GEC/GES/GEH
24 VDC
Commander2 Series Low
Frequency Evacuation Signals
Applications
SERIES
The Commander2 Series is a low profile strobe, horn or horn/strobe
combination that offers dependable audible and audible/visual
alarms and the absolute lowest current available.
The GE Series is available in fixed candela options of 15/75 and
177.
The Commander2 Series horn offers a continuous or synchable
temporal three in 2400Hz and mechanical tone, a chime and whoop
tone. All tones are easy for the professional to change in the field by
using switches.
The GE Series has a minimal operation current and has a minimum
flash rate of 1Hz regardless of input voltage.
Product Listings
The Commander2 Series is shipped with the standard 4" mounting
plate which incorporates the popular Super-Slide® feature that
allows the installer to easily test for supervision. The product also
features a locking mechanism which secures the product to the
bracket without any screws showing.
The Commander2 Series also features the patented Checkmate® Instant Voltage Verification feature which allows the installer to
check the voltage drop draw and match it to the blueprint.
The GE Series appliances are ANSI/UL 464, ANSI/UL 1971 and/or
ANSI/UL 1638 listed for use with fire protective systems and are
warranted for three years from date of purchase.
• ANSI/UL 464, ANSI/UL 1971 and/or ANSI/UL 1638 Listed
• CSFM: 7135-0569:122 (GEH-24 & GEC-24)
7125-0569:123 (GES-24)
7135-0569: 130 (GEH-12)
• MEA: 285-91-E-XV
Patents
• 7,375,617 May 20, 2008
Standard Features
Product Compliance
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
Nominal voltage 24VDC
Fixed candela options of 15/75 and 177
GEH horn is available in 12VDC or 24VDC
Super-Slide® Bracket - ease of supervision testing
Checkmate® - instant voltage verification
Unit Dimensions: 5” (12.7 cm) high x 4.5” (11.43 cm) wide x
2.5” (6.35 cm) deep
Synchronize strobe and/or horn with Gentex AVSM Control Module
Prewire entire system, install mounting bracket, then install signals
Documented lower installation and operating costs
Input terminals 12 to 18 AWG
Switch selection for high or low dBA
Switch for chime, whoop, mechanical and 2400Hz tone
Switch for continuous or temporal 3 (not available on whoop tone)
Tamperproof re-entrant grill
Surface mount with the GSB (Gentex Surface Mount Box)
Silence horn while strobes remain flashing
Faceplate available in red or off-white
NFPA 72
Amer icans with Disabilities Act (ADA)
IBC/IFC/IRC
City & State Ordinances/Laws/Regulations
Quality Management System is cer tified
to: ISO 9001:2008
GEH 12VDC and 24VDC Low Profile Evacuation Horn
Model
Number
GEH12-R
GEH12-W
GEH24-R
GEH24-W
Par t
Number
904-1239-002
904-1241-002
904-1205-002
904-1207-002
Nominal
Voltage
12 VDC
12 VDC
24 VDC
24 VDC
Reverberant dBA @
10ft., per ANSI/UL 464
70-82
70-82
70-82
70-82
In Anechoic Room
dBA @ 10ft.
100
100
100
100
GES 24 VDC Low Profile Evacuation Strobe
Par t
Number
Nominal
Voltage
Strobe
Candela
GES24-177WR
904-1183-002
24 VDC
177
GES24-177WW
904-1203-002
24 VDC
177
Model
Number
GES24-15/75WR
904-1167-002
24 VDC
GES24-15/75WW
904-1187-002
24 VDC
Model Designations:
W = Wall mount
R = Red Faceplate
W = White Faceplate
All units are available in plain (no lettering).
Plain units are non-returnable.
15 (ANSI/UL 1971) /
75 (ANSI/UL 1638)
15 (ANSI/UL 1971) /
75 (ANSI/UL 1638)
ALERT bezel available
AGENT bezel available
GEC 24VDC Fixed Candela, Low Profile Evacuation Horn/Strobe
Model
Number
Par t
Number
Nominal
Voltage
Strobe
Candela
Reverberant dBA @
10ft., per ANSI/UL 464
In Anechoic Room
dBA @ 10ft.
GEC24-177WR
904-1143-002
24 VDC
177
70-82
100
GEC24-177WW
904-1163-002
24 VDC
177
70-82
100
GEC24-15/75WR
904-1127-002
24 VDC
70-82
100
GEC24-15/75WW
904-1147-002
24 VDC
70-82
100
15 (ANSI/UL 1971) /
75 (ANSI/UL1638)
15 (ANSI/UL 1971) /
75 (ANSI/UL 1638)
GE-24 Product Strobe Current Ratings (mA)
24VDC (16-33 Volts)
Candela
24VDC
UL Max1
15/75cd
63mA
67mA
177cd
96mA
213mA
GEH-12 Product Horn Decibel and Current Ratings
GE-24 Product Horn Decibel and Current Ratings
Minimum dBA
@ 10ft. per
ANSI/UL 464
(HIGH)
76
Minimum dBA
@ 10ft. per
ANSI/UL 464
(LOW)
69*
29
Temp 3 2400Hz
Temp 3 Mechanical
75
68*
26
Temp 3 Chime
62*
60*
Continuous 2400Hz
79
Continuous Mechanical
Continuous Chime
Whoop
78
Horn Mode
Temp 3 2400Hz
Minimum dBA
@ 10ft. per
ANSI/UL 464
(HIGH)
78
Minimum dBA
@ 10ft. per
ANSI/UL 464
(LOW)
71*
Temp 3 Mechanical
76
70*
13
Temp 3 Chime
70*
66*
15
74*
29
Continuous 2400Hz
81
74*
28
78
72*
26
Continuous Mechanical
80
72*
25
63*
61*
13
Continuous Chime
70*
66*
15
71*
55
Whoop
82
69*
56
Regulated 12VDC
Max. Operating @
High Setting (mA)
Horn Mode
Regulated 24VDC
Max. Operating @
High Setting (mA)
28
25
NOTES:
• Operating temperature: 32°to 120°F (0° to 49°C). The GE Series is not listed for outdoor use.
The sound output for the temporal 3 tone is rated lower since the time the horn is off is averaged into the sound output rating. While the horn is
producing a tone in the temporal 3 mode its sound pressure is the same as the continuous mode.
• For nominal and peak current across UL regulated voltage range for filtered DC power and unfiltered (FWR [Full Wave Rectified]) power, see
installation manual. 12VDC models are DC only.
* Operating the horn in this mode at this voltage will result in not meeting the minimum ANSI/UL 464 reverberant sound level required for public mode fire protection service.
These settings are acceptable only for private mode fire alarm use. Use the high dBA setting for public mode application (not applicable when using the chime tone. The
chime tone is always private mode).
1
RMS current ratings are per UL average RMS method. UL max current rating is the maximum RMS current within the listed voltage range (16-33VDC for 24VDC units) (8-17VDC for
12VDC units). For strobes the UL max current is usually at the minimum listed voltage (16VDC for 24VDC units) (8VDC for 12VDC units). For audibles the max current is usually at
the maximum listed voltage. For unfiltered FWR ratings, see installation manual.
Tone Switch Locations
TONE
Mechanical Temporal 3
SWITCH POSITION
3
ON
ON
OFF
ON
ON
ON
OFF
OFF
OFF
OFF
2400Hz - Continuous
OFF
Chime - Continuous
OFF
Whoop
OFF
Chime - Temporal 3
Whoop
5
ON
Mechanical - Continuous
2400Hz - Temporal 3
4
ON
ON
ON
OFF
ON
OFF
ON
ON
OFF
OFF
NOTE:
• Switch Positions 1 and 2 in the OFF position to
select isolated hor n and strobe power inputs
• Switch Position 6 ON = HIGH dBA
• Switch Position 6 OFF = LOW dBA
Gentex Checkmate® Instant
Voltage Verification
Gentex Super-Slide®
Mounting Bracket
It is often necessary to confirm the
voltage drop along a line of devices. The
access holes are provided in the back of
the terminal block to allow the voltage to
be measured directly without removing
the device. Typically this would be done
at the end of the line to confirm design
criteria. Most measurements will be
taken using the S+ and S- locations
although access is provided to other
locations.
Allows the installer to pre-wire
the system, test for system
supervision, remove the signal
head until occupancy, switch
out Gentex signals without
changing mounting brackets
and has locking edge
connector for snap-in-place
installation.
NOTE: Care should be taken to not
shor t the test probes.
To remove bezel, grip both
sides of bezel and pull in a
downward and outward motion.
GEC/GES/GEH
24 VDC
SERIES
Conventional GES/GEC Series Wiring Diagrams
NOTES:
• All strobes are designed to flash as specified with continuous applied voltage. Strobes should not be used on coded or pulsing
signaling circuits. However, use of the Gentex AVSM control module or Gentex synchronization protocol is permitted to synchronize
the strobe, horn and/or mute the horn. See Technical Bulletin 014 for additional information.
• FOR SYNCHRONIZATION WIRING INFORMATION, REFERENCE AVSM CONTROL MODULE DATA SHEET (551-0031)
AND/OR AVSM CONTROL MODULE MANUAL (550-0284) FOR SYNCHRONIZATION MODULE WIRING DIAGRAMS. AVSM
CONTROL MODULE DATA SHEET AND MANUAL CAN BE OBTAINED AT http://www.gentex.com OR CALL GENTEX
CORPORATION AT 1-800-436-8391.
• When synchronizing the GEH 12VDC Series, the Gentex AVSM control module or Gentex synchronization protocol MUST be used.
Architect & Engineering Specifications
The audible and/or visible signal shall be Gentex GE Series or approved equal and shall be listed by Underwriters
Laboratories Inc. per ANSI/UL 1971, ANSI/UL 1638 and/or ANSI/UL 464. The notification appliance shall also be listed
with the California State Fire Marshal (CSFM) and the Bureau of Standards and Appeals (NYC).
The notification appliance (combination audible/visible and audible units only) shall produce a peak sound output of
100dBA or greater at 12VDC or 24VDC as measured in an anechoic chamber. The signaling appliance shall also have the
capability to silence the audible signal while leaving the visible signal energized with the use of a single pair of power
wires. Additionally, the user shall be able to select either continuous or temporal tone output with the temporal signal
having the ability to be synchronized.
The audible/visible and visible signaling appliance shall also maintain a minimum flash rate of 1Hz or up to 2Hz
regardless of power input voltage. The appliance shall also be capable of meeting the candela requirements of the ADA
(75Cd) for the combination listed (UL 1971/UL 1638) listed models. The appliance shall have an operating current of 67mA
or less at 24 VDC for the 15/75Cd for the strobe circuit.
The appliance shall be polarized to allow for electrical supervision of the system wiring. The unit shall be provided with
a mounting bracket with terminals with barriers for input/output wiring and be able to mount to a single gang or double
gang box or double workbox without the use of an adapter plate. The unit shall have an input voltage range of 16-33 volts
with either direct current of full wave rectified power.
The appliance shall be capable of test supervision without disconnecting wires, verify voltage without removing unit and
be capable of mounting to a surface back box.
24 units per carton
27 pounds per carton
Important Notice:
These materials have been prepared by Gentex Corporation ("Gentex") for informational purposes only,
are necessarily summary, and are not purported to serve as legal advice and should not be used as
such. Gentex makes no representations and warranties, express or implied, that these materials are
complete and accurate, up-to-date, or in compliance with all relevant local, state and federal laws, regulations and rules. The materials do not address all legal considerations as there is inevitable uncertainty
regarding interpretation of laws, regulations and rules and the application of such laws,
regulations and rules to particular fact patterns. Each person's activities can differently affect the
obligations that exist under applicable laws, regulations or rules. Therefore, these materials should be
used only for informational purposes and should not be used as a substitute for seeking professional
legal advice. Gentex will not be responsible for any action or failure to act in reliance upon the
information contained in this material.
551-0049-02