ANNEX (A) COMPLIANCE SHEET
The following Technical data shall be furnished and filled by the bidders:
1-GENERAL FOR 750KVA GENERATOR
#
UNDP specifications
Offered specification (Please
State clearly specifications
offered)
Original manufacturer (Local Assembled
1- Make:
Not acceptable)
Maximum:55/C
2- Ambient temperature :
Minimum:-10/C
around 60% at maximum temperature
3- Relative Humidity :
1000M above MSL
4- Altitude:
5- System Voltage :
400V
3PH
6- No of phase :
50Hz
7- Frequency:
one year ,1000h / operation
8- Guarantee:
9- Generator output Range 810KVA prime stand by not less
750KVA
400A 4pole
10 Maine MCCB breaker
8hour operation base tank
11- Daily base tank
2-ENGINE
1-
Description
Make:
2-
Type:
34-
UNDP specifications
Original manufacturer (Local
Assembled Not acceptable)
Cummins, Caterpillar, Perkins,
Volvo, or equivalent
12 cylinder,
1500
No of cylinders :
RPM:
Prime :
5- Standby :not less than 750KVA 810KVA
DG set
Mechanical /Electrical governor
6- Type of Governor:
as per International standard
7- Overload rating:
Standard water separator filter
8- Fuel filter :
Diesel
9- Type of fuel :
24 V DC Electrical
10- Type of starting
Radiator cooled engine
11- Type of cooling:
12-
Aspiration
12- TYPE:
12- Guarantee Period:
13- Guaranteed fuel
consumption/hour
Turbocharged
After cooled
Silencer/ soundproof canopy
. One year or 1000 hours
whichever comes first.
Offered specification
13-
75%
130.40 (litre/hr)
100%
165
(litre/hr)
14- Submit Manufacturer
certification :
15- Submit Operation and
maintenance manual
16- Submit Detail drawing
brochure catalogue
3- ALTERNATOR
Description
Make:
Type:
UNDP specifications
European, or Equivalent
STAMFORD, LEROY SOMER ,
MARATHON or equivalent
Rated Voltage :
Rated KVA :
Rated power factor :
No. of Phase
:
Frequency:
Type of excitation:
0.4KV
750KVA
between 0.8 and 1
3Ph
50Hz
Percentage regulation :
IP :
Insulation type :
Bearing :
AVR type :
Submit Manufacturer certification :
Submit Detail drawing brochure
catalogue :
+ -5%
not less than 23
class H
Single
Digital
3-CONTROL PANEL
UNDP specifications
Make:
Type:
Control Panel Control panel is
manufactured with 14/16 gauge
CRCA sheet
and is powder coated for weather.proof and long lasting finish
The control panel consists of the
following parts:
Offered specification
Brushless, self-regulation and
separately exited
UNDP specifications
European, or Equivalent
Power Command 3.3 controller
Aluminum bus bars with suitable
capacity with incoming/
outgoing terminals
Indicating lamps for ‘Load ON’
and ‘Set Running’
Instrument fuses duly wired and
ferruled
Air Circuit Breakers (ACBs) of
suitable rating with overload and
short circuit protections
generator set monitoring:
metering and control system
Offered specification (Please
State clearly specifications
offered)
with LCD display designed to
meet the demands of today’s
engine driven generator sets
Microprocessor / relay based
AMF control
panel, Battery charger, Auxiliary
output relays and remote
annunciators, Others: Trolley
mounted mobile sets
State whether comply or not
Submit Manufacturer certification :
Submit Detail drawing brochure
catalogue:
4-Encluser
UNDP specifications
Make:
UNDP specifications
Original manufacturer (Local
Assembled Not acceptable)
Typical Enclosed Genset Dimensions:
Length
Width
Height
8000 (mm)
2600 (mm)
3000 (mm)
Wet Weight (KG)
11900 (KG)
Standard Fuel tank
Capacity (litre)
Noise Level :
990 (litre)
75 dBA @ 1mtr at at a distance.
Offered specification
ANNEX (B) COMPLIANCE SHEET
The following Technical data shall be furnished and filled by the bidders:
2-GENERAL FOR 500KVA GENERATOR
#
UNDP specifications
1-
Make:
2-
Ambient temperature :
3456789-
Relative Humidity :
Altitude:
System Voltage :
No of phase :
Frequency:
Guarantee:
Generator output Range
10 Maine MCCB breaker
11- Daily base tank
2-ENGINE
Description
1- Make:
2-
Type:
34-
Original manufacturer (Local Assembled
Not acceptable)
Maximum:55/C
Minimum:-10/C
around 60% at maximum temperature
1000M above MSL
400V
3PH
50Hz
one year ,1000h / operation
500KVA prime stand by not less 550
KVA
400A 4pole
8hour operation base tank
UNDP specifications
Original manufacturer (Local
Assembled Not acceptable)
Cummins, caterpillar, Perkins,
Volvo, or equivalent
6 inline
1500
250KVA
No of cylinders :
RPM:
Prime :
5- Standby :not less than 275KVA
DG set
Electronic
6- Type of Governor:
as per International standard
7- Overload rating:
Standard water separator filter
8- Fuel filter :
Diesel
9- Type of fuel :
24Volt DC (star connection )
10- Type of starting
Radiator–fan cooled–fan to be
11- Type of cooling:
driven By the engine shaft.
Turbocharge red
12- Indicator
Fuel
Lube oil
13- Guaranteed fuel and oil
consumption/hour
25%
50%
75%
100%
14- Submit Manufacturer
certification :
15- Submit :
Offered specification (Please
State clearly specifications
offered)
Operation and maintenance
Offered specification
Fuel
Lube oil
16- Submit Detail drawing
brochure catalogue
3- ALTERNATOR
Description
Make:
Type:
UNDP specifications
European, or Equivalent
STAMFORD,LEROY SOMER
,MARATHON or equivalent
Rated Voltage :
Rated KVA :
Rated power factor :
No. of Phase
:
Frequency:
Type of excitation:
0.4KV
1500KVA
between 0.8 and 1
3Ph
50Hz
Percentage regulation :
IP :
Insulation type :
Bearing :
AVR type :
Submit Manufacturer certification :
Submit Detail drawing brochure
catalogue :
+ -5%
not less than 23
class H
single
digital
3-CONTROL PANEL
UNDP specifications
Make:
Submit Manufacturer certification :
Submit Detail drawing brochure
catalogue:
Offered specification
Brushless, self-regulation and
separately exited
UNDP specifications
European, or Equivalent
4-Encluser
UNDP specifications
Make:
Offered specification
UNDP specifications
Offered specification
Original manufacturer (Local
Assembled Not acceptable)
70 dB at a distance of 1.5 meter.
Noise Level :
STANDARD ITEMS: • Mainline Circuit Breaker • Generator Set mounted on Heavy Duty Steel Base
Frame • Anti-Vibration Pads between Engine/Alternator and Frame • 8 to 10 Hour Base Fuel Tank (up to
600 kW) • Forklift Pockets within Base Frame (up to 400 kW) • Battery Charging Alternator
Note: The control panel shall have the following provisions for the control of DG Set:
1. MCCB's as per BOQ & AMF panel.
2. Master engine control which for OFF/AUTO/MANUAL/TEST with a facility for
starting and stopping of the set.
4. Selectable Multifunction meter with the generator own control panel.
5. Engine control monitor.
6. Alternator voltage monitor.
7. D.C. Control relays, timers.
8. Engine protection system for low oil lubricating pressure and high water temperature.
9. Engine hours run counter.
10. Control fuses.
11. Lifting Hooks.
12. Gland Plates.
13. Power/Control Contactors.
14. Earthing studs
ANNEX (C) COMPLIANCE SHEET
The following Technical data shall be furnished and filled by the bidders:
3-GENERAL FOR 250KVA GENERATOR
#
UNDP specifications
1-
Make:
2-
Ambient temperature :
3456789-
Relative Humidity :
Altitude:
System Voltage :
No of phase :
Frequency:
Guarantee:
Generator output Range
10
TYPE:
11 Maine MCCB breaker
12- Daily base tank
Original manufacturer (Local Assembled
Not acceptable)
Maximum:55/C
Minimum:-10/C
around 60% at maximum temperature
1000M above MSL
400V
3PH
50Hz
one year ,1000h / operation
250KVA prime stand by not less
260KVA
SILENT
400A 4pole
8hour operation base tank
2-ENGINE
Description
1- Make:
2-
Type:
34-
No of cylinders :
RPM:
Prime :
5- Standby :not less than 250KVA
DG set
6- Type of Governor:
7- Overload rating:
8- Fuel filter :
9- Type of fuel :
10- Type of starting
11- Type of cooling:
UNDP specifications
Original manufacturer (Local
Assembled Not acceptable)
Cummins, caterpillar, Perkins,
Volvo, or equivalent
6 inline
1500
250KVA
Mechanical /Electrical governor
as per International standard
Standard water separator filter
Diesel
24Volt DC (star connection )
- Water cooled, four cycle,
Turbocharged
DIRECT INJECTION
12- COMBUSTION SYSTEM
Fuel
Guaranteed
fuel
and
consumption/hour
75%
100%
Offered specification (Please
State clearly specifications
offered)
48 Litre per hour
65 Litre per hour
Offered specification
14- Submit Manufacturer certification :
15- Submit Operation and maintenance :
16- Submit Detail drawing brochure catalogue
3- ALTERNATOR
Description
Make:
Type:
UNDP specifications
European, or Equivalent
Offered specification
STAMFORD,LEROY SOMER
,MARATHON or equivalent
Rated Voltage :
Rated KVA :
Rated power factor :
No. of Phase
:
Frequency:
Type of excitation:
0.4KV
250KVA
between 0.8 and 1
3Ph
50Hz
Percentage regulation :
IP :
Insulation type :
Bearing :
AVR type :
+ 5%
not less than 23
class H
single
digital
Winding Pitch
2/3 Pitch
Radiator Cooling Air
154m³/min
Brushless, self-regulation and
separately exited
Submit Manufacturer certification :
Submit Detail drawing brochure
catalogue :
3-CONTROL PANEL
UNDP specifications
Make:
UNDP specifications
European, or Equivalent
AUTOMATIC CONTROL
PANEL : Off/Auto/Manual
selector key switch
Offered specification
UNDP specifications
Original manufacturer (Local
Assembled Not acceptable)
Offered specification
Submit Manufacturer certification :
Submit Detail drawing brochure
catalogue:
4-Encluser
UNDP specifications
Make:
OPEN DIMENSION (W x L x H) mm
OPEN WEIGHT kg
1150 x 3340 x 2320
2340 KG
CANOPY
• Modular type sound-proof canopy
• Canopy installation executed with
screw and nut, without welding
process
• Epoxy and polyester powder painted
canopy
• Canopy designed for easy maintenance
• Lockable doors on both sides of
canopy
• Emergency stop button
• Transparent panel inspection window
Noise Level :
85 dB at a distance of 1meter.
Note: The control panel shall have the following provisions for the control of
DG Set:
1. MCCB's as per BOQ & AMF panel.
2. Master engine control which for OFF/AUTO/MANUAL/TEST with a facility for
starting and stopping of the set.
4. Selectable Multifunction meter with the generator own control panel.
5. Engine control monitor.
6. Alternator voltage monitor.
7. D.C. Control relays, timers.
8. Engine protection system for low oil lubricating pressure and high water
temperature.
9. Engine hours run counter.
10. Control fuses.
11. Lifting Hooks.
12. Gland Plates.
13. Power/Control Contactors. / Earthling studs