ChenYang
Version 2
Released in May 2016
Dr.-Ing. habil. Jigou Liu
Technologies GmbH & Co. KG
3-Phase 3-Wire AC Voltage Sensor CYVS13-xnU0
The CYVS13-xnU0 AC Voltage Sensor/Transducer works according to electromagnetic
induction and is designed for applications to measurement and monitoring of 3-Phase 3-Wire
AC voltage. The output signals (DC voltage or current) of this transducer are proportional to the
average effective value (RMS) of input AC voltages. They are suitable for general applications
such as fixed frequency voltage supplies and sinusoid voltages etc.
Specifications
Rated input voltage (Ux)
Linear measuring range
Overload capacity
Frequency of Input voltage
Input resistance
Output signals DC
Measuring accuracy
Load capacity
Response time
Thermal drift
Power supply
Static current
Isolation
Isolation withstanding voltage
Operating temperature
Storage temperature
Relative humidity
Protection of Case
Material of Case
Mounting
Case Style
MTBF
Unit weight
10V-500V AC
0 - 1.2 times of rated input voltage
2 times of rated input voltage
Typ. 50Hz, 60Hz, max. 5kHz
Ri=0.667Ux x 1kΩ /V, Ux : input voltage
0-5V, 0-10V, 0-20mA, 4-20mA DC
0.5%
voltage output: 5mA; current output: 6V
≤300ms
voltage output : 250ppm/°C; current output: 350ppm/°C
+12VDC, +24VDC
Voltage output: 8mA; 0-20mA output: 12mA; 4-20mA output: 35mA
Isoltion between input and output, power supply at the output
2.5 kV DC, 1min
-10°C ~ +60°C
-25°C ~ + 70°C
10% ~ 90%
IP20
ABS (according to UL94V-0)
DIN Rail
U0 without aperture
50000h
90g
Definition of Part number:
CYVS13
(1)
-
x
n
U0
(2)
(3)
(4)
-
0.5
-
(5)
(6)
(1)
(2)
(3)
(4)
(5)
Series name
Output signal
Power supply
Case
style
Accuracy
class
U0
0.5%
CYVS13
x=1: 0-5VAC
x=3: 0-5V DC
x=4: 0-20mA DC
x=5: 4-20mA DC
x=8: 0-10V DC
Markt Schwabener Str. 8
D-85464 Finsing
Germany
n=2: +12V DC
n=4: +24V DC
m
(6)
Input Voltage range
(m)
m=10V-500V AC
n=4: +24V DC
Tel: +49 (0)8121-2574100
Fax: +49 (0)8121-2574101
Email: [email protected]
http://www.chenyang-gmbh.com
ChenYang
Version 2
Released in May 2016
Dr.-Ing. habil. Jigou Liu
Technologies GmbH & Co. KG
Example 1:
CYVS13-32U0-0.2-100V, 3-phase 3 wire AC voltage sensor with
Output signal: 0-5V DC
Power supply: +12V DC
Rated input voltage: 0-100V AC
Example 2:
CYVS13-54U0-0.5-100V, 3-phase 3 wire AC voltage sensor with
Output signal: 4-20mA DC
Power supply: +24V DC
Rated input voltage: 0 -100V AC
DIMENSIONS (mm)
View of A Direction
Input
terminal
3
6
9
2
5
8
1
4
7
12
11
10
A
Input
Terminal
Case
cover
DIN Rail
Power LED
Output
terminal
Spring bolt
Dimensions: 105mm x 23mm x 70.5mm
Markt Schwabener Str. 8
D-85464 Finsing
Germany
Tel: +49 (0)8121-2574100
Fax: +49 (0)8121-2574101
Email: [email protected]
http://www.chenyang-gmbh.com
Output
Terminal
ChenYang
Version 2
Released in May 2016
Dr.-Ing. habil. Jigou Liu
Technologies GmbH & Co. KG
CONNECTIONS
Wiring of Terminals for voltage output:
Ua 1
IN
Ub 3
OUT
7 Uab
1,3,4:
8 Ubc
7,8,9:
9 Uca
Uc 4
10:
11:
11 GND
10
+V
Voltage Inputs
Ua, Ub, Uc
voltage Outputs
Uab, Ubc, Uca
Power supply
GND
11
GND
7: AB-Phase Output voltage Uab
1: A-Phase Input
8: BC-Phase Output voltage Ubc
3: B-Phase Input
CYVS13
4: C-Phase Input
9: CA-Phase Output voltage Uca
V
V
V
11: GND
10: V+: +12V, +24V
Wiring of Terminals for Current Output:
Ua 1
IN
Ub 3
OUT
7 Iab
1,3,4:
8 Ibc
7,8,9:
9 Ica
Uc 4
10:
11:
11 GND
10
+V
Voltage Inputs
Ua, Ub, Uc
Current Outputs
Iab, Ibc, Ica
Power supply
GND
11
GND
7: AB-Phase Output Current
1: A-Phase Input
8: BC-Phase Output Current
3: B-Phase Input
4: C-Phase Input
Iab
Vab
Ibc
Vbc
CYVS13
9: CA-Phase Output Current
Vca
Ica
11:
≤ 250 Ω
≤ 250 Ω
GND
10: V+: +12V, +24V
Markt Schwabener Str. 8
D-85464 Finsing
Germany
Tel: +49 (0)8121-2574100
Fax: +49 (0)8121-2574101
Email: [email protected]
http://www.chenyang-gmbh.com
≤ 250 Ω