Download Generator Ratings Model: HJW-250 T5

Survey
yes no Was this document useful for you?
   Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Document related concepts
no text concepts found
Transcript
Model: HJW-250 T5
INDUSTRIAL RANGE
Powered by JOHN DEERE
Market: Australia
F10
WATER-COOLED
THREE PHASE
50 HZ
HJW-250 T5
DIESEL
CE
COMPLIANCE
Generator Ratings
SERVICE
Power
Power
Rated Speed
Standard Voltage
Available Voltages
Rated at power factor
kVA
kW
r.p.m.
PRP (Prime)
250
200
STANDBY
275
220
1.500
V
415
V
Cos Phi
240/415V
0,8
Definitions
Standby rating
These ratings are applicable for supplying continuous
electrical power (at variable load) in the event of a utility
power failure. No overload is permitted on these ratings.
The alternator on this model is peak continuous rated
(as defined in ISO 8528-3).
General Data
Documents
A full set of operation and maintenance manuals and
circuit wiring diagrams.
Prime Rating
These ratings are applicable for supplying continuous
electrical power (at variable load) in lieu of commercially
purchased power. There is no limitation to the annual
hours of operation and this model can supply 10% overload
power for 1 hour in 12 hours.
Quality Standards
Standard Reference Conditions
Note: Standard reference conditions 25°C (77°F) air inlet
temp, 100m (328ft) A.S.L. 30% relative humidity.
Fuel consumption data at full load with diesel fuel with
specific gravity of 0.85 and conforming to BS2869:1998,
Class A2.
Warranty
BS4999, BS5000, BSEN60034, BSEN61000,
IEC60034
All equipment carries full manufacturer’s warranty.
2000 hours/12 months
HIMOINSA HEADQUARTERS:
Ctra. Murcia - San Javier, Km. 23,6 | 30730 SAN JAVIER (Murcia) Spain
Tel.+34 968 19 11 28 Fax +34 968 19 12 17 Fax +34 968 19 04 20 [email protected] www.himoinsa.com
Manufacture facilities:
QR Code
SPAIN • FRANCE • INDIA • CHINA • USA
Subsidiaries:
ITALY | PORTUGAL | POLAND | GERMANY I SINGAPORE | UAE | MEXICO | PANAMÁ | ARGENTINA | ANGOLA
Model: HJW-250 T5
INDUSTRIAL RANGE
Powered by JOHN DEERE
Market: Australia
Engine Specification
PRP
Engine
Rated Output
(Kw)
Standby
230
Engine Manufacturer
255
John Deree
6068HFU55
Engine Model
Engine Type
Injection Type
Diesel 4 strokes-cycle
direct
Turbocharged &ATAAC
Aspiration Type
Cylinders Arrangement
(mm)
Bore and Stroke
Displacement
6-L
106x127
6,8
Lube Oil Specifications
SAE 3 class 10W30 /
IPE grade CD,CF
Compression Ratio
17,2:1
Fuel Consumption 100% StandBy (kg/h)
Fuel Consumption 75% StandBy(kg/h)
Fuel Consumption 50 % StandBy (kg/h)
Fuel Consumption 25 % StandBy (kg/h)
Lube Oil Consumption Full Load (g/kwh)
Total Oil Capacity
Alternator Specification
(L)
Total Coolant Capacity
Governor Type
Generator
Alternator Manufacturer
Stamford
Alternator Model
Poles
UCI 274K
4
Winding Conections (standard)
Frame Mounting
Terminals
Star-serie
S-3 11,5”
12
Insulation Type
AVR Model
Winding Pitch
Voltage Regulation NL-FL
IP Rating
Telephone Interference
Excitation System
Bearing
Coupling
Coating (Standard)
49
37,6
25,4
13,9
H class
SX460
2/3
_
+1%
A.V.R. (Electronic)
IP23
THF<2%
self-excited, brushless
Single bearing
Flexible disc
Vacuum impregnation
-
(L)
Air Filter Type
Starting System
Battery Voltage
12,7
Electronic
Dry
electric- 12 volt DC
12V
Himoinsa reserves the right to modify any characteristic without prior notice.
Weights and dimensions based on standard products.
Illustrations may include optional equipment.
Technical data described here correspond with the available information at the
moment of printing.
Industrial design under patent.
Dimensions and Weights
Soundproof
Open Skid
Dimensions and Weights
Soundproof Model
Soundproof Luxury Model
Open Skid
(L) Length (mm)
(H) Height (mm)
(W) Width (mm)
Shipping Volume seaworthy (standard supplier) (m3)
(*) Dry weight (Kg)
3800
2290
1400
12,18
3800
2615
1400
13,91
3000
1793
1170
6,29
2713
2933
1513
Wet weight (Kg)
Fuel tank capacity (L)
Autonomy (Hours)
Sound Level (db(A)@7m)
3154
3614
1919
450
12
1000
26
445
12
70/tbc
70/tbc
-
STANDARD VERSION (Metal tank)
Model: HJW-250 T5
INDUSTRIAL RANGE
Powered by JOHN DEERE
Market: Australia
Generating Sets Standard Features
Electrical system






2 pole (single phase) & 4 pole (Three phase) main circuit breaker
Battery charger
Battery charging alternator
Heavy duty starting battery
Single pole battery Isolator
Microprocessor controller
Open version




Anti-vibration mounts
Easy access for maintenance
Exhaust heat shields
Guards for shielding all rotating parts
Enclosed version additional features






Intergrated high capacity bunded fuel tank
Single point lifting frame
Sound attenuated canopy encloure made from high quality powder coated steel
Attenuation through high density rock wool material
Steel residential silencer-35db(A) attenuation.
2× Emergency stop buttons
Optionals & Accessories







Galvanized pulling skid with fork lift pockets
PMG excitation
Anti-condensation heaters
3 way fuel valves
Adjustable earth leakage relay
Water jacket pre-heater
Extended Range double containment fuel tank with galvanized base
Galvanized Base Pulling Skid
CBR40
Model: HJW-250 T5
INDUSTRIAL RANGE
Powered by JOHN DEERE
Market: Australia
Control Panel CEM7
The CEM7 is an Auto-start digital controller which is equipped on
Himoinsa generator sets,which is able to control the operation,
monitoring and protection of a generator-set.
Controller Display:
1. Valtage between each Phase& Neutral
2. Valtage between Phases
3. Current (amps) on each Phase
4. Frequency
5. Active, Aparent,& Reactive Power
6. Power Factor
7. Instant Power (kwH) and Accumulative power
8. Fuel level
9. Oil pressure, coolant temperature
10. Battery voltage,
battery charging alternator voltage
11. Engine Speed
12. Hours running
Engine Alarms:
Generator Alarms:
1.
2.
3.
4.
5.
6.
7.
8.
9.
1.
2.
3.
4.
5.
6.
7.
8.
9.
High coolant temperature
Low oil pressure
Emergency stop
Battery charging alternator
Low coolant lewel
Over Speed
Under speed
Low fuel level by sensor
Battery low voltage
Over-load
Unbalanced voltage
Over-voltage
Under-voltage
Over-frequency
Under-frequency
Short-circuit
Inverse Power
Asymmetry among phases
Related documents