Larson Electronics LLC
www.LarsonElectronics.com
9419 E US HWY 175, Kemp, TX 75143 Phone: 903.498.3363 Fax: 903.498.3364 Email: [email protected]
Portable Power Disttribution - 225KVA 480 Delta to 480 Wye - 30KVA 480 Delta to 120/208Y
Part #: MPD-225K-200A-GFI.50.100.200-30K-100A-5X120.20
Made in the USA
The Larson Electronics MPD-225K -200A- GFI.50.100.200-30K-100A-5X120.20 power distribution system gives the operator several GFI
protected connectors to choose from, including (1) 50-amp, (1) 100-amp, and (1) 200-amp female pin and sleeve connectors for three
phase power and (5) 120V 20-amp duplex outlets for single phase power.
*PLEASE NOTE: ANY FREE SHIPPING OFFERS DO NOT APPLY TO POWER DISTRIBUTION PANELS, TRANSFORMERS, OR
SUBSTATIONS*
Primary voltage is brought into a NEMA 3R 225KVA 480-Delta to 480-Wye transformer to derive a neutral. This feeds a 480/277VAC 200-amp
main breaker panel that contains (1) 50-amp, (1) 100-amp, (1) 200-amp, and (1) 60-amp breaker. Each breaker in this panel protects GFI
systems, including a PGFS05456 North Shore Safety (50-amp), Bender LG2-100-480-3/4-C-4X-P GFI (100-amp) and Bender LG2-200-480-3/4D-4X-P GFI (200-amp). The GFI systems protect (1) Hubbell HBL560C7W connector with 24" cable (50-amp), (1) Hubbell HBL5100C7W
connector with 24" cable (100-amp), and (1) Hubbell M5200CS1 connector with 24" cable (200-amp). The 200-amp connector and GFI system
will be fed off the 200-amp main circuit breaker via a feed-through buss.
The 200-amp main breaker panel also feeds a 30 KVA 480-Delta to 120/208Y NEMA 3R transformer via (1) 60-amp breaker. This transformer
feeds a 100-amp main circuit breaker panel that contains (5) 20-amp breakers, protecting (5) 120VAC 20-amp GFCI duplex receptacle boxes
with waterproof covers.
Unlike many portable power distribution boxes made of plastic and utilizing thin gauge, low grade metals in their construction, this unit is
designed for serious use and is ruggedly constructed to withstand demanding conditions and heavy duty industrial applications. The transformer
and load assembly is mounted on a 3/16" thick carbon steel mounting platform and the load center/distribution assembly is mounted to the
standard 2" x 2" x 1/8" square carbon steel tubing frame, resulting in an extremely stable, durable and well protected power distribution platform.
This model is equipped with forklift skid pockets, locking polyurethane casters, and a top located lifting eyelet allows easy lifting with cable or
chain hooks. This can be replaced with stainless steel, hot dip galvanized steel, or aluminum depending on the customer’s needs for an
additional cost. Larger units are available upon request, and can be equipped with skids or trailer mounted.
Applications:
This power distribution system is ideal for indoor or outdoor use and applications including but not limited to, construction sites, plant
maintenance, plant turnarounds, shows, exhibits, and shipyard operations. These power distribution systems are popularly used in applications
where external power sources are often necessary. We also offer class rated transformers for use within explosion proof and hazardous location
environments.
Larson Electronics' Larson Electronics is a manufacturer and as such can build portable transformer systems to your specifications. Although we
carry several models of power distribution transformers, we can deliver custom ordered units almost as quickly as our prebuilt units If this model
does not meet your needs, please contact us at 1-800-369-6671 or [email protected] to discuss your specific requirements.
Transformer is grounded to the frame and we provide a grounding lug on the frame for the earth ground. ~~Please check all motor loads for dual
rated motors that will work 208 or 240. ~~
Page: 1
Larson Electronics LLC
www.LarsonElectronics.com
9419 E US HWY 175, Kemp, TX 75143 Phone: 903.498.3363 Fax: 903.498.3364 Email: [email protected]
Specifications / Additional Information
MPD-225K-200A-GFI.50.100.200-30K-100A-5X120.20 Power
Distribution System
Features:
Line In:480 VAC Three Phase
Max Primary OCP: 270 amps at 480V
Transformer 1: 225KVA - 480D to 480Y N3R
Max Secondary OCP: 83 amps at 208Y
Secondary Panel 1: 200A MCB with 50A, 100A, 200A and 60A
breakers
Certification: UL 1640
Ground Fault Interrupter 1:North Shore PGFS05456 (50A)
Ground Fault Interrupter 2:Bender 100A LG2-100-480-3/4-C-4X-P
GFI (100-amp)
Ground Fault Interrupter 3:Bender 200A LG2-200-480-3/4-D-4X-P
GFI (200-amp)
Secondary Connector 1:Hubbell HBL560C7W connector (50A – GFCI
protected
Secondary Connector 2:Hubbell HBL5100C7W connector (100A –
GFCI protected)
Secondary Connector 3:Hubbell M5200CS1 connector (200A – GFCI
protected)
Transformer 2: 30KVA 480D – 120/208Y N3R
Secondary Panel 2:100A MCB with 5X20A breakers
Special Orders- Requirements
Secondary Panel 2 Outlets:5 X 120V 20A GFCI duplex receptacles
Contact us for special requirements
Form Factor: Powder coated steel frame w/ skid pockets, top pick
eyes & 8" locking casters
Toll Free: 1-800-369-6671
Weight: 1680 lbs
Intl: 1-903-498-3363
Dimensions: 84”-L x 42”-W x 64”-H
E-mail: [email protected]
*All grounding shall comply with state and local codes and meet the
minimum requirements of the National Electronic Code section 250*
Scroll Down to Purchase-
Part #: MPD-225K-200A-GFI.50.100.200-30K-100A-5X120.20 (105047)
Links (Click on the below items to view):
- Manual
Page: 2