Cellex TubeTrace HTX
®
®
Tubing Bundles
HPT Power-Limiting Heating Cable
TM
Product Specifications
Application . . .
Freeze Protection 5°C. Suitable for steam service to 595°C.
TubeTrace HTX is a pre-engineered electric traced tube
bundle for steam sample lines and impulse lines to pressure
transmitters. TubeTrace HTX will provide water freeze protection during -40°C 10 m/s wind conditions. HTX is suitable for superheat steam service temperatures up to 595°C.
In the past, bundles subject to high temperature exposure
were heat traced with series resistance mineral insulated
(MI) heater cables that were custom made to length to fit
each application. Measurement errors rendered bundles
with MI heater cable unusable. TubeTrace HTX solves this
problem with Thermon parallel resistance HPT heater cable.
Bundles may be purchased in long rolls and “cut-to-length”
into smaller sections in the field for any application. This
minimizes waste and speeds up installation and engineering
time. HPT is contained within TubeTrace with a “double layer
thermal insulation system” that isolates it from extreme heat
exposure. TubeTrace HTX bundles can be controlled with
ambient sensing systems that turn heater cables on when
outdoor conditions approach freezing.
TubeTrace HTX bundles are designed to withstand 595°C
superheat steam service even when power is applied to the
heater cable during ambient conditions of 5°C, no wind.
Ratings/Specifications . . .
Watt density
33 W/m @ 10°C
Supply voltages1
230 Vac Nominal
Tube temperature
Ambient controlled at 5°C
Minimum ambient
-40°C
Superheat steam service temp.
595°C
Bend radius
1
2
3
4
5
6
7
Construction . . .
1 Process Tube
2 High Temperature Woven Glass Fiber Thermal Insulation
3 Heat Reflective Layer
4 HPT Heater Cable
5 Thermal Diffusion Layer
6 Non-hygroscopic Glass Fiber
7 Polymer Outer Jacket
500 mm
Note . . .
1. Higher voltages up to 480 Vac may be possible: contact Thermon for design
assistance.
89 mm
Product Features . . .
THERMON . . . The Heat Tracing Specialists®
www.thermon.com
European Headquarters
Boezemweg 25
2641 KG Pijnacker
PO Box 205
2640 AE Pijnacker
The Netherlands
Phone: +31 (0) 15-36 15 370
Facsimile: +31 (0) 15-36 15 379
•
•
•
•
• “Cut-to-Length”
• Suitable for Superheat Steam Service Temperatures to 595°C
• Designed for Ambient Sensing Control
• Will Freeze Protect in Low Ambient of -40°C
Corporate Headquarters
100 Thermon Dr.
PO Box 609
San Marcos, TX 78667-0609
U.S.A.
Phone: +1 512-396-5801
Facsimile: +1 512-396-3627
•
•
•
Cellex TubeTrace HTX
®
®
HPT Power-Limiting Heating Cable
TM
Product Specifications
Power Output Curves . . .
Circuit Breaker Sizing and Type . . .
The power outputs shown apply to cable installed on insulated metallic pipe (using the procedures outlined in IEEE
Standard 515-1997) at the service voltages stated below.
Power output will increase due to the thermal efficiency of
TubeTrace.
Maximum circuit lengths for various circuit breaker
amperages are shown below. Circuit breaker sizing and
earth-fault protection should be based on applicable local
codes. For information on design and performance on
other voltages, contact Thermon.
Catalog Number
230 Vac
Zone Length
cm
Power Output at 10ºC
W/m
H PT 10-2
61
28
Earth-fault protection of equipment should be provided for
each branch circuit supplying electric heating equipment.
Type B and C Circuit Breakers
HPT at 230 Vac
230 Vac Service Voltage
60
Product
Type
Watts per Metre
50
40
H PT 10-2
30
20
Max. Circuit Length* vs. Breaker Size
Metres
Start-Up
Temperature
°C
10
0
-20
16 A
124
120
112
25 A
199
199
182
32 A
199
199
199
40 A
199
199
199
* Maximum circuit lengths shown are based on an instantaneous trip current
characteristic per IEC 60898 at the referenced start-up temperature and a 10°C
maintenance temperature. For maximum circuit lengths with other trip current
characteristics contact Thermon.
HPT 10-2
10
0
0
30
60
90
Pipe Temperature °C
150
120
How to Specify . . .
SEI-6F1-53-1-ATPVC-1-HTX-M
Bundle Type
M or I
SEI = Single Tube
MEI = Multiple Tubes
Process
Tube O.D.
Process Tube Material
2 = 1/4"
A = 316 SS Welded
Metric or Imperial Indication
1
High Temperature
3 = 3/8"
As = 316 Ti SS Welded
4 = 1/2"
D = Monel 2
Number
of Tubes
6 = 6 mm
E = Titanium
1
10 = 10 mm
F = 316 SS Seamless
2
12 = 12 mm
Fs = 316 Ti SS Seamless
G = 304 SS Welded
H = 304 SS Seamless
HTX = 595°C Continuous
Heater Cable Option
1 = BN Nickel Plated Braid
7 = OJ/Fluoropolymer
Heater Cable Type
Jacket
Option Type
Process Tube
Wall Thickness
035 = .035"
ATPVC 3
049 = .049"
PE
065 = .065"
TPU
53 = HPT 10-2 (28 W/m) @ 230V
1
= 1 mm
1.5 = 1.5 mm
J = Hastaloy C276
K = Inconel 825
Notes . . .
R = 316H SS Seamless
1. Seamless tubing has a standard quality K3, other qualities are
available on special request. Tubing meets the ASTM standards,
tubing that meets DIN standards is available on special request.
X = Special
2. Monel and Inconel are trademarks of Inco Alloys International, Inc.
Heating Cable Certifications/Approvals . . .
3. Black ATPVC is standard, other jacket materials are available. ATPVC
is similar to PVC with improved low temperature flexibility.
European Organisation for Electrotechnical
Standardisation
Hazardous (Classified) Locations
II 2 G/D EEx e T2 to T6
02 ATEX 012337X
Factory Mutual Research
Hazardous (Classified) Locations
HPT has additional hazardous area approvals including:
• DNV • Lloyd’s • SAA • JIS • CCE/CMRS
Underwriters Laboratories Inc.
Hazardous (Classified) Locations
Contact Thermon for additional approvals and specific information.
Form CLX0018U-0403
© Thermon Manufacturing Co.
Printed in U.S.A.