading Stages Quantity Type (Direct Expansion) Number of Refrigerant Circuits Water Volume per Evaporator Refrigerant Volume Face Area 151 mm kW m3/s Type l dm3 Type dm3 kg kg kg kg kg kg kg mm mm mm Shell and Tube 9,4 12,1 23,4 32,3 Shell and Tube 2 x 15 2004 1944 344 190 95 40 4040 2040 1730 2 x 21 2114 2064 344 200 100 50 4040 2040 1730 2 x 21 2430 2360 258 250 115 50 5040 2040 1730 2 x 30 5380 5280 389 250 125 60 4860 2240 2225 2 x 34 5650 5550 700 600 200 150 4860 2240 2225 2 x 40 5700 5600 700 800 400 200 4860 2240 2225 2 x 45 5880 5780 700 800 400 200 4860 2240 2225 9.5 Total Unit Electrical Data RLC-A All Models Model Current Input (A) Power Input (kW) 210 240 300 360 400 450 525 Nominal 114 140 128 175 203 241 273 Maximum(2) 128 162 160 229 257 311 347 Nominal(1) 53 65 73 95 115 134 140 Maximum(2) 65 79 89 119 145 169 194 322 387 340 424 438 569 590 (1) Maximum Starting Current (A) Nota: 1 Nominal conditions 7°C chilled water outlet temperature, 35°C ambient temperature 2 Maximum condition at 14°C chilled water outlet temperature, 45°C ambient temperature Table applicable to units with standard fans RLC-B All Models Model Current Input (A) Power Input (kW) 210 240 300 360 400 450 525 600 700 800 116 136 158 184 205 219 261 293 361 417 Maximum 138 160 190 218 255 267 323 373 439 503 Nominal(1) 59 69 82 96 113 121 144 162 199 230 Maximum(2) 77 87 101 119 137 147 170 192 239 274 237 270 354 418 467 568 734 759 947 982 Nominal(1) (2) Maximum Starting Current (A) Nota: 1 Nominal conditions 7°C chilled water outlet temperature, 35°C ambient temperature 2 Maximum condition at 14°C chilled water outlet temperature, 45°C ambient temperature Table applicable to units with standard fans 49 9.6 Compressor Electrical Data RLC-A All Models Power Input per Compressor(1) (kW) Current per Compressor(1) (A) Power Input per Compressor(2) (kW) Current per Compressor(2) (A) Starting Current(3) (A) Fuse Size(4) Model Circuit Voltage(5) (V) 210 1+2 400 24 51 30 60 250 200 240 1+2 400 30 64 37 75 300 200 300 1+2 400 32 56 41 72 252 200 360 1+2 400 43 79 55 106 301 250 400 1+2 400 53 93 68 120 301 315 450 1+2 400 61 112 80 147 405 400 525 1+2 400 70 125 91 162 405 400 Nota: 1 2 3 4 5 Nominal conditions at 7°C chilled water outlet temperature, 35°C ambient temperature Maximum condition at 14°C chilled water outlet temperature, 45°C ambient temperature Compressors Starting, Part Winding Fuse sizes stated are maximum values, smaller sizes may be used if applicable Minimum allowable supply voltage 342 Volts RLC-B All Models Model Circuit Voltage(5) (V) Power Input per Compressor(1) (kW) Current per Compressor(1) (A) Power Input per Compressor(2) (kW) Current per Compressor(2) (A) Starting Current(3) (A) Fuse Size(4) 210 1+2 400 27 52 34 63 161 200 240 1+2 400 32 62 39 74 183 200 300 1+2 400 38 70 47 87 250 250 360 1+2 400 45 84 56 101 300 250 400 1+2 400 52 94 64 119 329 250 450 1+2 400 56 101 69 125 424 315 525 1+2 400 66 119 79 150 559 400 600 1+2 400 75 135 90 175 559 400 700 1+2 400 92 166 112 205 711 500 800 1+2 400 106 191 128 234 711 500 Nota 50 1 2 3 4 5 Nominal conditions at 7°C chilled water outlet temperature, 35°C ambient temperature Maximum condition at 14°C chilled water outlet temperature, 45°C ambient temperature Compressors Starting, Part Winding Fuse sizes stated are maximum values, smaller sizes may be used if applicable Minimum allowable supply voltage 342 Volts 9.7 Fan Electrical Data RLC-A All Models Model RLC-A 210-300 RLC-A 360-525 Nominal Power (kW) 0,9 1,5 Standard fans Max Running Current (A) 1,95 2,9 Max Starting Current (A) 5,9 8,8 Nominal Power (kW) 2,9 4,7 High Pressure Fans Max Running Current (A) 4,8 8,7 Max Running Current (A) 7,6 28 Nominal Power (kW) 0,9 1,5 Standard fans Max Running Current (A) 1,95 2,9 Max Starting Current (A) 5,9 8,8 Nominal Power (kW) 2,9 4,7 High Pressure Fans Max Running Current (A) 4,8 8,7 Max Running Current (A) 7,6 28 RLC-B All Models Model RLC-B 210-360 RLC-B 400-800 51 9.8 Sound Power Levels RLC-A All models Model 210 240 300 360 400 450 525 (1) (2) (1) (2) (1) (2) (1) (2) (1) (2) (1) (2) (1) (2) 125 90 78 91 78 92 78 91 80 93 83 93 86 96 87 250 93 81 92 85 96 87 95 87 96 91 96 90 99 93 500 95 87 95 88 97 92 99 94 98 94 98 94 101 95 Octave Band (Hz) 1000 90 83 90 84 91 85 93 84 94 87 94 88 95 89 2000 86 77 85 77 88 77 84 77 86 77 86 74 86 75 4000 75 67 80 69 79 69 80 70 78 67 78 67 79 68 8000 69 57 70 58 70 59 71 60 73 67 73 67 74 68 2000 86 77 84 76 88 76 84 76 85 76 85 74 86 78 88 85 88 78 89 88 4000 75 67 80 69 79 69 80 70 78 67 78 67 79 68 81 77 81 72 82 74 8000 69 57 70 59 70 59 71 60 73 67 73 67 74 68 75 70 75 68 76 71 Total dB(A) 95 87 95 88 97 90 98 92 98 93 98 93 100 94 Nota: Reference data with machine operating at nominal condition 12°/7°C chilled water 1 > 38°C ambient RLC-A (Standard Version) 2 < 25°C ambient RLC-A/Q (Quiet Version) Tolerance +/- 2 dB(A) RLC-B All Models Model 210 240 300 360 400 450 525 600 700 800 (1) (2) (1) (2) (1) (2) (1) (2) (1) (2) (1) (2) (1) (2) (1) (2) (1) (2) (1) (2) 125 90 78 91 78 92 78 91 80 93 83 93 86 96 87 94 87 96 87 97 88 250 92 83 93 83 95 87 95 86 96 88 96 88 98 90 97 91 98 92 99 92 500 95 87 95 88 97 89 96 90 98 90 98 91 100 92 100 93 101 95 102 95 Octave Band (Hz) 1000 91 83 92 84 91 86 94 86 94 89 94 90 96 90 96 90 97 92 98 92 Nota: Reference data with machine operating at nominal condition 12°/7°C chilled water 1 > 38°C ambient RLC-A (Standard Version) 2 < 25°C ambient RLC-A/Q (Quiet Version) Tolerance +/- 2 dB(A) 52 Total dB(A) 95 87 95 88 97 89 97 90 98 91 98 92 100 93 100 94 101 95 102 96 9.9 Dimension, Weight and Isolator Data RLC-A All Models RLC-A 300 RLC 210-240; 400-600 RLC-A 60-150 Compressor/ Control panel Top view Centre of gravity Model Dim. X Y A B C D Z Pos. 1 and 2 3 and 4 5 and 6 7 and 8 9 and 10 210 240 1550 140 790 1468 1500 1550 140 790 1468 1500 1930 1930 2004 2114 231 366 265 140 251 376 280 150 300 360 Dimensions (mm) 2060 1860 140 140 790 790 1468 2342 1710 1277 790 1930 2090 Overall Weight (kg) 2430 5380 Weight Distribution (kg) 245 619 365 667 265 540 220 464 120 400 450 525 1880 232 783 2342 1277 1890 232 783 2342 1277 1940 232 783 2342 1277 2090 2090 2090 5650 5700 5880 668 667 580 490 870 890 580 510 860 896 625 540 53 RLC-B All Models RLC-B 300-360; 700-800 RLC-B 210-240; 400-600 RLC-B 60-150 Compressor/ Control panel Top view Centre of gravity Model Dim. X Y A B C D Z Pos. 1 and 2 3 and 4 5 and 6 7 and 8 9 and 10 54 210 240 300 1680 140 790 1468 1500 1670 140 790 1468 1500 1930 1930 2060 140 790 1468 1710 790 1930 1780 1890 2430 175 310 265 140 195 320 280 150 245 365 265 220 120 360 400 450 Dimensionis (mm) 2060 1980 1980 140 232 232 790 783 783 1468 2342 2342 1710 1277 1277 790 1930 2090 2090 Overall Weight (kg) 2570 4500 4800 Weight Distribution (kg) 260 585 636 385 762 805 280 496 515 230 407 444 130 525 600 700 800 1970 232 783 2342 1277 1990 232 783 2342 1277 2090 2090 2680 235 1179 1663 1440 1350 2090 3030 235 1179 1850 2160 1500 2090 5200 5600 6640 7050 725 832 567 476 776 880 631 513 720 830 740 555 475 800 835 770 600 520 SPRING ISOLATOR TABLE KIT Kit Code 462B26050-210 462B26050-240 462B26050-300 462B26050-360 462B26050-400 462B26050-450 462B26050-525 462B26050-600 462B26050-700 462B26050-800 462B26150-210 462B26150-360 462B26150-400 462B26150-450 462B26150-525 462B26150-600 462B26200-210 462B26200-240 462B26200-300 462B26200-360 462B26200-400 462B26200-450 462B26200-525 462B26200-600 462B26200-700 462B26200-800 462B26300-210 462B26300-240 462B26300-300 462B26300-360 462B26300-400 462B26300-525 462B26350-210 462B26350-300 462B26350-360 462B26350-400 462B26350-450 462B26350-525 462B26100-210 462B26100-240 462B26100-300 462B26100-360 462B26100-400 462B26100-450 462B26100-525 462B26100-600 462B26100-700 462B26100-800 462B26400-210 462B26400-240 462B26400-300 462B26400-360 462B26400-400 462B26400-525 Chiller R407C 210 240 300 360 400 450 525 600 700 800 Chiller/H R22 SPRING ISOLATOR CODE Standard Coil Al/Cu Chiller Chiller/H R134A R134A Chiller/R R134A Standard Coil Cu/Cu Chiller R134A 240 300 210 360 400 450 525 600 210 240 300 360 400/450 525 210 240 210/240 300 360 400 450 525 210 240 300 360 400/450 525 55 9.10 Piping and Instrumentation Diagrams RLC, RLC-A and RLC-B Models 210 to 240 56 RLC-A and RLC-B Models 300 to 360 57 RLC-A and RLC-B Models 400 to 450 58 RLC-A Model 525 and RLC-B Models 525 to 800 59 9.11 General Arrangements RLC-A and RLC-B Models 210 to 240 1785 60 RLC-A and RLC-B Model 300 and RLC, RLC-B Model 360 61 RLC-A Model 360 and RLC and RLC-B Models 400 to 450 62 RLC-A Model 525 and RLC-B Models 525 to 600 63 RLC-B Model 700 64 RLC-B Model 800 65 10 SPARE PARTS 10.1 Recommended Spares The table below lists the recommended spares for one unit for 2 years Components HP Switch LP Switch Differential Oil Pressure Switch Gas Filter Thermostatic Valve Auxiliary Relays Fan fuses Compressor Fuses Auxiliary Fuses Compressor Contactor Fan Contactor Power Contactor Sensor L4000 Sensor SS 100 Pressure Transducer EPROM Electronic Board Keyboard Flat Cable Qty. 1 1 1 2 1 2 6 6 6 1 1 1 1 1 1 1 1 1 1 10.2 Recommended Compressor Oils The table below lists the recommended oil type for each unit Versione RLC 210 to 360 RLC 400 to 800 RLC-A 210 to 240 RLC-A 300 to 360 RLC-A 400 to 525 RLC-B 120 to 360 RLC-B 400 to 800 Tipo d’olio 3GS 22A 325C 685 22A 685 10.3 Wiring Diagrams Wiring diagrams are fitted on control panel door. Other requests for wiring diagrams have to be required to Service Centre. 66 Marca Wiltco Suniso ABC Mobile Arctic ICI Emkerate ICI Emkerate Mobile Arctic ICI Emkerate 11 WARNING DE-COMMISSIONIG, DISMANTLING AND DISPOSAL Never release refrigerant to the atmosphere when emptying the refrigerating circuits. Suitable retrieval equipment must be used. If reclaimed refrigerant cannot be re-used. It must be returned to the manufacturer. Never discard used compressor oil, as it contains refrigerant in solution. Return used oil to the oil manufacturer. WARNING Unless otherwise indicated, the operations described below can be performed by any properly trained maintenance technician. 11.1 General Isolate all sources of electrical supply to the unit including any control system supplies switched by the unit. Ensure that all points of isolation are secured in the ‘OFF’ position. The supply cables may then be disconnected and removed. For connection points refer to Section 4. Remove all refrigerant from each system of the unit into a suitable container using a refrigerant reclaim or recovery unit. This refrigerant may then be reused, if appropriate, or returned to the manufacturer for disposal. Under NO circumstances should refrigerant be vented to atmosphere. Drain the refrigerant oil from each system into a suitable container and dispose of according to local laws and regulations governing the disposal of oily wastes. Any spilt oil should be mopped up and similarly disposed of. Isolate the unit heat exchanger(s) from all external water systems and drain the heat exchanger section( s) of the system. If no isolation valves are installed it may be necessary to drain the complete system(s). WARNING If glycol or similar solutions have been used in the water system(s), or chemical additives are contained, the solution mUST be disposed of in a suitable and safe manner. Under NO circumstances should any system containing glycol or similar solutions be drained directly into domestic waste or natural water systems. After draining, the water pipework can be disconnected and removed. Packaged units can generally be removed in one piece after disconnection as above. Any fixing down bolts should be removed and then the unit should be lifted from position using the points provided and equipment of adequate lifting capacity. Reference should be made to Section 4 for unit installation instructions, Section 9 for unit weights and Section 3 for handling. Units which cannot be removed in one piece after disconnection as above, must be dismantled in position. special care should be taken regarding the weight and the handling of each component. Where possible units should be dismantled in the reverse order of installation. WARNING Residual refrigerant oil and glycol or similar solutions may remain in some parts of the system. These should be mopped up and disposed of as described above. It is important to ensure that whilst components are being removed the remaining parts are supported in a safe manner. Only use lifting equipment of adequate capacity. WARNING After removal from position the unit parts may be disposed of according to local laws and regulations. 67