Installation technique
Lighting time switch IL8811.41/100, SL8811.41/100
for fluorescent lamps with an electronic ballast unit
0222129
· VDE 0632 part 102
· Devices available in 2 enclosure versions:
IL 8811: depth 58 mm, with terminals at the bottom for
installation systems and industrial distribution
systems according to DIN 43 880
SL 8811: depth 98 mm, with terminals at the top for cabinets
with mounting plate and cable duct
· For controlling a maximum of 20 fluorescent lamps with an
electronic ballast unit
· Control of bright and dimmed phase timing and operating time
· Time setting for the bright phase
· Reswitching of the bright phase possible
· Variable degree of dimness
· Remote control inputs for continuous light and dimmed light
· With permanent light switch
· Can be used in combination with Siemens dyn. electronic ballast
unit 5LZ ... - 4 A; information about other lamps available on request
· Width 35 mm
Circuit diagrams
A1 13 14 T
A1
A2
A1
A2
T
13
+
A2
T
14
13
-
+
Approvals and marking
M7861
B2
M7860
B1
A1 13 14 T
+
-
IL 8811.41/100,
SL 8811.41/100
Applications
14
Staircase lighting time switch for controlling fluorescent lamps.
Aim: to conserve energy. When the bright phase is over, the staircase is
provided with dimmed light in accordance with DIN 18015 (draft). The
life of the fluorescent lamp can be extended by using the electronic ballast
unit.
-
Application examples:
A2
+
-
IL 8811.41,
SL 8811.41
Corridor lighting in old peoples homes
During dinner time between 17.00 and 19.00 p.m. the corridor lights
should be permanently switched on via a switch clock (contact B1). With
switch 2 the light is dimmed between 19.00 and 20.00 p.m. while the
local push button allows to activate bright light. At 22.00 p.m. the light
goes off and can be switched on via the local buttons.
Function diagram
All technical data in this list relate to the state at the moment of edition. We reserve the right
for technical improvements and changes at any time.
1
IL 8811.41/100, SL 8811.41/100 / 21.11.01 bzd
Applications
Technical data
Corridor lighting in hospitals
During certain periods like lunch time, visiting time, shift change, doctor's
round the light is switched on bright. During rest time, afternoon and
night the light is dimmed. Using the locals push buttons the bright light
can be activated individually. In the case of emergency a nurse can switch
to bright light with switch B1 (no time limit).
Weight
IL 8811.41/100:
SL 8811.41/100:
Dimensions
Width x height x depth
IL 8811.41/100:
SL 8811.41/100:
Note
The input (A1) and the pushbutton input (T) must be connected to the
same phase (see connection example).
Technical data
Time range / bright phase:
Repeat accuracy:
Operating time:
Degree of dimness:
Nominal voltage UN:
Control inputs B1, B2:
Voltage range:
Nominal consumption:
+ terminal:
- terminal:
Nominal frequency:
Glow lamp load parallel
to the pushbutton:
130 g
175 g
1 ... 10 min
± 2 % of the full scale value
30 min (fixed period)
90 ... 10 %
AC 230 V
AC 230 V (see Connection examples)
0,8 ... 1,1 UN
5,5 VA
DC 10 V by electronic ballast unit
DC 1 - 10 V from IL 8811
max. 20 electronic ballast units can
be connected to the + - terminals
50 / 60 Hz
35 x 90 x 58 mm
35 x 90 x 98 mm
Standard type
IL 8811.41/100 AC 230 V 50/60 Hz
· remote control inputs for continuous light and dimmed light
· Output:
1 NO contact
· Nominal voltage U N:
AC 230 V
· Width:
35 mm
SL 8811.41/100 AC 230 V 50/60Hz
· remote control inputs for continuous light and dimmed light
· Output:
1 NO contact
AC 230 V
· Nominal voltage U N:
· Width:
35 mm
Connection examples
+
L
N
10 mA
Contacts
IL 8811.41, SL 8811.41:
Thermal current Ith:
Switching capacity with
fluorescent lamp load
including electronic
ballast unit:
Electrical life
AC 15 at 3 A, AC 230 V:
Short circuit strength
max. fuse rating:
1 NO contact, delayed
10 A
B1
see connection diagrams
EN 60 947-5-1
5 x 10 4 switching cycles
10 A gL
A1
Housing:
Vibration resistance:
Climate resistance:
Wire connection:
Wire fixing:
Mounting:
A2
T
+
14
1
2
EVG
3
4
M6974_b
Connection example 1:
One lamp: Max. 10 electronic ballast units with 16 / 32 W or 6 electronic
ballast units with 58 W
Two lamps: Max. 5 electronic ballast units with 16 / 32 W or 3 electronic
ballast units with 58 W
Continuous operation
- 20 ... + 45°C
4 kV (air)
10 V/m
2 kV
+
L
N
13
--------- only for IL8811.41/100 and SL8811.41/100
4 kV / 2
3
4
EN 60 947-5-1
General data
Operating mode:
Temperature range:
Clearance and creepage
distances
overvoltage category/
contamination level:
EMC
Electrostatic discharge:
HF irradiation:
Fast transients:
Surge voltages
between
wires for power supply:
between wire and ground:
Interference suppression:
Degree of protection:
B2
IL8811
SL8811
EVG
...
Output
1
2
IEC 60 664-1
EN 61 000-4-2
EN 61 000-4-3
EN 61 000-4-4
2 kV
EN 61 000-4-5
4 kV
EN 61 000-4-5
Limit value class B
EN 55 011
Housing:
IP 40
EN 60 529
Terminals: IP 20
EN 60 529
Thermoplastic with V0 behaviour
according to UL subject 94
Amplitude 0,35 mm
EN 60 068-2-6
frequency 10 ... 55 Hz
20 / 045 / 04
EN 60 068-1
2 x 2,5 mm2 solid or
2 x 1,5 mm2 stranded ferruled
DIN 46 228-1/-2/-3
Flat terminals with self-lifting
clamping piece
EN 60 999
DIN rail
EN 50 022
2