Download Liebert NXc UPS; 30 - 40kVA; 380/400/415V Detailed Specification

Survey
yes no Was this document useful for you?
   Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Document related concepts

Audio power wikipedia , lookup

Utility frequency wikipedia , lookup

Decibel wikipedia , lookup

Electric battery wikipedia , lookup

Electric power system wikipedia , lookup

Solar micro-inverter wikipedia , lookup

Power factor wikipedia , lookup

Ohm's law wikipedia , lookup

Stepper motor wikipedia , lookup

Electrical ballast wikipedia , lookup

Electrification wikipedia , lookup

Electrical substation wikipedia , lookup

Resistive opto-isolator wikipedia , lookup

Power inverter wikipedia , lookup

Schmitt trigger wikipedia , lookup

Pulse-width modulation wikipedia , lookup

History of electric power transmission wikipedia , lookup

Rectifier wikipedia , lookup

Power engineering wikipedia , lookup

Islanding wikipedia , lookup

Current source wikipedia , lookup

Surge protector wikipedia , lookup

Uninterruptible power supply wikipedia , lookup

Stray voltage wikipedia , lookup

Voltage regulator wikipedia , lookup

Three-phase electric power wikipedia , lookup

Power electronics wikipedia , lookup

Opto-isolator wikipedia , lookup

Voltage optimisation wikipedia , lookup

Switched-mode power supply wikipedia , lookup

Alternating current wikipedia , lookup

Variable-frequency drive wikipedia , lookup

Buck converter wikipedia , lookup

Mains electricity wikipedia , lookup

Transcript
Liebert NXc UPS; 30 - 40kVA; 380/400/415V
Detailed Specification
1.1
Conformance And Standards
The UPS has been designed to comply with the European and international standards listed in Table 1-1.
Table 1-1
European and international standards
Item
Normative reference
General safety requirements for UPS
EN62040-1/IEC62040-1/AS62040-1
EMC requirements for UPS
EN62040-2/IEC62040-2/AS62040-2
Method of specifying the performance and test requirements of UPS
EN62040-3/IEC62040-3/AS62040-3 (VFI SS 111)
Note: The product standards in this table incorporate relevant compliance clauses with generic IEC and EN standards for safety
(IEC/EN/AS60950), electromagnetic emission and immunity (IEC/EN/AS61000 series) and construction (IEC/EN/AS60146 series
and 60529)
1.2
Environmental Characteristics
Table 1-2 Environmental characteristics
Item
Noise within 1m (in the front)
Altitude
Relative humidity
Operating temperature
Storage and transport ation
temperature for UPS
Over-voltage level
Pollution level
1.3
Unit
dB
m
%RH
°C
°C
Rated power (kVA)
30kVA
40kVA
74
76
≤ 1000 (derate power by 1% per 100m when above 1000m)
0 ~ 95%, non condensing
0 ~ 40°C (Note: Battery life is halved for every 10°C increase above 20°C)
-40°C ~ +70°C
Overvoltage level 2
Pollution level 2
Mechanical Characteristics
Table 1-3 Mechanical characteristics
Item
Unit
Dimensions (W × D × H)
mm
Net weight
Gross weight
Color
Protection degree, IEC (60529)
kg
kg
Black
Rated power (kVA)
30kVA
40kVA
6000 × 850 × 1600
215
260
ZP7021
IP20 (front door open or closed)
1.4
Electrical Characteristics (Input Rectifier)
Table 1-4
Item
Rated AC input voltage 1
Input voltage range2
Frequency 2
Rated power (kVA)
Unit
30kVA
Input current
Vac
Vac
Hz
kW/kVA, full load (half
load)
A, rated3
Harmonic current distortion
THDI% FL
Power factor
Rectifier AC input (mains)
40kVA
380/400/415, 3-phase 3-wire (+PE) TN power distribution system
228 ~ 437
50/60 (range: 40 ~ 70)
0.99 (0.98)
41.2
54.9
Linear full load < 2.8% (battery float
Linear full load < 3.1% (battery float
charge)
charge)
Non-linear full load < 4.75%
Non-linear full load < 4.95% (battery
boost charge)
(battery boost charge)
10s to reach full rated current (selectable 5s through 30s in 5-second
intervals)
Duration of progressive
s
power walk-in
Note:
1.. Rect ers operate at any of the rated supply voltages and frequencies without further adjustment.
2. At 324V input mains the UPS maintains the specified output voltage at rated load without discharging a previously charged
battery.
3.. IEC620 -3/EN50091-3: at rated load and input voltage 400V, battery fully charged
1.5
Electrical Characteristics (Intermediate DC Circuit)
Table 1-5 Battery
Item
Rated battery bus voltage
Quantity of lead-acid cells
(nominal)
Float voltage
Rated power (kVA)
Unit
30kVA
432
Cell
36 (12Vdc)
V/cell (VRLA)
2.27 (selectable from 2.2V/cell to 2.3V/cell)
Constant current and constant voltage charge mode
Temperature
compensation
Ripple voltage
mV/°C/cl
–3.0 (selectable from 0 to – 5.0 around 25°C or 30°C, or inhibit)
%
Boost voltage
V/cell (VRLA)
≤ 1.414%
2.35 (selectable from 2.3 to 2.35)
Constant current and constant voltage charge mode
Float-boost current trigger 0.050C10 (selectable from 0.001 to 0.070)
Boost-float current trigger 0.010C10 (selectable from 0.001 to 0.025)
24h safety time timeout (selectable from 8h to 30h)
Boost mode inhibit also selectable
1.60 ~ 1.85
2.35
Constant current and constant voltage charge mode
Programmable automatic trigger or inhibit of boost mode
Boost control
1.6
40kVA
Vdc
EOD voltage
V/cell (VRLA)
Battery charge
V/cell
Electrical Characteristics (Inverter Output)
Table 1-6
Item
Rated AC voltage 1
Frequency2
Unit
Vac
Hz
Inverter output (to critical load)
Rated power (kVA)
30kVA
40kVA
380/400/415 (3-phase 4-wire, with neutral reference to the bypass neutral)
50/60
Item
Rated power (kVA)
Unit
Overload
Non-linear load
capability3
Steady state voltage
stability
Transient voltage
response4
Total harmonic voltage
30kVA
40kVA
%
For linear load requirement:
< 105%, continues;
105 ~ 125% of rated load, 5min;
125 ~ 150% of rated load, 1min;
> 150%, 200ms
%
100%
%
±0.56% for balanced three phase load;
±1.29% for unbalanced load
%
±5% for 100% rated linear load step
%
±0.26% for balanced three phase load;
±1.39% for unbalanced load
0.86% (0 ~ 100% linear load);
0.99% (0 ~ 100% linear load);
3.74% (0 ~ 100% non-linear load)
4.1% (0 ~ 100% non-linear load)
Rated frequency ±0.5, ±1, ±2, ±3 (optional)
Synchronisation window
Hz
Slew rate (max. change
Hz/s
Setting range: 0.1 ~ o.6 (UPS module), 0.6 (parallel system)
rate of synchronisation
frequency)
Note:
1.. Fact y set to 380V. 400V or 415V selectable by service engineer.
2.. Fact y set to 50Hz. 60Hz selectable by service engineer. Note that the system frequency can be changed only when the UPS
is on bypass. It is strictly prohibited to change the system frequency when the UPS is on inverter.
3.. EN 500 -3 (1.4.58) crest factor 3:1, non-linear load.
4.. IEC 620 -3/EN 50091-3 also for 0% ~ 100% ~ 0% load transient. Transient recovery time: return to within 5% of steady state
output voltage within half a cycle
1.7
Electrical Characteristics (Bypass Input)
Table 1
Item
Rated AC voltage
Rated
current
Unit
1
380V
400V
415V
Vac
A
A 39
A
Overload
%
Frequency2
Hz
Bypass voltage tolerance
%Vac
-
7
Bypass input
Rated power (kVA)
30kVA
40kVA
380/400/415, 3-phase 4-wire, sharing neutral with the rectifier input and providing neutral
reference to the output
41
54
52
37
50
Based on nominal voltage and rated load current under apparent power:
< 105%, continues;
105 ~ 125% of rated load, 5min;
125 ~ 150% of rated load, 1min;
150 ~ 400% of rated load, 1s;
> 400%, 200ms
50/60
Upper limit: +10%, +15% or +20%, default: +15%;
Lower limit: -10%, -20%, -30% or -40%, default: -20%
Bypass frequency
%
±10% or ±20%, default: ±20%
tolerance
Synchronisation window
Hz
Rated frequency ±0.5, ±1, ±2, ±3 (optional)
Note:
1.. Fact y set to 380V. 400V or 415V selectable by service engineer.
2.. Fact y set to 50Hz. 60Hz selectable by service engineer
1.8
Loss
Table 1-8 Loss
Item
Rated normal mode
(empty load)
Rated normal mode (full
load)
Unit
Rated power (kVA)
30kVA
40kVA
kW
1.107
1.107
kW
1.758
2.344