Survey
* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project
* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project
The battery is replaced on the 1609-U750, 1609-U1000 and 1609-U1500 by removing the cover of the unit and unscrewing the top two screws on the plate behind the cover. Disconnect the battery and remove from housing and replace with new batteries. Note – Each UPS takes two of the batteries noted below. The 1609-U750N replacement battery is part # 1606-XLSBAT1. The 1609-U1000N and 1609-U1500N do not have replacement batteries available from Rockwell Automation / Allen Bradley, but they can be obtained from a third party source as noted below. The Chart below shows the replacement batteries for the 1609-U1000 and 1609-U1500. The last two columns are examples of a manufacture and the battery that the customer can use. The customer should be able to use any manufacturer as long as it meets the voltage and ampere-hour requirements of the unit. Note - the connectors that are attached to the existing batteries should be kept for use with the new replacement batteries. UPS Part Number 1609-U1000N 1609-U1500N* Replacement Battery 12 V 12 AH (need to of these batteries in series) 12V 17AH (need to of these batteries in series) Manufacturer Example Manufacturer Part No. CSB Battery GP12120 CSB Battery GP12170 * Note - keep the fuse and the connector from the old battery and connect them to the new replacement battery.